Emerson 3000 installation manual Line Voltage, Refrigerant Loop

Page 64

Split System Models

7.2.1Line Voltage

Line voltage electrical service is required for all condensing units at the location of the condensing unit. This power supply does not have to be the same voltage as the indoor unit. This separate power source may be 208, 230, 460 or 575V, 60 Hz; or 200, 230, or 380/415V, 50 Hz. A disconnect switch is required and must be mounted per local and national codes to isolate the unit for maintenance.

7.2.2Low Voltage

The control cable between the condensing unit and the evaporator unit is connected between terminals 1,2 and 3 on the terminal strip in the evaporator unit and the condensing unit control box. A fourth wire is required on systems with hot gas bypass. NEC Class 1 wiring is required. Glycol- cooled units also require a two-wire control connection to the drycooler and pump package.

7.3Piping Considerations

7.3.1 Refrigerant Loop

! WARNING

Risk of explosive discharge from high-pressure refrigerant. Can cause injury or death.

This unit contains fluids and gases under high pressure. Relieve pressure before working with piping.

NOTICE

Risk of improper refrigerant charge. Can cause equipment damage, environmental degradation and violation of national, state and local law.

Follow all applicable codes for handling refrigerant.

R22 and R407C are similar in properties—proper safety equipment and proper refrigeration tools are required on both types. Check unit nameplate for correct refrigerant type before topping off or recharging a system.

R407C refrigerant must be introduced and charged from the cylinder only as a liquid.

NOTICE

Risk of improper piping installation. Can cause contamination of hygroscopic oil with water.

When installing field piping, care must be taken to protect all refrigerant lines from the atmosphere, especially when using refrigerants, such as R407C which requires use of polyol ester oils. Do not allow the piping to stand open to air for more than 15 minutes. Units designed for R407C have a compressor that contains polyol ester oil, which is very hygroscopic; that is, it quickly absorbs water from the air. The longer the compressor piping is left open to air, the harder it will be to fully evacuate. If left open too long, the polyol ester oil may need to be replaced before achieving the required vacuum level.

NOTE

Complete all piping and evacuate lines before connecting quick connects when using an optional sweat adapter kit and field installed hard piping.

Follow all proper brazing practices including a dry nitrogen purge to maintain system cleanliness.

Liebert® Challenger 3000

58

Image 64
Contents Liebert Challenger 3000 with Liebert iCOM Page Table of Contents Chilled Water Models Split System ModelsFigures R407C RefrigerantTables Important Safety Instructions Liebert Challenger Important Safety Instructions System Descriptions Split Systems Prop Fan Air-CooledCentrifugal Fan Air-Cooled Water-CooledRoom Preparation Equipment InspectionLocation Considerations Equipment HandlingUnit net weight Handling With SkidRemoval of Skid Model Lb. kgUpflow BU cabinet dimensions Floor Cutout Dimensions Drain Line Piping ConsiderationsPiping connection size Piping connections for air-cooled units Downflow models Chilled Water Unit Connection Sizes-inPiping connections for air-cooled units Upflow models Installation Applicable to all Models Condensate Pump Line 1/2 OD CU used only Installation Applicable to all Models Installation Applicable to all Models Installation Applicable to all Models Installation Applicable to all Models Electrical Connections Facility Fluid and Piping MaintenanceHumidifier Supply Water-Optional Infrared Terminal Block For Customer Connectons Upflow Models with Liebert iCOM Downflow Models with Liebert iCOMPlenum Installation Balancing the Air DistributionUnder-Floor Discharge Systems Ducted ApplicationsChecklist for Completed Installation Line Voltage Condenser LocationLow Voltage Common to all models. See below for key to a dimension Air-cooled condenser statisticsLiebert Lee-Tempheater 43-9/16 51-7/16Refrigerant Piping Equivalent lengths feet for various pipe fittings Recommended line sizes OD copper, inchesCondenser refrigerant per serial tag Variable Fan Speed Control Piping Fan Speed Control SystemsVariable Fan Speed Control Materials Supplied Fan speed suction pressure transducer settings Variable Fan Speed ChargingDPN000349 Rev DPN001726 Liebert Lee-Temp Piping Liebert Lee-Temp Leak Check and Evacuation ProcedureLiebert Lee-Temp Controlled Materials Supplied Liebert Lee-TempCharging Liebert Lee-Temp suction pressure transducer settings407C Factory Piping Optional Piping Field Piping DPN001725 Condenser Factory Piping Field Piping Factory Piping Adjustment Water Regulating ValveRefrigerant control settings psi kPa Motorized Ball Valve-Digital Scroll CompressorsManual Flushing ControlControl Method StartupLocation Manual ControlDrycooler Location Drycooler InstallationPump and Drycooler Glycol Piping General GuidelinesRoom dew point temperatures Dry Bulb Wet Bulb Relative Dew Point HumidityVolume in standard Type L copper piping Filling InstructionsExpansion Tanks, Fluid Relief Valves and Other Devices Preparing the System for FillingGlycol Solutions Ethylene glycol concentrationsFilling the System For expansion tank dimensions, see on 43-3/16 43-9/16 110 5mmSee Note 30-1/4 483mm 1097mmMounting hole dimensional data Drycooler dataGlycol pump data Pump Pump Suction Pump Discharge Connection,Field Piping General arrangement-Glycol-cooled models with digital scroll Expansion Tank Field-Installed at Pressure Glycol Regulating Valve Testing Valve FunctionMotor Ball Valve-Digital Scroll Compressors Chilled Water Models WAY Valve Air-Cooled Condensing Units Water/Glycol-Cooled Condensing UnitsRefrigerant Loop R407C Charge Unit refrigerant chargeModel Lb kg Recommended refrigerant lines R407C sizes OD copper Line charges refrigerant per 100 ft m of Type L copper tubeLine coupling sizes Quick Connect Fittings Unit Dimensions See Table Outdoor Air-Cooled Condensing UnitsPFCZ42A-L PFCZ41A-L Outdoor air-cooled condensing unit-top air discharge models See Table36-1/4 38-1/2 Piping and electrical connections top air discharge152 Field-supplied unit disconnect switch Ton High Ambient Ton Quiet-LineInstalling the Indoor Condensing Unit Model Net Weight 60 Hz 50 Hz Lb kg MC40A MC39ACentrifugal Air-Cooled Condensing Units Indoor centrifugal condensing unitDucting Airflow CFM CMHPiping Connections Wire connections from evaporator DPN000207Rev0 ModTon centrifugal air-cooled condensing unit dimensional data AIR Cooled Water Cooled Water and Glycol-Cooled Condensing Units Piping ConsiderationsTon Connection Sizes Condenser Water RequirementsGlycol Systems Ton water/glycol-cooled condensing unitDPN000209 Ton water/glycol-cooled condensing unit dimensional data WATER/GLYCOL Temperature Gauge Pressure Psig KPa R407C RefrigerantCalculating Subcooling Temperature Pressure Gauge Psig KPaExample Page Ne t Ppor t Is tTwor k Care
Related manuals
Manual 60 pages 24.1 Kb Manual 88 pages 36.41 Kb Manual 32 pages 13.16 Kb Manual 22 pages 3.64 Kb Manual 76 pages 17.32 Kb Manual 184 pages 52.9 Kb