Emerson 3000/ITR manual Refrigeration System, Air Distribution, Suction Pressure

Page 46

Component Operation and Maintenance

7.3.3Air Distribution

All unit models are designed for constant volume air delivery. Therefore any unusual restrictions within the air circuit must be avoided. For downflow models operating on a raised floor, refer to the following table for recommended free area for proper air flow.

Table 5 Recommended free area ft2 (m2) for grilles or perforated panels at output velocities of 550 and 600 fpm (2.8 and 3.1 m/s)

 

550 FPM

600 FPM

Model

(2.8 m/s)

(3.1 m/s)

 

 

 

60 Hz Units

 

 

 

 

 

3 Ton

3.3 (0.31)

3.0 (0.28)

 

 

 

5 Ton

5.1 (0.41)

4.7 (0.44)

 

 

 

50 Hz Units

 

 

 

 

 

3 Ton

3.3 (0.31)

3.0 (0.28)

 

 

 

5 Ton

4.7 (0.44)

4.3 (0.40)

 

 

 

Grilles used in raised floors vary in size, the largest being 18" x 6" (46 cm x 15 cm). This type of grille has approximately 56 in2 (361 cm2) of free area. Perforated Panels are usually 2' x 2' (61 cm x 61 cm) and have a nominal free area of approximately 108 to 144 in2 (697 to 929 cm2).

NOTICE

Risk of airflow restriction. Can cause inefficient operation and equipment overheating.

In raised-floor use, all under-floor restrictions, such as clusters of cables or piping, must be avoided because they may form barriers to airflow. Whenever possible, cables and pipes should be run parallel to the airflow. Never stack cables or piping.

7.4Refrigeration System

Each month, the components of the refrigeration system should be inspected for proper function and signs of wear. Since, in most cases, evidence of malfunction is present prior to component failure, peri- odic inspections can be a major factor in the prevention of most system failures.

Refrigerant lines must be properly supported and not allowed to vibrate against ceilings, floors or the unit frame. Inspect all refrigerant lines every six months for signs of wear and proper support. Also inspect capillary and equalizer lines from the expansion valve and support as necessary.

Each liquid line has a sight glass that indicates liquid refrigerant flow and the presence of moisture. Bubbles in the sight glass indicate a shortage of refrigerant or a restriction in the liquid line. The moisture indicator changes from green to yellow when moisture is present in the system.

7.4.1Suction Pressure

Suction pressure will vary with load conditions. The low pressure switch will shut the compressor down if suction pressure falls below the cut-out setting. High suction pressure reduces the ability of the refrigerant to cool compressor components and can result in compressor damage. Minimum (pres- sure switch cut-out setting) and maximum (design operating) suction pressures are in Table 6.

Table 6 Suction pressures - R407c

 

Minimum

Maximum

System

PSIG (kPa)

PSIG (kPa)

 

 

 

Air w/FSC

15 (103)

95 (654)

(Fan Speed Control)

 

 

Air w/Lee-Temp Control

 

 

(Floodback head

20 (137)

95 (654)

pressure control)

 

 

Water Cooled

20 (137)

95 (654)

 

 

 

Glycol Cooled

20 (137)

95 (654)

 

 

 

40

Image 46
Contents Operation & Maintenance Manual 50 & 60Hz Page Table of Contents Component Operation and Maintenance Standard AlarmsFigures Tables Important Safety Instructions Page Compressorized Systems System DescriptionsIntroduction Glycool Chilled Glycol Cooling SystemsStartup Procedure StartupStartup Operation with Icom Control FeaturesLarge and Small Displays Liebert Icom Display Components and Functions Escape Key Down Arrow KeyKeyboard icons and functions Icon Key Name FunctionNavigating Through the Liebert iCOM Display Control Interface-Three Main Menus Sensor Reading Next Maintenance Evaporator Fan SpeedTime Most Recent Alarms Percent System or Unit Cooling On/Off DateAfter highlighting the Password command line, press Accessing Menus and Settings Viewing DataEntering the Password Password is factory-set atAccessing Submenus on Small Displays Accessing SubmenusAccessing Submenus on Large Displays Status Menu Unit 1 View User Menu Service Menu UnitStatus Menu System View Advanced Menu UnitService Changing Operational SettingsContacts Changing Liebert iCOM’s Display Settings Highlight the setting to be changed by pressing EnterGraphical Data Record Liebert iCOM Service Menu Icons and LegendNetwork Sample Liebert iCOM network configurations Wiring for Unit-to-Unit Communications-U2UWiring a Liebert iCOM U2U Network Small Displays Liebert iCOM U2U Ethernet NetworkWall-Mount Large Display Large DisplaysCombining Large and Small Displays on a U2U Network U2U network setup diagram Display Service/Network Liebert iCom Display MenuLiebert iCOM Display Components and Functions Liebert iCOM wiring-Unit as shipped 194273 194273 P65 P64 P61 P63 P67 P66Entering Network Setup Information Control board U2U network setup screenViewing Multiple Units with a Networked Large Display Service Menu Unit #Advanced Menu Unit # Unit/Fan Control Start Stop Single Unit FunctionsOperation Remote On / Off Display On / OffFan Alarm / Fan Protection Settings Loss of Power AlarmAutorestart Pump Down-Air Cooled with Condenser Only Units High Pressure AlarmDigital Scroll High Temperature Compressor TimingProportional Control Control TypesPI Control Intelligent Control Chilled Water Only Change Filter Standard AlarmsAlarm Descriptions Compressor OverloadHumidifier Problem Infrared Humidifiers High TemperatureHigh Temperature and Low Temperature Simultaneously High Head PressureLoss of Air Flow Loss of PowerLow Temperature Low HumidityOptional Alarms Set Alarms-User MenusSystem Testing Component Operation and MaintenanceHigh-Temp Sensor Fan Safety SwitchControl Transformer and Fuses Smoke DetectorRemote Shutdown Zone leak detection kit installation scenariosDistance From Unit, feet m Fan Impellers and Bearings FiltersBlower Package BeltSuction Pressure Refrigeration SystemAir Distribution Suction pressures R407cSuperheat AdjustmentDischarge Pressure Thermostatic Expansion Valve OperationAir Cooled Condenser Outdoor fan/condenser configuration Water/Glycol Cooled Condensers Coaxial CondenserControl Method Motorized Ball Valve-Digital Scroll CompressorControl StartupAdjusting Collar Nut Valve spring guideAquastat settings-two-fan through four-fan drycoolers Drycooler SettingsCooling Type Glycool Glycol Flow Control Before Replacing or Returning a Compressor Compressor ReplacementCompressor Oil Compressor Functional CheckMechanical Failure Standard Scroll Compressor ReplacementElectrical Failure Digital Scroll Compressor Replacement Procedure Glycol Solution MaintenanceInfrared Humidifier Cleaning the PanHumidifier Removing the PanAutoflush Operation Autoflush Infrared Humidifier Cleaning SystemChanging Humidifier Lamps Humidifier LampsAutoflush Controls Steam Generating HumidifierControls Part Capacity Number Voltage Lb/hr kg/hr Replacing the CanisterHumidifier canister part numbers 200-460Circuit Board Adjustments Drain Tempering FeatureChilled water troubleshooting TroubleshootingBlower troubleshooting Symptom Possible Cause Check or RemedyCompressor and refrigeration system troubleshooting Compressor and refrigeration system troubleshooting Infrared humidifier troubleshooting Dehumidification troubleshootingGlycol pump troubleshooting See 7.5.1 Compressor FunctionalSteam generating humidifier troubleshooting Reheat troubleshooting Monthly Maintenance Inspection Checklist Semiannual Maintenance Inspection Checklist Semiannual Maintenance Inspection Checklist Page Ppor t Ti n Ne tIti That

3000/ITR specifications

The Emerson 3000/ITR is a powerful and versatile instrument designed for industrial automation and process control applications. This modular platform integrates advanced features and technologies tailored to meet the needs of diverse industries including oil and gas, pharmaceuticals, and manufacturing.

One of the main features of the Emerson 3000/ITR is its exceptional scalability. The system can be easily expanded to accommodate growing operational demands. With its modular architecture, operators can add or remove components without significant downtime, ensuring continuous productivity. This flexibility allows businesses to adapt their systems to changing environments and requirements seamlessly.

The Emerson 3000/ITR leverages state-of-the-art communication technologies to ensure reliable data exchange between devices. With support for various protocols, including Hart, Modbus, and Profibus, the system can easily integrate with existing infrastructure. This adaptability enhances interoperability and simplifies the communication between field devices and control systems, promoting efficient data handling.

Built with robust security features, the Emerson 3000/ITR guarantees the integrity of sensitive data. The platform incorporates advanced encryption techniques and user authentication protocols to protect against potential cyber threats. This focus on security is essential in today’s digitally connected industrial environments.

Another key characteristic of the Emerson 3000/ITR is its user-friendly interface. The system is designed with operators in mind, featuring intuitive controls and comprehensive dashboards that provide real-time visibility into process performance. The graphical user interface simplifies complex operations, enabling quick decision-making and minimizing human errors.

Additionally, the Emerson 3000/ITR supports advanced analytics capabilities that enhance operational efficiency. By leveraging predictive analytics and machine learning algorithms, the system can identify patterns and anomalies, allowing for proactive maintenance and reducing the risk of unexpected downtime. This predictive maintenance approach helps organizations optimize their resources and extend the lifecycle of their equipment.

In conclusion, the Emerson 3000/ITR stands out as an exemplary solution for modern industrial automation. Its modular design, robust communication support, strong security measures, user-friendly interface, and advanced analytics capabilities make it an ideal choice for businesses looking to enhance their operational efficiency and adaptability. As industries continue to evolve, the Emerson 3000/ITR remains at the forefront, facilitating smarter and more efficient automation processes.