Carrier 40RMS, 40RMQ installation instructions Face-Split Coil Suction Liquid Line Piping Typical

Page 13

IMPORTANT: Never attach the sensor to the suction manifold. Do NOT mount the sensor on a trapped por- tion of the suction line.

40RM Series evaporator coils have a face-split design. En- sure that lower circuit of coil is ®rst on/last off when con- nected to the condensing unit and/or system controls. See Fig. 6.

External TXV equalizer connections are provided and factory- brazed into the coil suction manifolds.

If suction line must be horizontal, clamp bulb to suction line at least 45 degrees above bottom, at approximately the 4 o'clock or 8 o'clock position. See Fig. 7.

NOTE: The 40RMQ units are supplied with factory-installed thermostatic expansion valves and check valve bypasses. No extra piping connections or kits are required to install the 40RMQ with a 38AQS condensing unit in a heat pump system, however, some ®eld supplied components may be required. See the following two sections.

LEGEND

TXV Ð Thermostatic Expansion Valve

NOTE: Component location arrangement shown for ®eld installation of sight glasses, solenoid valves, ®lter driers, and TXV sensing bulbs. The TXVs and equalizer lines are factory installed.

Fig. 5 Ð Face-Split Coil Suction and

Liquid Line Piping (Typical)

FIRST ON/LAST OFF=B

VERTICAL INSTALLATION

FIRST ON/LAST OFF=A

HORIZONTAL INSTALLATION

Fig. 6 Ð Typical Evaporator Coil Connections

(40RM, 40RMQ)

LEGEND

TXV Ð Thermostatic Expansion Valve

NOTE: The 8 o'clock position is shown above.

Fig. 7 Ð TXV Sensing Bulb Location

13

Image 13
Contents Installation, Start-Up Service Instructions Ð 40RM Physical Data, English Unit 40RMQ Ð 40RMQ Physical Data, EnglishUnit 40RMS Ð 40RMS Physical Data, EnglishChilled Water Coil Ð 40RM Physical Data, SI Ð 40RMQ Physical Data, SI Ð 40RMS Physical Data, SI Unit Unit Weight Ð Dimensions Ð Sizes40RM014 Ð Dimensions Ð Sizes 028,034 40RMQ 40RMS UnitNumbers Refrigerant and Chilled Water Piping Access HolesFace-Split Coil Suction Liquid Line Piping Typical TXV Distributor Feeder Tubes Nozzle Unit PER Distributor Factory-Installed Nozzle and Distributor DataLiquid Unit Line Quantity 38AQS Size Required Reference 40RMQ Fitting Requirements11¤8 Street Elbow Nipple, 23¤4 L Long Radius Elbow Liquid Typical 40RMS Chilled Water Piping Condensate Drains Wiring and Service Access Side Panel Removed Electrical Data, Standard Motors Voltage FAN Motor Power Supply Unit PH-HZFLA MocpFLA Ð Electrical Data, Alternate MotorsMocp Ð Fan Contactor Coil Data Manufacturer Lubricant Lubricant DataFan Shaft Bearing Fan Pulley Alignment Ð Align as follows Ð Fan Motor Data, Alternate Motor Ð English Ð Fan Motor Data, Standard Motor Ð English40RMQ 40RMS Unit 40RMS 40RMQ UnitÐ Fan Motor Data, Alternate Motor Ð SI Ð Fan Motor Data, Standard Motor Ð SIÐ Medium-Static Drive Data, 60 Hz Ð English Ð Standard Drive Data, 60 Hz Ð EnglishMotor Drive FAN DriveÐ Standard Drive Data, 50 Hz Ð English Ð High-Static Drive Data, 60 Hz Ð EnglishÐ High-Static Drive Data, 50 Hz Ð English Ð Medium-Static Drive Data, 50 Hz Ð EnglishÐ Medium-Static Drive Data, 60 Hz Ð SI Ð Standard Drive Data, 60 Hz Ð SI40RMQ Unit Ð Standard Drive Data, 50 Hz Ð SI Ð High-Static Drive Data, 60 Hz Ð SIÐ High-Static Drive Data, 50 Hz Ð SI Ð Medium-Static Drive Data, 50 Hz Ð SIAirflow Ð Fan Performance Data Ð 0.0-1.2 in. wg ESP Ð EnglishÐ Fan Performance Data Ð 1.4-2.4 in. wg ESP Ð English Unit Airflow Pressure Drop Ð Fan Performance Data Ð 0-300 Pa ESP Ð SI Ð Fan Performance Data Ð 350-600 Pa ESP Ð SI Filter Removal/Replacement Page Page Copyright 1995 Carrier Corporation START-UP Checklist Comp A1 Comp B1 Check Voltage Imbalance