Emerson 3000 installation manual Checklist for Completed Installation

Page 29

Installation (Applicable to all Models)

2.9Checklist for Completed Installation

___ 1. Unpack and check received material.

___ 2. Proper clearance for service access has been maintained around the equipment.

___ 3. Equipment is level and mounting fasteners are tight.

___ 4. Piping completed to refrigerant or coolant loop (if required). Piping has been leak checked, evacuated and charged (if required).

___ 5. Check piping within the unit & outside of the unit. Remove potential of rub-through or chaffing.

___ 6. Condensate pump installed (if required).

___ 7. Drain line connected and checked for leaks.

___ 8. Water supply line connected to humidifier and/or water/glycol condenser (if required) and checked for leaks.

___ 9. Field provided pan with drain installed under all ceiling mounted fluid condensing units (if installed).

___ 10. Filter box installed (if applicable).

___ 11. Ducting completed (if applicable).

___ 12. Filter(s) installed.

___ 13. Line voltage to power wiring matches equipment serial tag.

___ 14. Power wiring connections completed between disconnect switch, evaporator and condensing unit, including earth ground.

___ 15. Power line circuit breakers or fuses have proper ratings for equipment installed.

___ 16. Control wiring connections completed to evaporator and condensing unit.

___ 17. Verify water detection is properly installed around all units (if installed).

___ 18. All wiring connections are tight.

___ 19. Control panel DIP switches set based on customer requirements.

___ 20. Foreign materials have been removed from, in and around all equipment installed (literature, shipping materials, construction materials, tools, etc.).

___ 21. Fans and blowers rotate freely.

___ 22. Inspect all piping connections for leaks during initial operations. Correct as needed.

___ 23. Verify that a blank startup sheet has been sent with the unit(s) and is ready to be completed by the installer.

___ 24. Rubber band removed from humidifier and/or evaporator pan float switch (if supplied).

23

Liebert® Challenger 3000

Image 29
Contents Liebert Challenger 3000 with Liebert iCOM Page Table of Contents Split System Models Chilled Water ModelsR407C Refrigerant FiguresTables Important Safety Instructions Liebert Challenger Important Safety Instructions System Descriptions Prop Fan Air-Cooled Split SystemsCentrifugal Fan Air-Cooled Water-CooledEquipment Inspection Room PreparationLocation Considerations Equipment HandlingHandling With Skid Unit net weightRemoval of Skid Model Lb. kgUpflow BU cabinet dimensions Floor Cutout Dimensions Piping connection size Piping ConsiderationsDrain Line Chilled Water Unit Connection Sizes-in Piping connections for air-cooled units Downflow modelsPiping connections for air-cooled units Upflow models Installation Applicable to all Models Condensate Pump Line 1/2 OD CU used only Installation Applicable to all Models Installation Applicable to all Models Installation Applicable to all Models Installation Applicable to all Models Humidifier Supply Water-Optional Infrared Facility Fluid and Piping MaintenanceElectrical Connections Terminal Block For Customer Connectons Downflow Models with Liebert iCOM Upflow Models with Liebert iCOMBalancing the Air Distribution Plenum InstallationUnder-Floor Discharge Systems Ducted ApplicationsChecklist for Completed Installation Low Voltage Condenser LocationLine Voltage Air-cooled condenser statistics Common to all models. See below for key to a dimensionLiebert Lee-Tempheater 43-9/16 51-7/16Refrigerant Piping Condenser refrigerant per serial tag Recommended line sizes OD copper, inchesEquivalent lengths feet for various pipe fittings Variable Fan Speed Control Materials Supplied Fan Speed Control SystemsVariable Fan Speed Control Piping Variable Fan Speed Charging Fan speed suction pressure transducer settingsDPN000349 Rev DPN001726 Liebert Lee-Temp Controlled Materials Supplied Liebert Lee-Temp Leak Check and Evacuation ProcedureLiebert Lee-Temp Piping 407C Liebert Lee-Temp suction pressure transducer settingsLiebert Lee-TempCharging Factory Piping Optional Piping Field Piping DPN001725 Condenser Factory Piping Field Piping Factory Piping Water Regulating Valve AdjustmentMotorized Ball Valve-Digital Scroll Compressors Refrigerant control settings psi kPaManual Flushing ControlStartup Control MethodLocation Manual ControlPump and Drycooler Drycooler InstallationDrycooler Location General Guidelines Glycol PipingDry Bulb Wet Bulb Relative Dew Point Humidity Room dew point temperaturesFilling Instructions Volume in standard Type L copper pipingExpansion Tanks, Fluid Relief Valves and Other Devices Preparing the System for FillingEthylene glycol concentrations Glycol SolutionsFilling the System 43-3/16 43-9/16 110 5mm For expansion tank dimensions, see onSee Note 30-1/4 483mm 1097mmDrycooler data Mounting hole dimensional dataGlycol pump data Pump Pump Suction Pump Discharge Connection,Field Piping General arrangement-Glycol-cooled models with digital scroll Expansion Tank Field-Installed at Pressure Motor Ball Valve-Digital Scroll Compressors Testing Valve FunctionGlycol Regulating Valve Chilled Water Models WAY Valve Water/Glycol-Cooled Condensing Units Air-Cooled Condensing UnitsRefrigerant Loop Model Lb kg Unit refrigerant chargeR407C Charge Line coupling sizes Line charges refrigerant per 100 ft m of Type L copper tubeRecommended refrigerant lines R407C sizes OD copper Quick Connect Fittings Outdoor Air-Cooled Condensing Units Unit Dimensions See TablePFCZ42A-L PFCZ41A-L See Table Outdoor air-cooled condensing unit-top air discharge models152 Piping and electrical connections top air discharge36-1/4 38-1/2 Ton High Ambient Ton Quiet-Line Field-supplied unit disconnect switchModel Net Weight 60 Hz 50 Hz Lb kg MC40A MC39A Installing the Indoor Condensing UnitCentrifugal Air-Cooled Condensing Units Indoor centrifugal condensing unitAirflow CFM CMH DuctingPiping Connections DPN000207 Wire connections from evaporatorRev0 ModTon centrifugal air-cooled condensing unit dimensional data AIR Cooled Water Cooled Piping Considerations Water and Glycol-Cooled Condensing UnitsTon Connection Sizes Condenser Water RequirementsTon water/glycol-cooled condensing unit Glycol SystemsDPN000209 Ton water/glycol-cooled condensing unit dimensional data WATER/GLYCOL R407C Refrigerant Temperature Gauge Pressure Psig KPaExample Temperature Pressure Gauge Psig KPaCalculating Subcooling Page Ppor t Is t Ne tTwor k Care
Related manuals
Manual 60 pages 24.1 Kb Manual 88 pages 36.41 Kb Manual 32 pages 13.16 Kb Manual 22 pages 3.64 Kb Manual 76 pages 17.32 Kb Manual 184 pages 52.9 Kb

3000 specifications

The Emerson 3000 is a cutting-edge control system designed to enhance the efficiency, reliability, and precision of industrial operations. Employed across various sectors such as oil and gas, pharmaceutical, food and beverage, and power generation, the Emerson 3000 has gained recognition for its robustness and versatility.

One of the main features of the Emerson 3000 is its advanced process control capability. With integrated control algorithms, it can optimize complex processes in real-time, resulting in significant improvements in production rates and reduced operational costs. The system's predictive analytics capabilities enable operators to anticipate equipment failures and maintenance needs, allowing for proactive management and minimizing downtime.

The Emerson 3000 features a modular architecture, providing flexibility for scaling and customization. Operators can easily tailor the system to fit specific application needs, whether it requires additional control loops or integration with other systems. This adaptability is particularly beneficial for facilities planning for future expansions or modifications.

Another technology highlight of the Emerson 3000 is its seamless integration with the latest Internet of Things (IoT) advancements. The system is designed to communicate effectively with a variety of smart devices and sensors, harnessing data to create insightful analytics that drive operational excellence. This connectivity empowers businesses to leverage big data for improved decision-making and increased agility.

Additionally, the Emerson 3000 incorporates state-of-the-art cybersecurity measures to safeguard critical data and operations. With built-in security protocols and regular updates, the system protects against emerging cyber threats, ensuring the integrity of the control network.

User experience is also a focal point of the Emerson 3000. The intuitive graphical user interface presents complex data in a user-friendly format, making it easier for operators to monitor system performance and respond to alerts quickly. This ease of use contributes to enhanced safety and operational efficiency.

In summary, the Emerson 3000 represents a fusion of advanced process control, modular design, IoT connectivity, robust cybersecurity, and user-centric interface, making it an ideal choice for industries seeking to enhance their operational performance while adapting to ever-evolving technological landscapes.