3.4Fan Speed Control Systems
The Variable Fan Speed Control systems (FSC & VFD) uses
Variable Fan Speed Control Piping
A discharge line and a liquid line must be
Variable Fan Speed Control Materials Supplied
•
•
•Piping access cover to be reinstalled when piping is complete
•
•Terminal block for
•Condenser
Variable Fan Speed Control Leak Check and Evacuation Procedure
Proper leak check and evacuation can be accomplished only with all system solenoid valves open and check valves accounted for.
NOTE
Systems with a scroll or digital scroll compressor include a
1.If unit power is available, open the unit liquid line solenoid valves using the evacuation function in the diagnostic section of the Liebert iCOM® control (refer to the Liebert iCOM user manual,
2.For scroll and digital scroll compressors, connect refrigerant gauges to the suction rotalock valves and discharge line Schrader valves (see Note above) on the compressor.
3.Open the service valves and place a 150 PSIG (1034 kPa) of dry nitrogen with a tracer of refrigerant. Check system for leaks with a suitable leak detector.
4.After completion of leak testing, release the test pressure (per local code) and pull an initial deep vacuum on the system with a suitable pump.
5.After four hours, check the pressure readings and, if they have not changed, break vacuum with dry nitrogen. Pull a second and third vacuum to 250 microns or less. Recheck the pressure after two hours. After completing this step, proceed to Variable Fan Speed Charging on page 29.