4.3.2High Pressure Valve - 350 psig (2413 kPa) System for
The valve may be adjusted using a 1/8" diameter rod. Turn the adjusting collar nut counterclockwise to raise head pressure; turn it clockwise to lower head pressure. Rotation directions are viewed from top of valve spring housing.
Figure 22 Metrex Valve adjustment
Adjusting collar nut
Table 12 Refrigerant control settings psi (kPa)
Low Pressure | Low Pressure | High Pressure |
Cut Out | Cut In | Cut Out |
|
|
|
20 (137.9) | 65 (448.2) | 400 (2758) |
|
|
|
Manual Flushing
The valve may be flushed by rotating the socket head screw clockwise. This screw must be in the OUT position (counterclockwise) for normal valve operation.
4.4Motorized Ball Valve—Digital Scroll Compressors
On digital scroll units, discharge pressure is controlled by a motorized ball valve. During unloaded operation, the pressure changes during each digital cycle could cause excessive repositions with a
4.4.1Control
The valve actuator operates on 24VAC power and is controlled by a
Liebert® Challenger 3000™ | 40 |