Emerson 3000/ITR manual High Head Pressure, High Humidity and Low Humidity Simultaneously

Page 39

Alarm Descriptions

6.1.3High Head Pressure

Compressor high head is monitored with a pressure switch. One SPDT pressure switch is used for the compressor in the unit. If head pressure exceeds 360 PSIG, the switch opens the compressor contactor and sends an input signal to the control. On a self-contained system, the head pressure switch located at the compressor requires a manual reset and the alarm condition to be acknowledged on the front display panel. On a split system, the high head pressure condition is acknowledged by pressing the alarm silence button that will clear the alarm if the high head pressure condition no longer exists. On a split system, if the compressor is Off for 1 hour, the control goes into a special “cold start mode.” In the cold start mode on a call for cooling or dehumidification, the Liquid Line Solenoid Valve (LLSV) is energized. If the high pressure switch does NOT trip within 10 seconds, the control returns to normal operation of monitoring the high head pressure switch for three occurrences in a 12-hour period. It is a rolling timer; after the third high head alarm occurs and is acknowledged by the user, it will lock Off the compressor. If while in the cold start mode, the high head pressure switch DOES trip within 10 seconds of the activation of the LLSV, the control does not annunciate the alarm. The control will turn Off the LLSV and delay 10 seconds. The control will permit this occurrence two more times or a total of three times. If on the fourth try the high head pressure switch trips within 10 seconds, the control will annunciate the alarm, turn Off the LLSV, wait for the user to acknowledge the alarm and hold the compressor Off for three minutes, which is the normal short cycle control. On the third occur- rence, the control will lock the compressor Off until the control power is reset.

On air cooled systems, check for power shut Off to the condenser, condenser fans not working, defec- tive head pressure control valves, closed service valves, dirty condenser coils, and crimped lines. Also, make sure that when the compressor contactor is energized, the side switch on the contactor closes to energize the control circuit on the air cooled condenser.

On water/glycol/GLYCOOL systems, check water regulating valves. Verify water/glycol flow (are pumps operating and service valves open?). Is water tower or drycooler operating? Is the coolant tem- perature entering the condenser at or below design conditions? Is relay R5 operating during cooling to turn On the drycooler?

6.1.4High Humidity

The return air humidity has increased to the High Humidity Alarm setpoint. Is the unit setup for dehumidification (check DIP switch)? Check for proper setpoints. Does the room have a vapor barrier to seal it from outdoor humidity? Are doors or windows open to outside air? Run diagnostics to make sure the cooling system is working properly (the cooling system dehumidifies).

6.1.5High Humidity and Low Humidity (Simultaneously)

If these two alarms are displayed at the same time, the humidity input signal is lost. Dashes will be displayed for the humidity reading. The control system will deactivate humidification and dehumidi- fication. Check for a disconnected cable or a failed sensor.

6.1.6High Temperature

If the return air temperature has increased to the High Temperature Alarm setpoint, check for proper setpoints. Is the room load more than the unit can handle (is the unit capacity too small)? Run diag- nostics to make sure all cooling components are operating (compressor and/or valves).

6.1.7High Temperature and Low Temperature (Simultaneously)

If these two alarms are displayed at the same time, the temperature input signal is lost (or the humidity is out of sensor range: 15 to 85% RH). Dashes will be displayed for the temperature reading. The control system will initiate 100% cooling. Check for a disconnected cable or a failed sensor.

6.1.8Humidifier Problem Infrared Humidifiers

This alarm is activated by the high-water float switch in the humidifier pan assembly. The high- water float switch is normally closed and opens upon alarm condition. Check for drain clog and, if present, clean drain. Check for float switch stuck high; replace the switch as necessary. Check for proper operation of the humidifier water makeup valve.

Steam Generating (Canister) Humidifiers

This alarm is activated by a signal from the humidifier control indicating that the canister needs to be replaced.

33

Image 39
Contents Operation & Maintenance Manual 50 & 60Hz Page Table of Contents Standard Alarms Component Operation and MaintenanceFigures Tables Important Safety Instructions Page Glycool Chilled Glycol Cooling Systems System DescriptionsIntroduction Compressorized SystemsStartup Startup ProcedureStartup Features Operation with Icom ControlLarge and Small Displays Escape Key Down Arrow Key Liebert Icom Display Components and FunctionsIcon Key Name Function Keyboard icons and functionsNavigating Through the Liebert iCOM Display Percent System or Unit Cooling On/Off Date Sensor Reading Next Maintenance Evaporator Fan SpeedTime Most Recent Alarms Control Interface-Three Main MenusPassword is factory-set at Accessing Menus and Settings Viewing DataEntering the Password After highlighting the Password command line, pressAccessing Submenus Accessing Submenus on Small DisplaysAccessing Submenus on Large Displays Advanced Menu Unit Service Menu UnitStatus Menu System View Status Menu Unit 1 View User MenuChanging Operational Settings ServiceContacts Highlight the setting to be changed by pressing Enter Changing Liebert iCOM’s Display SettingsLiebert iCOM Service Menu Icons and Legend Graphical Data RecordNetwork Liebert iCOM U2U Ethernet Network Wiring for Unit-to-Unit Communications-U2UWiring a Liebert iCOM U2U Network Small Displays Sample Liebert iCOM network configurationsLarge Displays Wall-Mount Large DisplayCombining Large and Small Displays on a U2U Network Display Service/Network Liebert iCom Display Menu U2U network setup diagramLiebert iCOM Display Components and Functions Liebert iCOM wiring-Unit as shipped 194273 194273 P67 P66 P65 P64 P61 P63Control board U2U network setup screen Entering Network Setup InformationService Menu Unit # Viewing Multiple Units with a Networked Large DisplayAdvanced Menu Unit # Remote On / Off Display On / Off Single Unit FunctionsOperation Unit/Fan Control Start StopLoss of Power Alarm Fan Alarm / Fan Protection SettingsAutorestart Compressor Timing High Pressure AlarmDigital Scroll High Temperature Pump Down-Air Cooled with Condenser Only UnitsControl Types Proportional ControlPI Control Intelligent Control Chilled Water Only Compressor Overload Standard AlarmsAlarm Descriptions Change FilterHigh Head Pressure High TemperatureHigh Temperature and Low Temperature Simultaneously Humidifier Problem Infrared HumidifiersLow Humidity Loss of PowerLow Temperature Loss of Air FlowSet Alarms-User Menus Optional AlarmsComponent Operation and Maintenance System TestingSmoke Detector Fan Safety SwitchControl Transformer and Fuses High-Temp SensorZone leak detection kit installation scenarios Remote ShutdownDistance From Unit, feet m Belt FiltersBlower Package Fan Impellers and BearingsSuction pressures R407c Refrigeration SystemAir Distribution Suction PressureThermostatic Expansion Valve Operation AdjustmentDischarge Pressure SuperheatAir Cooled Condenser Water/Glycol Cooled Condensers Coaxial Condenser Outdoor fan/condenser configurationStartup Motorized Ball Valve-Digital Scroll CompressorControl Control MethodValve spring guide Adjusting Collar NutDrycooler Settings Aquastat settings-two-fan through four-fan drycoolersCooling Type Glycool Glycol Flow Control Compressor Functional Check Compressor ReplacementCompressor Oil Before Replacing or Returning a CompressorStandard Scroll Compressor Replacement Mechanical FailureElectrical Failure Glycol Solution Maintenance Digital Scroll Compressor Replacement ProcedureRemoving the Pan Cleaning the PanHumidifier Infrared HumidifierHumidifier Lamps Autoflush Infrared Humidifier Cleaning SystemChanging Humidifier Lamps Autoflush OperationSteam Generating Humidifier Autoflush ControlsControls 200-460 Replacing the CanisterHumidifier canister part numbers Part Capacity Number Voltage Lb/hr kg/hrDrain Tempering Feature Circuit Board AdjustmentsSymptom Possible Cause Check or Remedy TroubleshootingBlower troubleshooting Chilled water troubleshootingCompressor and refrigeration system troubleshooting Compressor and refrigeration system troubleshooting See 7.5.1 Compressor Functional Dehumidification troubleshootingGlycol pump troubleshooting Infrared humidifier troubleshootingSteam generating humidifier troubleshooting Reheat troubleshooting Monthly Maintenance Inspection Checklist Semiannual Maintenance Inspection Checklist Semiannual Maintenance Inspection Checklist Page That Ne tIti Ppor t Ti n

3000/ITR specifications

The Emerson 3000/ITR is a powerful and versatile instrument designed for industrial automation and process control applications. This modular platform integrates advanced features and technologies tailored to meet the needs of diverse industries including oil and gas, pharmaceuticals, and manufacturing.

One of the main features of the Emerson 3000/ITR is its exceptional scalability. The system can be easily expanded to accommodate growing operational demands. With its modular architecture, operators can add or remove components without significant downtime, ensuring continuous productivity. This flexibility allows businesses to adapt their systems to changing environments and requirements seamlessly.

The Emerson 3000/ITR leverages state-of-the-art communication technologies to ensure reliable data exchange between devices. With support for various protocols, including Hart, Modbus, and Profibus, the system can easily integrate with existing infrastructure. This adaptability enhances interoperability and simplifies the communication between field devices and control systems, promoting efficient data handling.

Built with robust security features, the Emerson 3000/ITR guarantees the integrity of sensitive data. The platform incorporates advanced encryption techniques and user authentication protocols to protect against potential cyber threats. This focus on security is essential in today’s digitally connected industrial environments.

Another key characteristic of the Emerson 3000/ITR is its user-friendly interface. The system is designed with operators in mind, featuring intuitive controls and comprehensive dashboards that provide real-time visibility into process performance. The graphical user interface simplifies complex operations, enabling quick decision-making and minimizing human errors.

Additionally, the Emerson 3000/ITR supports advanced analytics capabilities that enhance operational efficiency. By leveraging predictive analytics and machine learning algorithms, the system can identify patterns and anomalies, allowing for proactive maintenance and reducing the risk of unexpected downtime. This predictive maintenance approach helps organizations optimize their resources and extend the lifecycle of their equipment.

In conclusion, the Emerson 3000/ITR stands out as an exemplary solution for modern industrial automation. Its modular design, robust communication support, strong security measures, user-friendly interface, and advanced analytics capabilities make it an ideal choice for businesses looking to enhance their operational efficiency and adaptability. As industries continue to evolve, the Emerson 3000/ITR remains at the forefront, facilitating smarter and more efficient automation processes.