Carrier 40RMQ installation instructions Typical 40RMS Chilled Water Piping

Page 17

Table 3 Ð Fitting Requirements (cont)

UNIT

ACCESS

CONNECTION

CIRCUIT

FITTINGS REQUIRED²

HOLE NO.*

TYPE

 

(in.)

 

 

 

 

5

Supply

Lower

21¤8

Long Radius Elbow

 

21¤8

Nipple, 31¤2 L

 

 

 

 

21¤8

Long Radius Elbow

 

 

 

 

21¤8

Long Radius Elbow

 

6

Return

Lower

21¤8

Nipple, 3 L

40RMS

 

 

 

21¤8

Long Radius Elbow

028, 034

7

Return

Upper

21¤8

Long Radius Elbow

 

21¤8

Nipple, 67¤8 L

 

 

 

 

21¤8

Long Radius Elbow

 

 

 

 

21¤8

Long Radius Elbow

 

8

Supply

Upper

21¤8

Nipple, 117¤8 L

 

 

 

 

21¤8

Long Radius Elbow

 

1

Suction

Lower

13¤8

Street Elbow

 

13¤8

Nipple, 3 L

 

 

 

 

13¤8

Long Radius Elbow

 

2

Liquid

Lower

5¤8

Street Elbow

 

5¤8

Nipple, 73¤4 L

40RM

 

 

 

5¤8

Long Radius Elbow

 

 

 

5¤8

Street Elbow

034

3

Liquid

Upper

5¤8

Nipple, 181¤2 L

 

 

 

 

 

5¤8

Long Radius Elbow

 

 

 

 

13¤8

Nipple, 43¤16 L

 

4

Suction

Upper

13¤8

Long Radius Elbow

 

13¤8

Nipple, 191¤4 L

 

 

 

 

 

 

 

 

13¤8

Long Radius Elbow

*See Fig. 4 for access hole location by number.

²Fittings are listed in order from header or tee stub connection out to access hole in corner support post.

Chilled Water Piping Ð See Tables 1C and 1F for chilled water connection sizes. For ease in brazing, it is rec- ommended that all internal solder joints be made before unit is placed in ®nal position.

Knockouts are provided in the unit corner posts for 40RM and 40RMQ refrigerant piping; additional ®eld-fabricated ac- cess holes are required for 40RMS chilled water piping. See Fig. 4, which lists recommended knockouts and access holes to use for each 40RMS unit size.

To size, design, and install chilled water piping, consult the Carrier System Design manual. See Fig. 9 for an ex- ample of a typical installation. Recommended ®ttings are listed in Table 3.

To access 40RMS coil vents and drains, remove the unit side panel over the coil header. Vent and drain plugs are on the top and bottom of header, respectively. See the Service section for information on preventing coil freeze-up during winter.

Fig. 9 Ð Typical 40RMS Chilled Water Piping

17

Image 17
Contents Installation, Start-Up Service Instructions Ð 40RM Physical Data, English Unit 40RMQ Ð 40RMQ Physical Data, EnglishChilled Water Coil Ð 40RMS Physical Data, EnglishUnit 40RMS Ð 40RM Physical Data, SI Ð 40RMQ Physical Data, SI Ð 40RMS Physical Data, SI Unit Unit Weight Ð Dimensions Ð Sizes40RM014 Ð Dimensions Ð Sizes 028,034 40RMQ 40RMS UnitNumbers Refrigerant and Chilled Water Piping Access HolesFace-Split Coil Suction Liquid Line Piping Typical Liquid Unit Line Quantity 38AQS Size Required Reference Factory-Installed Nozzle and Distributor DataTXV Distributor Feeder Tubes Nozzle Unit PER Distributor 40RMQ Fitting Requirements11¤8 Street Elbow Nipple, 23¤4 L Long Radius Elbow Liquid Typical 40RMS Chilled Water Piping Condensate Drains Wiring and Service Access Side Panel Removed Electrical Data, Standard Motors Voltage FAN Motor Power Supply Unit PH-HZFLA MocpMocp Ð Electrical Data, Alternate MotorsFLA Ð Fan Contactor Coil Data Manufacturer Lubricant Lubricant DataFan Shaft Bearing Fan Pulley Alignment Ð Align as follows Ð Fan Motor Data, Alternate Motor Ð English Ð Fan Motor Data, Standard Motor Ð English40RMQ 40RMS Unit 40RMS 40RMQ UnitÐ Fan Motor Data, Alternate Motor Ð SI Ð Fan Motor Data, Standard Motor Ð SIÐ Medium-Static Drive Data, 60 Hz Ð English Ð Standard Drive Data, 60 Hz Ð EnglishMotor Drive FAN DriveÐ Standard Drive Data, 50 Hz Ð English Ð High-Static Drive Data, 60 Hz Ð EnglishÐ High-Static Drive Data, 50 Hz Ð English Ð Medium-Static Drive Data, 50 Hz Ð English40RMQ Unit Ð Standard Drive Data, 60 Hz Ð SIÐ Medium-Static Drive Data, 60 Hz Ð SI Ð Standard Drive Data, 50 Hz Ð SI Ð High-Static Drive Data, 60 Hz Ð SIÐ High-Static Drive Data, 50 Hz Ð SI Ð Medium-Static Drive Data, 50 Hz Ð SIAirflow Ð Fan Performance Data Ð 0.0-1.2 in. wg ESP Ð EnglishÐ Fan Performance Data Ð 1.4-2.4 in. wg ESP Ð English Unit Airflow Pressure Drop Ð Fan Performance Data Ð 0-300 Pa ESP Ð SI Ð Fan Performance Data Ð 350-600 Pa ESP Ð SI Filter Removal/Replacement Page Page Copyright 1995 Carrier Corporation START-UP Checklist Comp A1 Comp B1 Check Voltage Imbalance