Emerson 3000/ITR Motorized Ball Valve-Digital Scroll Compressor, Control Method, Startup

Page 50

Component Operation and Maintenance

7.4.8Motorized Ball Valve—Digital Scroll Compressor

On water-cooled and glycol-cooled digital scroll units, the discharge pressure is controlled by a motor- ized ball valve. During unloaded operation, the pressure changes during each digital cycle could result in excessive repositions with a pressure operated water regulating valve. The control algorithm for the motorized ball valve uses an intelligent sampling rate and adjustable pressure thresholds to reduce valve repositions. The valve assembly consists of the brass valve, linkage and actuator.

Control

The valve actuator operates on 24VAC power and is controlled by a 2-10VDC proportional control sig- nal. The valve full open to full close time is 60 seconds. At 2VDC the valve is closed; at 10VDC the valve is fully open. There is a 20-second delay to position the motorized ball valve before starting the compressor.

Control Method

The control utilizes an upper and lower pressure threshold with a 35 PSI (241 kPa) deadband to reduce valve movement. If the liquid pressure is between the upper and lower threshold the valve remains at the current position. If the liquid pressure exceeds the upper threshold the valve opens, and if the pressure falls below the lower threshold the valve closes. There are multiple adjustment bands to ease discharge pressure back into control range.

Adjustment

Both pressure thresholds can be shifted simultaneously over a 50 PSI (345 kPa) range (the 35 PSI [241 kPa] differential remains constant). The ball valve setpoint offset parameter in the Service menu can be adjusted from 0 to 50 PSI (345 kPa) to raise or lower the control band similar to the pressure adjustment on a water regulating valve. Units are factory set at a 30 PSI (207 kPa) setpoint offset (30 PSI [207 kPa] above minimum). This results in a 220 PSIA (1517 kPa) lower threshold and a 255 PSIA (1758 kPa) upper threshold pressure.

Startup

The setpoint offset is adjusted to the minimum value during startup, then transitions to the set value once the compressor reaches normal operating pressures. Additionally changes in fluid temperature could cause pressure changes that do not result in valve movement within the dead band on drycool- ers. Fan cycling stats should be set to prevent continuous fluid temperature swings greater than 10oF (5.6oC) (see 7.4.10 - Drycooler Settings).

Location

The motorized ball valves are located in the condenser fluid return line. The three-way valve is piped in a mixing arrangement with the common port at the valve outlet.

Manual Control

The valve can be manually set by disconnecting AC power, depressing the manual override button on the valve actuator, and adjusting the valve position with the handle. You also have the option to con- trol the motorized ball valves through the Service menu using manual mode to override the normal control.

7.4.9Regulating Valve—Scroll Compressor

The water regulating valve automatically regulates the amount of fluid necessary to remove the heat from the refrigeration system, permitting more fluid to flow when load conditions are high and less fluid to flow when load conditions are low. The valve consists of a brass body, balance spring, valve seat, valve disc holders, capillary tube to discharge pressure, and adjusting screw.

Standard Valve - 150 psig (1034 kPa) system for 3 & 5 ton units (Johnson Controls Valve) High Pressure Valve - 350 psig (2413 kPa) system for 5 ton units (Johnson Controls Valve)

Adjustment—The valve may be adjusted with a standard refrigeration service valve wrench or screw driver. Refer to Table 7 for recommended refrigerant pressures.

To lower the head pressure setting, turn the square adjusting screw clockwise until the high pressure gauge indicates the desired setting.

44

Image 50
Contents Operation & Maintenance Manual 50 & 60Hz Page Table of Contents Component Operation and Maintenance Standard AlarmsFigures Tables Important Safety Instructions Page Compressorized Systems System DescriptionsIntroduction Glycool Chilled Glycol Cooling SystemsStartup Procedure StartupStartup Large and Small Displays FeaturesOperation with Icom Control Liebert Icom Display Components and Functions Escape Key Down Arrow KeyKeyboard icons and functions Icon Key Name FunctionNavigating Through the Liebert iCOM Display Control Interface-Three Main Menus Sensor Reading Next Maintenance Evaporator Fan SpeedTime Most Recent Alarms Percent System or Unit Cooling On/Off DateAfter highlighting the Password command line, press Accessing Menus and Settings Viewing DataEntering the Password Password is factory-set atAccessing Submenus on Large Displays Accessing SubmenusAccessing Submenus on Small Displays Status Menu Unit 1 View User Menu Service Menu UnitStatus Menu System View Advanced Menu UnitContacts Changing Operational SettingsService Changing Liebert iCOM’s Display Settings Highlight the setting to be changed by pressing EnterNetwork Liebert iCOM Service Menu Icons and LegendGraphical Data Record Sample Liebert iCOM network configurations Wiring for Unit-to-Unit Communications-U2UWiring a Liebert iCOM U2U Network Small Displays Liebert iCOM U2U Ethernet NetworkCombining Large and Small Displays on a U2U Network Large DisplaysWall-Mount Large Display U2U network setup diagram Display Service/Network Liebert iCom Display MenuLiebert iCOM Display Components and Functions Liebert iCOM wiring-Unit as shipped 194273 194273 P65 P64 P61 P63 P67 P66Entering Network Setup Information Control board U2U network setup screenAdvanced Menu Unit # Service Menu Unit #Viewing Multiple Units with a Networked Large Display Unit/Fan Control Start Stop Single Unit FunctionsOperation Remote On / Off Display On / OffAutorestart Loss of Power AlarmFan Alarm / Fan Protection Settings Pump Down-Air Cooled with Condenser Only Units High Pressure AlarmDigital Scroll High Temperature Compressor TimingPI Control Control TypesProportional Control Intelligent Control Chilled Water Only Change Filter Standard AlarmsAlarm Descriptions Compressor OverloadHumidifier Problem Infrared Humidifiers High TemperatureHigh Temperature and Low Temperature Simultaneously High Head PressureLoss of Air Flow Loss of PowerLow Temperature Low HumidityOptional Alarms Set Alarms-User MenusSystem Testing Component Operation and MaintenanceHigh-Temp Sensor Fan Safety SwitchControl Transformer and Fuses Smoke DetectorDistance From Unit, feet m Zone leak detection kit installation scenariosRemote Shutdown Fan Impellers and Bearings FiltersBlower Package BeltSuction Pressure Refrigeration SystemAir Distribution Suction pressures R407cSuperheat AdjustmentDischarge Pressure Thermostatic Expansion Valve OperationAir Cooled Condenser Outdoor fan/condenser configuration Water/Glycol Cooled Condensers Coaxial CondenserControl Method Motorized Ball Valve-Digital Scroll CompressorControl StartupAdjusting Collar Nut Valve spring guideCooling Type Glycool Glycol Flow Control Drycooler SettingsAquastat settings-two-fan through four-fan drycoolers Before Replacing or Returning a Compressor Compressor ReplacementCompressor Oil Compressor Functional CheckElectrical Failure Standard Scroll Compressor ReplacementMechanical Failure Digital Scroll Compressor Replacement Procedure Glycol Solution MaintenanceInfrared Humidifier Cleaning the PanHumidifier Removing the PanAutoflush Operation Autoflush Infrared Humidifier Cleaning SystemChanging Humidifier Lamps Humidifier LampsAutoflush Controls Steam Generating HumidifierControls Part Capacity Number Voltage Lb/hr kg/hr Replacing the CanisterHumidifier canister part numbers 200-460Circuit Board Adjustments Drain Tempering FeatureChilled water troubleshooting TroubleshootingBlower troubleshooting Symptom Possible Cause Check or RemedyCompressor and refrigeration system troubleshooting Compressor and refrigeration system troubleshooting Infrared humidifier troubleshooting Dehumidification troubleshootingGlycol pump troubleshooting See 7.5.1 Compressor FunctionalSteam generating humidifier troubleshooting Reheat troubleshooting Monthly Maintenance Inspection Checklist Semiannual Maintenance Inspection Checklist Semiannual Maintenance Inspection Checklist Page Ppor t Ti n Ne tIti That

3000/ITR specifications

The Emerson 3000/ITR is a powerful and versatile instrument designed for industrial automation and process control applications. This modular platform integrates advanced features and technologies tailored to meet the needs of diverse industries including oil and gas, pharmaceuticals, and manufacturing.

One of the main features of the Emerson 3000/ITR is its exceptional scalability. The system can be easily expanded to accommodate growing operational demands. With its modular architecture, operators can add or remove components without significant downtime, ensuring continuous productivity. This flexibility allows businesses to adapt their systems to changing environments and requirements seamlessly.

The Emerson 3000/ITR leverages state-of-the-art communication technologies to ensure reliable data exchange between devices. With support for various protocols, including Hart, Modbus, and Profibus, the system can easily integrate with existing infrastructure. This adaptability enhances interoperability and simplifies the communication between field devices and control systems, promoting efficient data handling.

Built with robust security features, the Emerson 3000/ITR guarantees the integrity of sensitive data. The platform incorporates advanced encryption techniques and user authentication protocols to protect against potential cyber threats. This focus on security is essential in today’s digitally connected industrial environments.

Another key characteristic of the Emerson 3000/ITR is its user-friendly interface. The system is designed with operators in mind, featuring intuitive controls and comprehensive dashboards that provide real-time visibility into process performance. The graphical user interface simplifies complex operations, enabling quick decision-making and minimizing human errors.

Additionally, the Emerson 3000/ITR supports advanced analytics capabilities that enhance operational efficiency. By leveraging predictive analytics and machine learning algorithms, the system can identify patterns and anomalies, allowing for proactive maintenance and reducing the risk of unexpected downtime. This predictive maintenance approach helps organizations optimize their resources and extend the lifecycle of their equipment.

In conclusion, the Emerson 3000/ITR stands out as an exemplary solution for modern industrial automation. Its modular design, robust communication support, strong security measures, user-friendly interface, and advanced analytics capabilities make it an ideal choice for businesses looking to enhance their operational efficiency and adaptability. As industries continue to evolve, the Emerson 3000/ITR remains at the forefront, facilitating smarter and more efficient automation processes.