Carrier 40RMS, 40RMQ Ð Standard Drive Data, 60 Hz Ð SI, Ð Medium-Static Drive Data, 60 Hz Ð SI

Page 31

Table 9G Ð Standard Drive Data, 60 Hz Ð SI

 

 

40RM

 

40RM

 

40RM

 

 

40RM

 

40RM

 

40RM

40RM

 

40RM

40RMQ

40RMS

40RMQ

 

 

40RMQ

 

 

UNIT

 

40RMS

 

 

40RMS

 

40RMS

40RMS

007

40RMS

010

40RMS

 

 

40RMS

 

 

 

 

014

 

 

024

 

028

034

 

 

008

 

012

 

 

 

016

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MOTOR DRIVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor Pulley Pitch Diameter

61.0-

71.1-

71.1-

86.4-

 

71.1-

 

 

71.1-

 

94.0-

 

109.2-

109.2-

(mm)

86.4

96.5

96.5

111.8

 

96.5

 

 

96.5

 

119.4

 

134.6

134.6

Pulley Factory Setting

2.5

2.5

2.5

2.5

 

2.5

 

 

2.5

 

3.0

 

3.0

3.0

Full Turns Open

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN DRIVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pulley Pitch Dia (mm)

224

224

224

224

 

229

 

 

229

 

239

 

279

279

Pulley Bore (mm)

25.4

25.4

25.4

25.4

 

36.5

 

 

36.5

 

36.5

 

49.2

49.2

Belt No. Ð Section

1ÐA

1ÐA

1ÐA

1ÐA

 

1ÐA

1ÐA

2ÐB

2ÐB*

 

2ÐB*

 

Belt Pitch (mm)

1024

1049

1049

1074

 

1074

 

 

1074

 

1062

 

(2) 1087

(2) 1087

 

 

 

 

 

(2) 1113

(2) 1113

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN SPEEDS (r/s)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Setting

9.5

10.8

10.8

12.7

 

10.5

 

 

10.5

 

12.9

 

12.5

12.5

Range

7.8-11.1

9.2-12.4

9.2-12.4

11.1-14.4

9.0-12.1

 

9.0-12.1

11.3-14.4

 

11.4-14.0

11.2-13.9

Max Allowable Speed (r/s)

20.0

20.0

20.0

20.0

 

20.0

 

 

20.0

 

20.0

 

18.3

18.3

Change per 1¤2 Turn of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Moveable Motor Pulley

0.327

0.327

0.327

0.328

 

0.318

 

 

0.318

 

0.255

 

0.218

0.218

Flange

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAX FULL TURNS FROM

5

5

5

5

 

5

 

 

5

 

6

 

6

6

CLOSED POSITION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHAFTS CENTER DISTANCE

265-313

265-313

265-313

265-313

 

265-313

 

265-313

 

232-279

 

169-240

169-240

(mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.

Table 9H Ð Medium-Static Drive Data, 60 Hz Ð SI

 

 

40RM

 

40RM

 

40RM

 

 

40RM

 

40RM

 

40RM

40RM

 

40RM

40RMQ

40RMS

40RMQ

 

 

40RMQ

 

 

UNIT

 

40RMS

 

 

40RMS

 

40RMS

40RMS

007

40RMS

010

40RMS

 

 

40RMS

 

 

 

 

014

 

 

024

 

028

034

 

 

008

 

012

 

 

 

016

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MOTOR DRIVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor Pulley Pitch Diameter

86.4-

86.4-

86.4-

86.4-

 

86.4-

 

 

94.0-

 

109.2-

 

109.2-

109.2-

(mm)

111.8

111.8

111.8

111.8

 

111.8

 

 

119.4

 

134.6

 

134.6

134.6

Pulley Factory Setting

2.5

2.5

2.5

2.5

 

2.5

 

 

3.0

 

3.0

 

3.0

3.0

Full Turns Open

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN DRIVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pulley Pitch Dia (mm)

224

203

203

203

 

208

 

 

218

 

239

 

239

239

Pulley Bore (mm)

25.4

25.4

25.4

25.4

 

36.5

 

 

36.5

 

36.5

 

49.2

49.2

Belt No. Ð Section

1ÐA

1ÐA

1ÐA

1ÐA

 

1ÐA

1ÐB

2ÐB

2ÐB*

 

 

2ÐB*

 

 

Belt Pitch (mm)

1074

1024

1024

1024

 

1049

 

 

1062

 

1062

 

(2)

986

(2)

986

 

 

 

 

 

(2) 1011

(2) 1011

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN SPEEDS (r/s)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Setting

12.7

14.0

14.0

14.0

 

13.7

 

 

14.0

 

14.7

 

14.7

14.7

Range

11.1-

12.2-

12.2-

12.2-

 

11.9-

 

 

12.4-

 

13.3-

 

13.3-

13.3-

14.4

15.8

15.8

15.8

 

15.4

 

 

15.7

 

16.4

 

16.4

16.4

 

 

 

 

 

 

Max Allowable Speed (r/s)

20.0

20.0

20.0

20.0

 

20.0

 

 

20.0

 

20.0

 

18.3

18.3

Change per 1¤2 Turn of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Moveable Motor Pulley

0.328

0.360

0.360

0.360

 

0.352

 

 

0.278

 

0.255

 

0.255

0.255

Flange

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAX FULL TURNS FROM

5

5

5

5

 

5

 

 

6

 

6

 

 

6

 

6

CLOSED POSITION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHAFTS CENTER DISTANCE

265-313

265-313

265-313

265-313

 

265-313

 

265-313

 

232-279

 

169-240

169-240

(mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.

31

Image 31
Contents Installation, Start-Up Service Instructions Ð 40RM Physical Data, English Unit 40RMQ Ð 40RMQ Physical Data, EnglishUnit 40RMS Ð 40RMS Physical Data, EnglishChilled Water Coil Ð 40RM Physical Data, SI Ð 40RMQ Physical Data, SI Ð 40RMS Physical Data, SI Unit Unit Weight Ð Dimensions Ð Sizes40RM014 Ð Dimensions Ð Sizes 028,034 40RMQ 40RMS UnitNumbers Refrigerant and Chilled Water Piping Access HolesFace-Split Coil Suction Liquid Line Piping Typical TXV Distributor Feeder Tubes Nozzle Unit PER Distributor Factory-Installed Nozzle and Distributor DataLiquid Unit Line Quantity 38AQS Size Required Reference 40RMQ Fitting Requirements11¤8 Street Elbow Nipple, 23¤4 L Long Radius Elbow Liquid Typical 40RMS Chilled Water Piping Condensate Drains Wiring and Service Access Side Panel Removed Mocp Voltage FAN Motor Power Supply Unit PH-HZElectrical Data, Standard Motors FLAFLA Ð Electrical Data, Alternate MotorsMocp Ð Fan Contactor Coil Data Manufacturer Lubricant Lubricant DataFan Shaft Bearing Fan Pulley Alignment Ð Align as follows 40RMS 40RMQ Unit Ð Fan Motor Data, Standard Motor Ð EnglishÐ Fan Motor Data, Alternate Motor Ð English 40RMQ 40RMS UnitÐ Fan Motor Data, Alternate Motor Ð SI Ð Fan Motor Data, Standard Motor Ð SIFAN Drive Ð Standard Drive Data, 60 Hz Ð EnglishÐ Medium-Static Drive Data, 60 Hz Ð English Motor DriveÐ Standard Drive Data, 50 Hz Ð English Ð High-Static Drive Data, 60 Hz Ð EnglishÐ High-Static Drive Data, 50 Hz Ð English Ð Medium-Static Drive Data, 50 Hz Ð EnglishÐ Medium-Static Drive Data, 60 Hz Ð SI Ð Standard Drive Data, 60 Hz Ð SI40RMQ Unit Ð Standard Drive Data, 50 Hz Ð SI Ð High-Static Drive Data, 60 Hz Ð SIÐ High-Static Drive Data, 50 Hz Ð SI Ð Medium-Static Drive Data, 50 Hz Ð SIAirflow Ð Fan Performance Data Ð 0.0-1.2 in. wg ESP Ð EnglishÐ Fan Performance Data Ð 1.4-2.4 in. wg ESP Ð English Unit Airflow Pressure Drop Ð Fan Performance Data Ð 0-300 Pa ESP Ð SI Ð Fan Performance Data Ð 350-600 Pa ESP Ð SI Filter Removal/Replacement Page Page Copyright 1995 Carrier Corporation START-UP Checklist Comp A1 Comp B1 Check Voltage Imbalance