Emerson 3000 Filling Instructions, Expansion Tanks, Fluid Relief Valves and Other Devices

Page 51

Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor

5.4.1Expansion Tanks, Fluid Relief Valves and Other Devices

An expansion tank must be provided for expansion and contraction of the fluid due to temperature change in this closed system. Vents are required at system high points to vent trapped air when filling the system. A relief valve is a also a necessary piping component.

Depending on the complexity of the system, various other devices may be specified. Pressure gauges, flow switches, automatic air separator, tempering valves, standby pumps, sensors for electrical controls, and flow switches are just a few of these devices.

NOTICE

Risk of frozen fluids. Can cause piping and system components to rupture and leak, resulting in equipment and building damage.

Immediately following the use of water for leak testing or system cleaning, charge the system with the proper percentage of glycol and water for your coldest design ambient. Complete system drain-down cannot be assured.

5.5Filling Instructions

5.5.1 Preparing the System for Filling

It is important to remove any dirt, oil or metal filings that may contaminate the cooling system piping in order to prevent contamination of the fresh glycol solution and fouling of the drycooler piping. The system should be flushed thoroughly using a mild cleaning solution or high-quality water and then completely drained before charging with glycol. Cleaning new systems is just as important as cleaning old ones. New systems can be coated with oil or a protective film; dirt and scale are also common. Any residual contaminants could adversely affect the heat transfer stability and performance of your system. In many cases, in both old and new systems, special cleaners are needed to remove scale, rust and hydrocarbon foulants from pipes, manifolds and passages. Clean heat transfer surfaces are important in maintaining the integrity of the heating/cooling system. For more information on cleaners and degreasers, contact your sales representative. Follow the manufacturer's instructions when using these products.

Calculate the internal volume of the system as closely as possible. See Table 14 and Table 16 for unit volumes. Use volume in Table 15 for glycol piping volumes.

Table 14

Indoor unit glycol volume approximate gallons (liters) max.

 

 

 

 

 

 

 

 

Model (50 Hz)

 

Glycol-Cooled

GLYCOOL

 

 

 

 

 

 

 

 

 

 

046WG/(045WG)

 

 

1.2 (4.5)

 

 

 

 

 

 

 

 

 

 

 

071WG/(070WG)

 

 

2.0 (7.5)

 

 

 

 

 

 

 

 

 

 

 

061G/(058G)

 

 

 

4.0 (15.1)

 

 

 

 

 

 

 

 

Table 15 Volume in standard Type “L” copper piping

 

 

 

 

 

 

Diameter (in.)

 

Volume

 

 

 

 

 

 

 

 

Outside

 

Inside

 

Gal/Ft

 

L/M

 

 

 

 

 

 

 

 

 

 

1/2

 

 

0.123

 

0.008

 

0.01

 

 

 

 

 

 

 

 

 

 

5/8

 

 

0.555

 

0.012

 

0.15

 

 

 

 

 

 

 

 

 

 

3/4

 

 

0.666

 

0.018

 

0.22

 

 

 

 

 

 

 

 

 

 

7/8

 

 

0.785

 

0.025

 

0.31

 

 

 

 

 

 

 

 

 

 

1-1/8

 

 

1.025

 

0.043

 

0.53

 

 

 

 

 

 

 

 

 

 

 

45

Liebert® Challenger 3000

Image 51
Contents Liebert Challenger 3000 with Liebert iCOM Page Table of Contents Split System Models Chilled Water ModelsR407C Refrigerant FiguresTables Important Safety Instructions Liebert Challenger Important Safety Instructions System Descriptions Water-Cooled Split SystemsProp Fan Air-Cooled Centrifugal Fan Air-CooledEquipment Handling Room PreparationEquipment Inspection Location ConsiderationsModel Lb. kg Unit net weightHandling With Skid Removal of SkidUpflow BU cabinet dimensions Floor Cutout Dimensions Piping Considerations Drain LinePiping connection size Chilled Water Unit Connection Sizes-in Piping connections for air-cooled units Downflow modelsPiping connections for air-cooled units Upflow models Installation Applicable to all Models Condensate Pump Line 1/2 OD CU used only Installation Applicable to all Models Installation Applicable to all Models Installation Applicable to all Models Installation Applicable to all Models Facility Fluid and Piping Maintenance Electrical ConnectionsHumidifier Supply Water-Optional Infrared Terminal Block For Customer Connectons Downflow Models with Liebert iCOM Upflow Models with Liebert iCOMDucted Applications Plenum InstallationBalancing the Air Distribution Under-Floor Discharge SystemsChecklist for Completed Installation Condenser Location Line VoltageLow Voltage 43-9/16 51-7/16 Common to all models. See below for key to a dimensionAir-cooled condenser statistics Liebert Lee-TempheaterRefrigerant Piping Recommended line sizes OD copper, inches Equivalent lengths feet for various pipe fittingsCondenser refrigerant per serial tag Fan Speed Control Systems Variable Fan Speed Control PipingVariable Fan Speed Control Materials Supplied Variable Fan Speed Charging Fan speed suction pressure transducer settingsDPN000349 Rev DPN001726 Liebert Lee-Temp Leak Check and Evacuation Procedure Liebert Lee-Temp PipingLiebert Lee-Temp Controlled Materials Supplied Liebert Lee-Temp suction pressure transducer settings Liebert Lee-TempCharging407C Factory Piping Optional Piping Field Piping DPN001725 Condenser Factory Piping Field Piping Factory Piping Water Regulating Valve AdjustmentControl Refrigerant control settings psi kPaMotorized Ball Valve-Digital Scroll Compressors Manual FlushingManual Control Control MethodStartup Location Drycooler Installation Drycooler Location Pump and Drycooler General Guidelines Glycol PipingDry Bulb Wet Bulb Relative Dew Point Humidity Room dew point temperaturesPreparing the System for Filling Volume in standard Type L copper pipingFilling Instructions Expansion Tanks, Fluid Relief Valves and Other DevicesEthylene glycol concentrations Glycol SolutionsFilling the System 483mm 1097mm For expansion tank dimensions, see on43-3/16 43-9/16 110 5mm See Note 30-1/4Pump Pump Suction Pump Discharge Connection, Mounting hole dimensional dataDrycooler data Glycol pump dataField Piping General arrangement-Glycol-cooled models with digital scroll Expansion Tank Field-Installed at Pressure Testing Valve Function Glycol Regulating ValveMotor Ball Valve-Digital Scroll Compressors Chilled Water Models WAY Valve Water/Glycol-Cooled Condensing Units Air-Cooled Condensing UnitsRefrigerant Loop Unit refrigerant charge R407C ChargeModel Lb kg Line charges refrigerant per 100 ft m of Type L copper tube Recommended refrigerant lines R407C sizes OD copperLine coupling sizes Quick Connect Fittings Outdoor Air-Cooled Condensing Units Unit Dimensions See TablePFCZ42A-L PFCZ41A-L See Table Outdoor air-cooled condensing unit-top air discharge modelsPiping and electrical connections top air discharge 36-1/4 38-1/2152 Ton High Ambient Ton Quiet-Line Field-supplied unit disconnect switchIndoor centrifugal condensing unit Installing the Indoor Condensing UnitModel Net Weight 60 Hz 50 Hz Lb kg MC40A MC39A Centrifugal Air-Cooled Condensing UnitsAirflow CFM CMH DuctingPiping Connections Mod Wire connections from evaporatorDPN000207 Rev0Ton centrifugal air-cooled condensing unit dimensional data AIR Cooled Water Cooled Condenser Water Requirements Water and Glycol-Cooled Condensing UnitsPiping Considerations Ton Connection SizesTon water/glycol-cooled condensing unit Glycol SystemsDPN000209 Ton water/glycol-cooled condensing unit dimensional data WATER/GLYCOL R407C Refrigerant Temperature Gauge Pressure Psig KPaTemperature Pressure Gauge Psig KPa Calculating SubcoolingExample Page Care Ne tPpor t Is t Twor k