Air-Cooled Models—Self-Contained Compressor

3.4Fan Speed Control Systems

The Variable Fan Speed Control systems (FSC & VFD) uses pressure-activated electronic fan speed control systems and remotely located thermostat(s) to ensure operation at ambient temperatures as low as 0°F (-18°C). For this ambient temperature range, the VFD Control Condenser must be used with digital scroll indoor units and can be used for energy savings with any Liebert Challenger 3000unit.

Variable Fan Speed Control Piping

A discharge line and a liquid line must be field-installed between the indoor unit and the outdoor condenser. See Figures 15 and 16 for details.

Variable Fan Speed Control Materials Supplied

Built-in, pre-wired condenser control box

Air-Cooled condenser

Piping access cover to be reinstalled when piping is complete

Bolts—four per leg (3/8" x 5/8")

Terminal block for two-wire, 24V interlock connection between unit and condenser

Condenser legs—four with 1-fan, 2-fan and 3-fan models; six with 4-fan models

Variable Fan Speed Control Leak Check and Evacuation Procedure

Proper leak check and evacuation can be accomplished only with all system solenoid valves open and check valves accounted for.

NOTE

Systems with a scroll or digital scroll compressor include a factory-installed check valve and an additional downstream Schrader valve with core in the compressor discharge line. Proper evacuation of the condenser side of the compressor can be accomplished only using the downstream Schrader valve. See piping schematic (Figures 15 and 16).

1.If unit power is available, open the unit liquid line solenoid valves using the evacuation function in the diagnostic section of the Liebert iCOM® control (refer to the Liebert iCOM user manual, SL-18835). If unit power is not available, a field-supplied 24VAC / 75VA power source must be directly connected to each of the unit solenoid valves.

2.For scroll and digital scroll compressors, connect refrigerant gauges to the suction rotalock valves and discharge line Schrader valves (see Note above) on the compressor.

3.Open the service valves and place a 150 PSIG (1034 kPa) of dry nitrogen with a tracer of refrigerant. Check system for leaks with a suitable leak detector.

4.After completion of leak testing, release the test pressure (per local code) and pull an initial deep vacuum on the system with a suitable pump.

5.After four hours, check the pressure readings and, if they have not changed, break vacuum with dry nitrogen. Pull a second and third vacuum to 250 microns or less. Recheck the pressure after two hours. After completing this step, proceed to Variable Fan Speed Charging on page 29.

Liebert® Challenger 3000

28

Image 34
Contents Liebert Challenger 3000 with Liebert iCOM Page Table of Contents Chilled Water Models Split System ModelsFigures R407C RefrigerantTables Important Safety Instructions Liebert Challenger Important Safety Instructions System Descriptions Centrifugal Fan Air-Cooled Split SystemsProp Fan Air-Cooled Water-CooledLocation Considerations Room PreparationEquipment Inspection Equipment HandlingRemoval of Skid Unit net weightHandling With Skid Model Lb. kgUpflow BU cabinet dimensions Floor Cutout Dimensions Drain Line Piping ConsiderationsPiping connection size Piping connections for air-cooled units Downflow models Chilled Water Unit Connection Sizes-inPiping connections for air-cooled units Upflow models Installation Applicable to all Models Condensate Pump Line 1/2 OD CU used only Installation Applicable to all Models Installation Applicable to all Models Installation Applicable to all Models Installation Applicable to all Models Electrical Connections Facility Fluid and Piping MaintenanceHumidifier Supply Water-Optional Infrared Terminal Block For Customer Connectons Upflow Models with Liebert iCOM Downflow Models with Liebert iCOMUnder-Floor Discharge Systems Plenum InstallationBalancing the Air Distribution Ducted ApplicationsChecklist for Completed Installation Line Voltage Condenser LocationLow Voltage Liebert Lee-Tempheater Common to all models. See below for key to a dimension Air-cooled condenser statistics 43-9/16 51-7/16Refrigerant Piping Equivalent lengths feet for various pipe fittings Recommended line sizes OD copper, inchesCondenser refrigerant per serial tag Variable Fan Speed Control Piping Fan Speed Control SystemsVariable Fan Speed Control Materials Supplied Fan speed suction pressure transducer settings Variable Fan Speed ChargingDPN000349 Rev DPN001726 Liebert Lee-Temp Piping Liebert Lee-Temp Leak Check and Evacuation ProcedureLiebert Lee-Temp Controlled Materials Supplied Liebert Lee-TempCharging Liebert Lee-Temp suction pressure transducer settings407C Factory Piping Optional Piping Field Piping DPN001725 Condenser Factory Piping Field Piping Factory Piping Adjustment Water Regulating ValveManual Flushing Refrigerant control settings psi kPaMotorized Ball Valve-Digital Scroll Compressors ControlLocation Control MethodStartup Manual ControlDrycooler Location Drycooler InstallationPump and Drycooler Glycol Piping General GuidelinesRoom dew point temperatures Dry Bulb Wet Bulb Relative Dew Point HumidityExpansion Tanks, Fluid Relief Valves and Other Devices Volume in standard Type L copper pipingFilling Instructions Preparing the System for FillingGlycol Solutions Ethylene glycol concentrationsFilling the System See Note 30-1/4 For expansion tank dimensions, see on43-3/16 43-9/16 110 5mm 483mm 1097mmGlycol pump data Mounting hole dimensional dataDrycooler data Pump Pump Suction Pump Discharge Connection,Field Piping General arrangement-Glycol-cooled models with digital scroll Expansion Tank Field-Installed at Pressure Glycol Regulating Valve Testing Valve FunctionMotor Ball Valve-Digital Scroll Compressors Chilled Water Models WAY Valve Air-Cooled Condensing Units Water/Glycol-Cooled Condensing UnitsRefrigerant Loop R407C Charge Unit refrigerant chargeModel Lb kg Recommended refrigerant lines R407C sizes OD copper Line charges refrigerant per 100 ft m of Type L copper tubeLine coupling sizes Quick Connect Fittings Unit Dimensions See Table Outdoor Air-Cooled Condensing UnitsPFCZ42A-L PFCZ41A-L Outdoor air-cooled condensing unit-top air discharge models See Table36-1/4 38-1/2 Piping and electrical connections top air discharge152 Field-supplied unit disconnect switch Ton High Ambient Ton Quiet-LineCentrifugal Air-Cooled Condensing Units Installing the Indoor Condensing UnitModel Net Weight 60 Hz 50 Hz Lb kg MC40A MC39A Indoor centrifugal condensing unitDucting Airflow CFM CMHPiping Connections Rev0 Wire connections from evaporatorDPN000207 ModTon centrifugal air-cooled condensing unit dimensional data AIR Cooled Water Cooled Ton Connection Sizes Water and Glycol-Cooled Condensing UnitsPiping Considerations Condenser Water RequirementsGlycol Systems Ton water/glycol-cooled condensing unitDPN000209 Ton water/glycol-cooled condensing unit dimensional data WATER/GLYCOL Temperature Gauge Pressure Psig KPa R407C RefrigerantCalculating Subcooling Temperature Pressure Gauge Psig KPaExample Page Twor k Ne tPpor t Is t Care