Emerson 3000/ITR manual Standard Alarms, Alarm Descriptions, Change Filter, Compressor Overload

Page 38

Alarm Descriptions

6.0ALARM DESCRIPTIONS

The Liebert iCOM will audibly and visually annunciate all enabled alarms. Alarms are wired from Terminal 24 through a normally open contact to locations 50, 51, 55 and 56, respectively, for alarms 1 through 4.

The alarms can be delayed from 0 to 255 seconds.

The alarms can be designated as WARNING, URGENT, or DISABLED. Alarms designated as WARNINGS are annunciated after the Time Delay, but do not energize the Common Alarm Relay. If designated as URGENT, they are annunciated after the Time Delay as a WARNING alarm and then re-annunciated after a user programmable period from 0 minutes to 999 hours as an URGENT alarm. When annunciated as an URGENT alarm, the Common Alarm Relay is activated.

When a new alarm occurs, it is displayed on the screen and the audible alarm is activated. If the Lie- bert Challenger 3000/Liebert Challenger ITR with iCOM is communicating with a Liebert site moni- toring product, the alarm is also transmitted. The display will also show a message to “PRESS ENTER KEY TO SILENCE” the alarm. After the alarm is silenced, the display will return to the Nor- mal Status Display.

The alarms can also be silenced through communications with a Liebert site monitoring unit. Most alarms will reset automatically when the alarm condition is no longer present and only after it has been acknowledged by being “Silenced.” The exceptions are:

The three software alarms: Loss of Power, Low Suction Pressure, and Short Cycle, which reset automatically 90 minutes after being “Silenced” or acknowledged.

Some alarms, such as overloads and high pressure switches, may require a manual reset depend- ing on your model.

An alarms history is retained in nonvolatile memory.

6.1Standard Alarms

6.1.1Change Filter

Periodically, the return air filters in the environmental units must be changed. The Change Filter alarm notifies the user that filter replacement is necessary. A differential air pressure switch closes when the pressure drop across the filters becomes excessive. The switch is adjustable using the proce- dure on the switch label.

6.1.2Compressor Overload

An optional tri-block overload device can be used for the compressor. Compressor overload may be manual or automatic reset, depending on your model. Overload is located at the electric connection box on the compressor.

32

Image 38
Contents Operation & Maintenance Manual 50 & 60Hz Page Table of Contents Component Operation and Maintenance Standard AlarmsFigures Tables Important Safety Instructions Page Compressorized Systems System DescriptionsIntroduction Glycool Chilled Glycol Cooling SystemsStartup Procedure StartupStartup Large and Small Displays FeaturesOperation with Icom Control Liebert Icom Display Components and Functions Escape Key Down Arrow KeyKeyboard icons and functions Icon Key Name FunctionNavigating Through the Liebert iCOM Display Control Interface-Three Main Menus Sensor Reading Next Maintenance Evaporator Fan SpeedTime Most Recent Alarms Percent System or Unit Cooling On/Off DateAfter highlighting the Password command line, press Accessing Menus and Settings Viewing DataEntering the Password Password is factory-set atAccessing Submenus on Large Displays Accessing SubmenusAccessing Submenus on Small Displays Status Menu Unit 1 View User Menu Service Menu UnitStatus Menu System View Advanced Menu UnitContacts Changing Operational SettingsService Changing Liebert iCOM’s Display Settings Highlight the setting to be changed by pressing EnterNetwork Liebert iCOM Service Menu Icons and LegendGraphical Data Record Sample Liebert iCOM network configurations Wiring for Unit-to-Unit Communications-U2UWiring a Liebert iCOM U2U Network Small Displays Liebert iCOM U2U Ethernet NetworkCombining Large and Small Displays on a U2U Network Large DisplaysWall-Mount Large Display U2U network setup diagram Display Service/Network Liebert iCom Display MenuLiebert iCOM Display Components and Functions Liebert iCOM wiring-Unit as shipped 194273 194273 P65 P64 P61 P63 P67 P66Entering Network Setup Information Control board U2U network setup screenAdvanced Menu Unit # Service Menu Unit #Viewing Multiple Units with a Networked Large Display Unit/Fan Control Start Stop Single Unit FunctionsOperation Remote On / Off Display On / OffAutorestart Loss of Power AlarmFan Alarm / Fan Protection Settings Pump Down-Air Cooled with Condenser Only Units High Pressure AlarmDigital Scroll High Temperature Compressor TimingPI Control Control TypesProportional Control Intelligent Control Chilled Water Only Change Filter Standard AlarmsAlarm Descriptions Compressor OverloadHumidifier Problem Infrared Humidifiers High TemperatureHigh Temperature and Low Temperature Simultaneously High Head PressureLoss of Air Flow Loss of PowerLow Temperature Low HumidityOptional Alarms Set Alarms-User MenusSystem Testing Component Operation and MaintenanceHigh-Temp Sensor Fan Safety SwitchControl Transformer and Fuses Smoke DetectorDistance From Unit, feet m Zone leak detection kit installation scenariosRemote Shutdown Fan Impellers and Bearings FiltersBlower Package BeltSuction Pressure Refrigeration SystemAir Distribution Suction pressures R407cSuperheat AdjustmentDischarge Pressure Thermostatic Expansion Valve OperationAir Cooled Condenser Outdoor fan/condenser configuration Water/Glycol Cooled Condensers Coaxial CondenserControl Method Motorized Ball Valve-Digital Scroll CompressorControl StartupAdjusting Collar Nut Valve spring guideCooling Type Glycool Glycol Flow Control Drycooler SettingsAquastat settings-two-fan through four-fan drycoolers Before Replacing or Returning a Compressor Compressor ReplacementCompressor Oil Compressor Functional CheckElectrical Failure Standard Scroll Compressor ReplacementMechanical Failure Digital Scroll Compressor Replacement Procedure Glycol Solution MaintenanceInfrared Humidifier Cleaning the PanHumidifier Removing the PanAutoflush Operation Autoflush Infrared Humidifier Cleaning SystemChanging Humidifier Lamps Humidifier LampsAutoflush Controls Steam Generating HumidifierControls Part Capacity Number Voltage Lb/hr kg/hr Replacing the CanisterHumidifier canister part numbers 200-460Circuit Board Adjustments Drain Tempering FeatureChilled water troubleshooting TroubleshootingBlower troubleshooting Symptom Possible Cause Check or RemedyCompressor and refrigeration system troubleshooting Compressor and refrigeration system troubleshooting Infrared humidifier troubleshooting Dehumidification troubleshootingGlycol pump troubleshooting See 7.5.1 Compressor FunctionalSteam generating humidifier troubleshooting Reheat troubleshooting Monthly Maintenance Inspection Checklist Semiannual Maintenance Inspection Checklist Semiannual Maintenance Inspection Checklist Page Ppor t Ti n Ne tIti That

3000/ITR specifications

The Emerson 3000/ITR is a powerful and versatile instrument designed for industrial automation and process control applications. This modular platform integrates advanced features and technologies tailored to meet the needs of diverse industries including oil and gas, pharmaceuticals, and manufacturing.

One of the main features of the Emerson 3000/ITR is its exceptional scalability. The system can be easily expanded to accommodate growing operational demands. With its modular architecture, operators can add or remove components without significant downtime, ensuring continuous productivity. This flexibility allows businesses to adapt their systems to changing environments and requirements seamlessly.

The Emerson 3000/ITR leverages state-of-the-art communication technologies to ensure reliable data exchange between devices. With support for various protocols, including Hart, Modbus, and Profibus, the system can easily integrate with existing infrastructure. This adaptability enhances interoperability and simplifies the communication between field devices and control systems, promoting efficient data handling.

Built with robust security features, the Emerson 3000/ITR guarantees the integrity of sensitive data. The platform incorporates advanced encryption techniques and user authentication protocols to protect against potential cyber threats. This focus on security is essential in today’s digitally connected industrial environments.

Another key characteristic of the Emerson 3000/ITR is its user-friendly interface. The system is designed with operators in mind, featuring intuitive controls and comprehensive dashboards that provide real-time visibility into process performance. The graphical user interface simplifies complex operations, enabling quick decision-making and minimizing human errors.

Additionally, the Emerson 3000/ITR supports advanced analytics capabilities that enhance operational efficiency. By leveraging predictive analytics and machine learning algorithms, the system can identify patterns and anomalies, allowing for proactive maintenance and reducing the risk of unexpected downtime. This predictive maintenance approach helps organizations optimize their resources and extend the lifecycle of their equipment.

In conclusion, the Emerson 3000/ITR stands out as an exemplary solution for modern industrial automation. Its modular design, robust communication support, strong security measures, user-friendly interface, and advanced analytics capabilities make it an ideal choice for businesses looking to enhance their operational efficiency and adaptability. As industries continue to evolve, the Emerson 3000/ITR remains at the forefront, facilitating smarter and more efficient automation processes.