Emerson 3000 installation manual Control Method, Startup, Location, Manual Control

Page 47

Water-Cooled Models—Self-Contained Compressor

Control Method

The control utilizes an upper and lower pressure threshold with a 35psi (241kPa) deadband to reduce valve movement. If the liquid pressure is between the upper and lower threshold, the valve remains at the current position. If the liquid pressure exceeds the upper threshold the valve opens, and if the pressure falls below the lower threshold the valve closes. There are multiple adjustment bands to ease discharge pressure back into control range.

4.4.2Adjustment

Both pressure thresholds can be shifted simultaneously over a 50psi (345kPa) range (the 35psi [241kPa] differential remains constant). The ball valve setpoint offset parameter in the Liebert iCOM® Service menu can be adjusted from 0 to 50 PSI (345 kPa) to raise or lower the control band similar to the pressure adjustment on a water regulating valve. Changing the setpoint offset will adjust the pressure thresholds for both circuits. Units are factory-set at a 30psi (207 kPa) setpoint offset (30psi [207 kPa] above minimum). This results in a 220psiA (1517kPa) lower threshold and a 255psiA (1758kPa) upper threshold pressure.

4.4.3Startup

The setpoint offset is adjusted to the minimum value during startup, then changes to the set value once the compressor reaches normal operating pressures. Changes in fluid temperature could cause pressure changes that do not result in valve movement within the deadband. Fan cycling stats should be set to prevent continuous fluid temperature swings greater than 10°F (5.6°C).

4.4.4Location

The motorized ball valve is located in the condenser fluid return line. Three-way valves are piped in a mixing arrangement with the common port at the valve outlet.

4.4.5Manual Control

The valve can be manually set by disconnecting AC power, depressing the manual override button on the valve actuator and adjusting the valve position with the handle. The motorized ball also can be controlled through the Liebert iCOM’s Service menu using manual mode to override the normal control.

41

Liebert® Challenger 3000

Image 47
Contents Liebert Challenger 3000 with Liebert iCOM Page Table of Contents Split System Models Chilled Water ModelsR407C Refrigerant FiguresTables Important Safety Instructions Liebert Challenger Important Safety Instructions System Descriptions Water-Cooled Split SystemsProp Fan Air-Cooled Centrifugal Fan Air-CooledEquipment Handling Room PreparationEquipment Inspection Location ConsiderationsModel Lb. kg Unit net weightHandling With Skid Removal of SkidUpflow BU cabinet dimensions Floor Cutout Dimensions Piping connection size Piping ConsiderationsDrain Line Chilled Water Unit Connection Sizes-in Piping connections for air-cooled units Downflow modelsPiping connections for air-cooled units Upflow models Installation Applicable to all Models Condensate Pump Line 1/2 OD CU used only Installation Applicable to all Models Installation Applicable to all Models Installation Applicable to all Models Installation Applicable to all Models Humidifier Supply Water-Optional Infrared Facility Fluid and Piping MaintenanceElectrical Connections Terminal Block For Customer Connectons Downflow Models with Liebert iCOM Upflow Models with Liebert iCOMDucted Applications Plenum InstallationBalancing the Air Distribution Under-Floor Discharge SystemsChecklist for Completed Installation Low Voltage Condenser LocationLine Voltage 43-9/16 51-7/16 Common to all models. See below for key to a dimensionAir-cooled condenser statistics Liebert Lee-TempheaterRefrigerant Piping Condenser refrigerant per serial tag Recommended line sizes OD copper, inchesEquivalent lengths feet for various pipe fittings Variable Fan Speed Control Materials Supplied Fan Speed Control SystemsVariable Fan Speed Control Piping Variable Fan Speed Charging Fan speed suction pressure transducer settingsDPN000349 Rev DPN001726 Liebert Lee-Temp Controlled Materials Supplied Liebert Lee-Temp Leak Check and Evacuation ProcedureLiebert Lee-Temp Piping 407C Liebert Lee-Temp suction pressure transducer settingsLiebert Lee-TempCharging Factory Piping Optional Piping Field Piping DPN001725 Condenser Factory Piping Field Piping Factory Piping Water Regulating Valve AdjustmentControl Refrigerant control settings psi kPaMotorized Ball Valve-Digital Scroll Compressors Manual FlushingManual Control Control MethodStartup LocationPump and Drycooler Drycooler InstallationDrycooler Location General Guidelines Glycol PipingDry Bulb Wet Bulb Relative Dew Point Humidity Room dew point temperaturesPreparing the System for Filling Volume in standard Type L copper pipingFilling Instructions Expansion Tanks, Fluid Relief Valves and Other DevicesEthylene glycol concentrations Glycol SolutionsFilling the System 483mm 1097mm For expansion tank dimensions, see on43-3/16 43-9/16 110 5mm See Note 30-1/4Pump Pump Suction Pump Discharge Connection, Mounting hole dimensional dataDrycooler data Glycol pump dataField Piping General arrangement-Glycol-cooled models with digital scroll Expansion Tank Field-Installed at Pressure Motor Ball Valve-Digital Scroll Compressors Testing Valve FunctionGlycol Regulating Valve Chilled Water Models WAY Valve Water/Glycol-Cooled Condensing Units Air-Cooled Condensing UnitsRefrigerant Loop Model Lb kg Unit refrigerant chargeR407C Charge Line coupling sizes Line charges refrigerant per 100 ft m of Type L copper tubeRecommended refrigerant lines R407C sizes OD copper Quick Connect Fittings Outdoor Air-Cooled Condensing Units Unit Dimensions See TablePFCZ42A-L PFCZ41A-L See Table Outdoor air-cooled condensing unit-top air discharge models152 Piping and electrical connections top air discharge36-1/4 38-1/2 Ton High Ambient Ton Quiet-Line Field-supplied unit disconnect switchIndoor centrifugal condensing unit Installing the Indoor Condensing UnitModel Net Weight 60 Hz 50 Hz Lb kg MC40A MC39A Centrifugal Air-Cooled Condensing UnitsAirflow CFM CMH DuctingPiping Connections Mod Wire connections from evaporatorDPN000207 Rev0Ton centrifugal air-cooled condensing unit dimensional data AIR Cooled Water Cooled Condenser Water Requirements Water and Glycol-Cooled Condensing UnitsPiping Considerations Ton Connection SizesTon water/glycol-cooled condensing unit Glycol SystemsDPN000209 Ton water/glycol-cooled condensing unit dimensional data WATER/GLYCOL R407C Refrigerant Temperature Gauge Pressure Psig KPaExample Temperature Pressure Gauge Psig KPaCalculating Subcooling Page Care Ne tPpor t Is t Twor k