9-2. Run-In Procedure Using Load Bank

4

2

1

3

YStop engine.

YDo not touch hot exhaust pipe, engine parts, or load bank/grid.

YKeep exhaust and pipe away from flammables.

1 Load Bank

Turn all load bank switches Off. If needed, connect load bank to 115 volts ac wall receptacle or genera- tor auxiliary power receptacle.

2 Welding Generator

Place A/V range switch in maxi- mum position, A/V control in mini- mum position, and Output Selector switch (if present) in either DC position.

3 Weld Cables

Connect load bank to generator weld output terminals using proper size weld cables with correct connectors. Observe correct polarity.

Start engine and run for several minutes.

Set load bank switches and then adjust generator A/V control so load equals rated generator output (see nameplate).

Check generator and load bank meters after first five minutes then every fifteen minutes to be sure generator is loaded properly.

.Check oil level frequently dur- ing run-in; add oil if needed.

After one hour (minimum) place A/V control in minimum position, then turn off load bank to remove load. Run engine several minutes at no load.

YStop engine and let cool.

4 Engine Exhaust Pipe

Repeat procedure if wetstacking is present.

S-0683

OM-474 Page 39

Image 43
Contents July OM-474Processes DescriptionFrom Hobart to You Table of Contents Page ARC Rays can burn eyes and skin Symbol UsageArc Welding Hazards Electric Shock can killEngine Hazards Engine Heat can cause fire Battery Explosion can BlindMoving Parts can cause injury Engine Exhaust Gases can killARC Welding can cause interference Principal Safety StandardsEMF Information Radiation can cause interferenceLES Fumées ET LES GAZ peuvent être dangereux Signification des symbolesConsignes DE Sécurité Lire Avant Utilisation UN Choc Électrique peut tuerLE Bruit peut affecter l’ouïe LE Soudage peut provoquer un in- cendie ou une explosionDES Particules Volantes peuvent blesser les yeux DES Pièces Chaudes peuvent provoquer des brûlures gravesLA Chute DE L’APPAREIL peut blesser DES Organes Mobiles peuvent provoquer des blessures’EXPLOSION DE LA Batterie peut LA Chaleur DU Moteur peut pro- voquer un incendieConsignes relatives aux stimulateurs cardiaques Principales normes de sécuritéInformation sur les champs électromagnétiques LE Soudage À L’ARC risque de provoquer des interférencesDefinitions SpecificationsSymbols And Definitions Weld, Power, And Engine SpecificationsFuel Consumption Dimensions, Weights, And Operating AnglesDimensions WeightMinutes Welding AC Auxiliary PowerDuty Cycle And Overheating 60% Duty Cycle At 350 Amperes5 KVA/KW Single-Phase Auxiliary Power Plant No Weld Load Optional AC Power Plant Curves12.5 KVA/KW Three-Phase Auxiliary Power Plant No Weld Load 100 Ranges 190-Max 110-270 Volt-Ampere CurvesDC Volts CC/DC Standard AC Amperes CV/DC Models with Optional CV-3 ModuleInstalling Welding Generator InstallationConnecting The Battery Do not use gasoline. Gasoline will damage engine Installing MufflerTemperatures below 0 F -18C 13 mm Full Diesel Valve Open Engine Prestart Checks10 100% Duty Cycle Connecting To Weld Output TerminalsSelecting Weld Cable Sizes 100 ft 30 m Or LessStop engine Remote 14 Receptacle RC3 Information Optional, See SectionTerminal Strip 3T Connections Optional Socket InformationFront Panel Controls See Section Operating Welding GeneratorStop engine and fix trouble if either warning light goes on Ampere Range SwitchDo not switch under load Description Of Front Panel Controls See SectionExample Combination remote amperage control Remote Control OptionalVolt Duplex And Optional Gfci Receptacles Operating Auxiliary EquipmentOpen Contact Volt Duplex Receptacle OptionalSet Engine Control switch to Run when using auxiliary power Connecting Optional Auxiliary Power PlantFront Maintenance and Troubleshooting Maintenance Label To Clean air filter Servicing Air CleanerDo not clean housing with air hose To replace fuel filter Servicing Fuel SystemStop engine and let cool To drain water from fuel systemIdle Speed Adjustment Adjusting Engine SpeedEngine Speed No Load Changing Engine Oil And Filter If any fuse or circuit breaker Overload ProtectionTrouble Remedy Inspecting And Cleaning Optional Spark Arrestor MufflerTroubleshooting WeldingAuxiliary Power See engine manual Coolant temperature gets too high see SectionCheck engine control switch, and replace if necessary EngineOM-474 Circuit Diagram For Welding Generator For Standard Models Electrical DiagramsOM-474 193 989-B Wetstacking RUN-IN ProcedureLoad Bank Run-In Procedure Using Load BankFrom flammables Run-In Procedure Using Resistance GridDo not touch hot exhaust Bank/gridSelecting Equipment Auxiliary Power GuidelinesGrounding Generator To Truck Or Trailer Frame Use ground device as stated in electrical codes Grounding When Supplying Building SystemsHow Much Power Does Equipment Require? Earth ground if supplyingFarm/Home Equipment Rating Starting Watts Running Watts Approximate Power Requirements For Industrial MotorsApproximate Power Requirements For Farm/Home Equipment Industrial Motors Rating Starting Watts Running WattsContractor Rating Starting Watts Running Watts Approximate Power Requirements For Contractor EquipmentKVA/HP x HP x Power Required To Start MotorHow Much Power Can Generator Supply? Single-Phase Induction Motor Starting RequirementsProtection is already present Typical Connections To Supply Standby PowerWelding Generator Auxiliary Power output circuit Item 4 is not necessary if circuitCurrent Load Watts Amperes Selecting Extension Cord Use Shortest Cord Possible101 102 105 104 103 Parts List65 66 Includes Items Dia Part Description Mkgs Quantity PLG9,RC9 PC4 Control Box w/Components Control Box w/Components -4 ItemGenerator Generator -1 Item Panel, Front w/Components Panel, Front w/Components -1 Item Page Support ServiceHobart Welding Products Contact your Distributor forCall