Emerson 3000/ITR manual Compressor and refrigeration system troubleshooting

Page 64

 

 

Troubleshooting

Table 14 Compressor and refrigeration system troubleshooting (continued)

 

 

 

Symptom

Possible Cause

Check or Remedy

 

 

 

 

Defective or improperly set expansion

Increase superheat or replace valve

 

valve

 

 

Flooding

Evaporator fan motor or belt

Correct problem or replace fan motor and/

or belts.

 

Low condensing pressure

Check head pressure control device

 

 

 

 

Slipping belts

Inspect and adjust

 

 

 

 

Compressor rotation in reverse

Check for proper power phase wiring to

Low compressor capacity or

direction.

unit and to compressor motor.

inability to pull down system

Leaking liquid line solenoid valve or dirt

Replace valve if clean; clean out valve if

 

in valve

dirty.

Compressor noisy

Loose compressor or piping support

Tighten clamps.

 

 

 

Pipe rattle

Loose pipe connections

Check pipe connections

 

 

 

 

 

Check setting of high and low pressure

Compressor running hot

Compression ratio too high

switches. Check condenser -- is it

plugged? Check that all evaporator and

 

 

 

 

condenser fans are operating properly.

 

 

 

 

 

Check tubing to switch to see if clogged or

 

Low-pressure switch erratic in operation

crimped. Check for proper switch

 

 

operation.

 

 

Check for leaks, fix, and add refrigerant on

 

Insufficient refrigerant in system

air cooled unit. Evacuate and recharge

Compressor cycles intermittently

 

water/glycol unit.

 

Suction service valve closed

Open valve.

 

 

 

 

Insufficient fluid flowing through

Adjust fluid regulating valve to condenser.

 

condenser or clogged condenser, or

 

Flush the condenser.

 

dirty air cooled condenser coils

 

 

 

 

 

 

Discharge service valve not fully open

Open valve

 

 

 

 

Faulty low pressure switch

Repair or replace.

 

 

 

 

Dirt or restriction in tubing to pressure

Check and clean tubing.

 

stat

Compressor cycles continually

 

Defective liquid line solenoid valve

Check valve and solenoid operator;

 

 

replace if necessary.

 

 

 

 

 

 

Plugged filter-drier

Replace filter.

 

 

 

 

High discharge pressure

Check for loss of condenser water or

 

blocked condenser fan or coil.

 

 

 

Defective overload relay

Replace.

 

 

 

 

 

Reduce suction temperature by expansion

Compressor motor protectors

High suction temperature

valve adjustment or provide

tripping or cycling

 

desuperheating.

 

Loose power or control circuit wiring

Check all power and control circuit

 

connection

connections.

 

Defective motor

Check for motor ground or short. Replace

 

compressor, if either condition is found.

 

 

 

Low line voltage

Check line voltage and determine location

 

of voltage drop.

 

 

Compressor cycles on locked rotor

Compressor motor defective

Check for motor winding short or ground.

 

 

 

 

Single phasing

Check voltage across all 3 legs at

 

contactor. Correct source problem.

 

 

 

Check control panel for welded

 

Motor burnout

contactor contacts or welded overload

Replace defective components

 

contacts

 

58

Image 64
Contents Operation & Maintenance Manual 50 & 60Hz Page Table of Contents Component Operation and Maintenance Standard AlarmsFigures Tables Important Safety Instructions Page System Descriptions IntroductionCompressorized Systems Glycool Chilled Glycol Cooling SystemsStartup Procedure StartupStartup Operation with Icom Control FeaturesLarge and Small Displays Liebert Icom Display Components and Functions Escape Key Down Arrow KeyKeyboard icons and functions Icon Key Name FunctionNavigating Through the Liebert iCOM Display Sensor Reading Next Maintenance Evaporator Fan Speed Time Most Recent AlarmsControl Interface-Three Main Menus Percent System or Unit Cooling On/Off DateAccessing Menus and Settings Viewing Data Entering the PasswordAfter highlighting the Password command line, press Password is factory-set atAccessing Submenus on Small Displays Accessing SubmenusAccessing Submenus on Large Displays Service Menu Unit Status Menu System ViewStatus Menu Unit 1 View User Menu Advanced Menu UnitService Changing Operational SettingsContacts Changing Liebert iCOM’s Display Settings Highlight the setting to be changed by pressing EnterGraphical Data Record Liebert iCOM Service Menu Icons and LegendNetwork Wiring for Unit-to-Unit Communications-U2U Wiring a Liebert iCOM U2U Network Small DisplaysSample Liebert iCOM network configurations Liebert iCOM U2U Ethernet NetworkWall-Mount Large Display Large DisplaysCombining Large and Small Displays on a U2U Network U2U network setup diagram Display Service/Network Liebert iCom Display MenuLiebert iCOM Display Components and Functions Liebert iCOM wiring-Unit as shipped 194273 194273 P65 P64 P61 P63 P67 P66Entering Network Setup Information Control board U2U network setup screenViewing Multiple Units with a Networked Large Display Service Menu Unit #Advanced Menu Unit # Single Unit Functions OperationUnit/Fan Control Start Stop Remote On / Off Display On / OffFan Alarm / Fan Protection Settings Loss of Power AlarmAutorestart High Pressure Alarm Digital Scroll High TemperaturePump Down-Air Cooled with Condenser Only Units Compressor TimingProportional Control Control TypesPI Control Intelligent Control Chilled Water Only Standard Alarms Alarm DescriptionsChange Filter Compressor OverloadHigh Temperature High Temperature and Low Temperature SimultaneouslyHumidifier Problem Infrared Humidifiers High Head PressureLoss of Power Low TemperatureLoss of Air Flow Low HumidityOptional Alarms Set Alarms-User MenusSystem Testing Component Operation and MaintenanceFan Safety Switch Control Transformer and FusesHigh-Temp Sensor Smoke DetectorRemote Shutdown Zone leak detection kit installation scenariosDistance From Unit, feet m Filters Blower PackageFan Impellers and Bearings BeltRefrigeration System Air DistributionSuction Pressure Suction pressures R407cAdjustment Discharge PressureSuperheat Thermostatic Expansion Valve OperationAir Cooled Condenser Outdoor fan/condenser configuration Water/Glycol Cooled Condensers Coaxial CondenserMotorized Ball Valve-Digital Scroll Compressor ControlControl Method StartupAdjusting Collar Nut Valve spring guideAquastat settings-two-fan through four-fan drycoolers Drycooler SettingsCooling Type Glycool Glycol Flow Control Compressor Replacement Compressor OilBefore Replacing or Returning a Compressor Compressor Functional CheckMechanical Failure Standard Scroll Compressor ReplacementElectrical Failure Digital Scroll Compressor Replacement Procedure Glycol Solution MaintenanceCleaning the Pan HumidifierInfrared Humidifier Removing the PanAutoflush Infrared Humidifier Cleaning System Changing Humidifier LampsAutoflush Operation Humidifier LampsAutoflush Controls Steam Generating HumidifierControls Replacing the Canister Humidifier canister part numbersPart Capacity Number Voltage Lb/hr kg/hr 200-460Circuit Board Adjustments Drain Tempering FeatureTroubleshooting Blower troubleshootingChilled water troubleshooting Symptom Possible Cause Check or RemedyCompressor and refrigeration system troubleshooting Compressor and refrigeration system troubleshooting Dehumidification troubleshooting Glycol pump troubleshootingInfrared humidifier troubleshooting See 7.5.1 Compressor FunctionalSteam generating humidifier troubleshooting Reheat troubleshooting Monthly Maintenance Inspection Checklist Semiannual Maintenance Inspection Checklist Semiannual Maintenance Inspection Checklist Page Ne t ItiPpor t Ti n That

3000/ITR specifications

The Emerson 3000/ITR is a powerful and versatile instrument designed for industrial automation and process control applications. This modular platform integrates advanced features and technologies tailored to meet the needs of diverse industries including oil and gas, pharmaceuticals, and manufacturing.

One of the main features of the Emerson 3000/ITR is its exceptional scalability. The system can be easily expanded to accommodate growing operational demands. With its modular architecture, operators can add or remove components without significant downtime, ensuring continuous productivity. This flexibility allows businesses to adapt their systems to changing environments and requirements seamlessly.

The Emerson 3000/ITR leverages state-of-the-art communication technologies to ensure reliable data exchange between devices. With support for various protocols, including Hart, Modbus, and Profibus, the system can easily integrate with existing infrastructure. This adaptability enhances interoperability and simplifies the communication between field devices and control systems, promoting efficient data handling.

Built with robust security features, the Emerson 3000/ITR guarantees the integrity of sensitive data. The platform incorporates advanced encryption techniques and user authentication protocols to protect against potential cyber threats. This focus on security is essential in today’s digitally connected industrial environments.

Another key characteristic of the Emerson 3000/ITR is its user-friendly interface. The system is designed with operators in mind, featuring intuitive controls and comprehensive dashboards that provide real-time visibility into process performance. The graphical user interface simplifies complex operations, enabling quick decision-making and minimizing human errors.

Additionally, the Emerson 3000/ITR supports advanced analytics capabilities that enhance operational efficiency. By leveraging predictive analytics and machine learning algorithms, the system can identify patterns and anomalies, allowing for proactive maintenance and reducing the risk of unexpected downtime. This predictive maintenance approach helps organizations optimize their resources and extend the lifecycle of their equipment.

In conclusion, the Emerson 3000/ITR stands out as an exemplary solution for modern industrial automation. Its modular design, robust communication support, strong security measures, user-friendly interface, and advanced analytics capabilities make it an ideal choice for businesses looking to enhance their operational efficiency and adaptability. As industries continue to evolve, the Emerson 3000/ITR remains at the forefront, facilitating smarter and more efficient automation processes.