Carrier 40RMQ, 40RMS installation instructions Factory-Installed Nozzle and Distributor Data

Page 14

Table 2 Ð Factory-Installed Nozzle and Distributor Data

 

 

TXV

DISTRIBUTOR

FEEDER TUBES

NOZZLE

UNIT

 

PER DISTRIBUTOR*

Qty Part No.

Qty...

Part No.

Qty...

Part No.

 

Qty...Size (in.)

 

 

 

 

 

 

 

40RM007

1...

XVE-5

1...

1116

12

1...

E5

40RM008

1...

SVE-8

1...

1126

15

1...

C6

40RMQ008

1...

SVE-8

1...

1657

15

1...

C6

40RM012

2...

XVE-4

2...

1115

9

2...

E4

40RMQ012

2...

XVE-4

2...

1655

9

2...

E4

40RM014

2...

XVE-5

2...

1115

9

2...

E5

40RM016

2...

XVE-8

2...

1116

12

2...

E6

40RMQ016

2...

SVE-8

2...

1126

16

2...

C6

40RM024

2...

XVE-10

2...

1116

13

2...

E8

40RM028

2...

EBSVE-11

2...

1126

15

2...

C10

40RM034

2...

SVE-15

2...

1126

18

2...

C12

 

 

 

 

 

 

 

 

* Feeder tube size is 1¤4 in. (6.35 mm).

NOTE: Hot gas bypass applications require ®eld-supplied auxiliary side connector.

38AQS008/40RMQ008 HEAT PUMP SYSTEM PIPING Ð Addition of a liquid solenoid valve (LLSV) is recommended when the piping system length exceeds 75 feet. The LLSV must be a bi-¯ow type suited for use in heat pump systems. The recommended valve is Sporlan model CB14S2 (5/8-in. ODF, 7/8-in. ODM) available from the Replacement Com- ponents Division as part number EF23JS-214. This solenoid valve requires Sporlan part no. MKC-2 coils that must be purchased locally. Wire the solenoid valve in parallel with the compressor contactor coil.

The LLSV must be installed at the outdoor unit with the ¯ow arrow pointed toward the outdoor unit (in-¯ow direction for the heating mode.)

FILTER DRIER REQUIREMENTS FOR 38AQS012/ 40RMQ012 AND 38AQS016/40RMQ016 HEAT PUMP SYSTEMS Ð The 38AQS012 and 016 units do not in- clude ®lter driers. Filter driers must be ®eld-supplied and installed in 38AQS012/40RMQ012 and 38AQS016/ 40RMQ016 systems. The ®lter driers used with these sys- tems must be bi-¯ow types suited for use in heat pump applications. The Replacement Component Division part num- bers listed in Fig. 8 are recommended and available for ®eld installation.

LEGEND

TXV Ð Thermostatic Expansion Valve

RECOMMENDED FILTER DRIERS* (38AQS012,016/40RMQ SYSTEMS)

 

LIQUID

 

 

 

UNIT

LINE

PART NO.

QUANTITY

FIGURE

38AQS

SIZE

REQUIRED

REFERENCE

 

 

(in.)

 

 

 

012

1¤2

P504-8084S

2

A

5¤8

P504-8165S

1

B

 

016

1¤2

P504-8084S

2

A

5¤8

P504-8085S

2

A

 

*Available from Carrier Replacement Components Division.

Fig. 8 Ð Filter Drier Requirements Ð

38AQS012/40RMQ012 and 38AQS016/40RMQ016

Heat Pump Systems

14

Image 14
Contents Installation, Start-Up Service Instructions Ð 40RM Physical Data, English Ð 40RMQ Physical Data, English Unit 40RMQChilled Water Coil Ð 40RMS Physical Data, EnglishUnit 40RMS Ð 40RM Physical Data, SI Ð 40RMQ Physical Data, SI Ð 40RMS Physical Data, SI Ð Dimensions Ð Sizes Unit Unit Weight40RM014 Ð Dimensions Ð Sizes 028,034 Unit 40RMQ 40RMSRefrigerant and Chilled Water Piping Access Holes NumbersFace-Split Coil Suction Liquid Line Piping Typical Liquid Unit Line Quantity 38AQS Size Required Reference Factory-Installed Nozzle and Distributor DataTXV Distributor Feeder Tubes Nozzle Unit PER Distributor Fitting Requirements 40RMQ11¤8 Street Elbow Nipple, 23¤4 L Long Radius Elbow Liquid Typical 40RMS Chilled Water Piping Condensate Drains Wiring and Service Access Side Panel Removed FLA Voltage FAN Motor Power Supply Unit PH-HZElectrical Data, Standard Motors MocpMocp Ð Electrical Data, Alternate MotorsFLA Ð Fan Contactor Coil Data Lubricant Data Manufacturer LubricantFan Shaft Bearing Fan Pulley Alignment Ð Align as follows 40RMQ 40RMS Unit Ð Fan Motor Data, Standard Motor Ð EnglishÐ Fan Motor Data, Alternate Motor Ð English 40RMS 40RMQ UnitÐ Fan Motor Data, Standard Motor Ð SI Ð Fan Motor Data, Alternate Motor Ð SIMotor Drive Ð Standard Drive Data, 60 Hz Ð EnglishÐ Medium-Static Drive Data, 60 Hz Ð English FAN DriveÐ High-Static Drive Data, 60 Hz Ð English Ð Standard Drive Data, 50 Hz Ð EnglishÐ Medium-Static Drive Data, 50 Hz Ð English Ð High-Static Drive Data, 50 Hz Ð English40RMQ Unit Ð Standard Drive Data, 60 Hz Ð SIÐ Medium-Static Drive Data, 60 Hz Ð SI Ð High-Static Drive Data, 60 Hz Ð SI Ð Standard Drive Data, 50 Hz Ð SIÐ Medium-Static Drive Data, 50 Hz Ð SI Ð High-Static Drive Data, 50 Hz Ð SIÐ Fan Performance Data Ð 0.0-1.2 in. wg ESP Ð English AirflowÐ Fan Performance Data Ð 1.4-2.4 in. wg ESP Ð English Unit Airflow Pressure Drop Ð Fan Performance Data Ð 0-300 Pa ESP Ð SI Ð Fan Performance Data Ð 350-600 Pa ESP Ð SI Filter Removal/Replacement Page Page Copyright 1995 Carrier Corporation START-UP Checklist Check Voltage Imbalance Comp A1 Comp B1