3.0
3.1Condenser Location
The
NOTE
If the condenser is located below the level of the room unit, the factory should be consulted.
Install condensers in a level position to assure proper refrigerant flow and oil return. For roof installation, mount condensers on steel supports in accordance with local codes. To minimize sound and vibration transmission, mount steel supports across load bearing walls. For ground installation, a concrete pad will provide adequate support. Condenser legs have mounting holes for securing the condenser to the steel supports or concrete pad.
3.2Electrical Connections
Refer to equipment nameplate regarding wire size and circuit protection requirements. Refer to electrical schematic when making connections. Make all wiring and electrical connection in accordance with local and national codes.
! WARNING
Risk of electric shock. Can cause injury or death.
Potentially lethal voltages exist within this equipment during operation. Observe all cautions and warnings on unit and in this manual.
The Liebert iCOM® microprocessor does not isolate power from the unit, even in the “Unit Off” mode. The only way to ensure that there is NO voltage inside the unit is to install and open a remote disconnect switch. Refer to unit electrical schematic.
Use voltmeter to make sure power is turned Off before making any electrical connections.
3.2.1Line Voltage
Line voltage electrical service is required for all
! WARNING
Risk of loose electrical wiring connections. Can cause overheating of wire, smoke and fire resulting in building and/or equipment damage, injury or death.
Use copper wire only and verify that all connections are tight.
3.2.2Low Voltage
A control interlock between the condenser and the indoor unit is required and is connected between 70 and 71 in the handy box of the indoor unit and the electric panel of the
3.2.3Liebert
Liebert
Liebert® Challenger 3000™ | 24 |