6-2. 240 Volt Duplex Receptacle (Optional)
Y If unit does not have GFCI re- ceptacles, use
1 240 V 15 A AC Receptacle RC1
1 |
| Receptacle supplies 60 Hz single- | ||||
|
| phase power at weld/power speed. | ||||
|
| Maximum output is 3 kVA/kW. | ||||
|
| 2 | Circuit Breaker CB1 |
| ||
|
| 3 | Circuit Breaker CB2 |
| ||
|
| CB1 and CB2 protect the recep- | ||||
|
| tacles from overload. If CB1 or CB2 | ||||
|
| opens, the 240 V receptacle and | ||||
2 | 3 | half of the 120 V receptacle does | ||||
not work. | 120 volts | may | still be | |||
|
| present at the 240 V receptacle. | ||||
|
| Press button to reset circuit | ||||
|
| breaker. |
|
|
| |
|
| . If a circuit breaker continues to | ||||
|
|
| open, | contact | a | Factory |
|
|
| Authorized Service Agent. |
Combined output of all receptacles is 3 kVA/kW. Auxiliary power is not affected by weld output.
EXAMPLE: If 10 A is drawn from the 240 V receptacle, only 5 A is avail- able at the 120 V receptacle:
(240 V x 10 A) + (120 V x 5 A) = 3.0 kVA/kW