Carrier 40RMQ, 40RMS installation instructions Fan Shaft Bearing

Page 24

Centering Fan Wheel Ð If fan and fan shaft assem- bly are not properly centered, blades may scrape against scroll or may create an objectionable whistling noise. It may be necessary to adjust individual fan wheels or move entire fan shaft. See the following two sections.

Fan Shaft Position Adjustment Ð Loosen set- screw or locking collar of each fan shaft bearing. Slide shaft into correct position and replace locking collar (Fig. 18). To replace locking collar, push collar up against inner face of bearing. Turn collar in direction of fan rotation until tight, and tighten setscrew. Tightening locking collar in direction of fan rotation results in further tightening of collar should setscrew work itself loose.

Fig. 18 Ð Fan Shaft Bearing

Individual Fan Wheel Adjustment Ð Loosen the 2 locking bolts holding fan wheel hub to shaft. See Fig. 17. Position fan wheel in center of the fan housing and tighten locking bolts. Clearance between wheel and housing should be the same on both sides.

Fan Belts Ð Motor mounting plate and motor support angles are slotted to permit both vertical and horizontal adjustment. Adjust belt(s) for correct de¯ection by loosen- ing motor plate mounting bolts, moving motor/plate assem- bly forward or back, and retightening bolts. Press down on belt with one ®nger midway between fan and motor pulleys to check de¯ection. For units with motor sizes up to and including 3.7 Hp (2.76 kW), correct de¯ection is 3¤16-in. (4.8 mm) For larger motor sizes, correct de¯ection is 1¤8-in. (3.2 mm). See Fig. 19.

NOTE: The 028 and 034 size units with 60 Hz motors are shipped with an extra set of matching belts. Use the pre- installed belts or extra belts depending on the adjustable pulley setting.

If complete belt replacement is required during serv- icing, loosen the motor plate mounting bolts (Fig. 19), move motor/plate assembly towards fan pulley, and pull belt(s) off pulleys. Reverse the procedure with new bolts and readjust de¯ection.

Fan Rotation Ð Correct fan rotation with respect to fan outlet is shown in Fig. 20.

To reverse the direction of rotation of a 3-phase fan mo- tor, reverse any 2 of the power leads. Refer to the connection diagram on the inside of motor terminal box cover for proper reversing procedure of single-phase motor.

Fig. 19 Ð Fan Motor Mounting

24

Image 24
Contents Installation, Start-Up Service Instructions Ð 40RM Physical Data, English Ð 40RMQ Physical Data, English Unit 40RMQÐ 40RMS Physical Data, English Unit 40RMSChilled Water Coil Ð 40RM Physical Data, SI Ð 40RMQ Physical Data, SI Ð 40RMS Physical Data, SI Ð Dimensions Ð Sizes Unit Unit Weight40RM014 Ð Dimensions Ð Sizes 028,034 Unit 40RMQ 40RMSRefrigerant and Chilled Water Piping Access Holes NumbersFace-Split Coil Suction Liquid Line Piping Typical Factory-Installed Nozzle and Distributor Data TXV Distributor Feeder Tubes Nozzle Unit PER DistributorLiquid Unit Line Quantity 38AQS Size Required Reference Fitting Requirements 40RMQ11¤8 Street Elbow Nipple, 23¤4 L Long Radius Elbow Liquid Typical 40RMS Chilled Water Piping Condensate Drains Wiring and Service Access Side Panel Removed Voltage FAN Motor Power Supply Unit PH-HZ Electrical Data, Standard MotorsFLA MocpElectrical Data, Alternate Motors FLA ÐMocp Ð Fan Contactor Coil Data Lubricant Data Manufacturer LubricantFan Shaft Bearing Fan Pulley Alignment Ð Align as follows Ð Fan Motor Data, Standard Motor Ð English Ð Fan Motor Data, Alternate Motor Ð English40RMQ 40RMS Unit 40RMS 40RMQ UnitÐ Fan Motor Data, Standard Motor Ð SI Ð Fan Motor Data, Alternate Motor Ð SIÐ Standard Drive Data, 60 Hz Ð English Ð Medium-Static Drive Data, 60 Hz Ð EnglishMotor Drive FAN DriveÐ High-Static Drive Data, 60 Hz Ð English Ð Standard Drive Data, 50 Hz Ð EnglishÐ Medium-Static Drive Data, 50 Hz Ð English Ð High-Static Drive Data, 50 Hz Ð EnglishÐ Standard Drive Data, 60 Hz Ð SI Ð Medium-Static Drive Data, 60 Hz Ð SI40RMQ Unit Ð High-Static Drive Data, 60 Hz Ð SI Ð Standard Drive Data, 50 Hz Ð SIÐ Medium-Static Drive Data, 50 Hz Ð SI Ð High-Static Drive Data, 50 Hz Ð SIÐ Fan Performance Data Ð 0.0-1.2 in. wg ESP Ð English AirflowÐ Fan Performance Data Ð 1.4-2.4 in. wg ESP Ð English Unit Airflow Pressure Drop Ð Fan Performance Data Ð 0-300 Pa ESP Ð SI Ð Fan Performance Data Ð 350-600 Pa ESP Ð SI Filter Removal/Replacement Page Page Copyright 1995 Carrier Corporation START-UP Checklist Check Voltage Imbalance Comp A1 Comp B1