Legend and Notes for Tables 10C and 10D
LEGEND
ESP Ð External Static Pressure
NOTES:
1.Maximum allowable fan speed is 18.3 r/s for unit sizes 028 and 034; 20 r/s for all other sizes.
2.Fan performance is based on deductions for wet coil, clean
3.Refer to fan motor and drive tables for additional data.
UNIT | AIRFLOW | PRESSURE DROP | |
(L/s) | (Pa) | ||
| |||
40RM | 850 | 13 | |
1150 | 20 | ||
007 | |||
1450 | 28 | ||
| |||
40RM | 1000 | 17 | |
40RMQ | |||
1400 | 27 | ||
40RMS | |||
1800 | 38 | ||
008 | |||
|
| ||
40RMS | 1200 | 21 | |
1600 | 32 | ||
010 | |||
2000 | 45 | ||
| |||
40RM | 1450 | 28 | |
40RMQ | |||
1900 | 42 | ||
40RMS | |||
2350 | 56 | ||
012 | |||
|
| ||
40RM | 1750 | 15 | |
40RMS | 2350 | 24 | |
014 | 2950 | 33 | |
40RM | 2100 | 20 | |
40RMQ | |||
2800 | 30 | ||
40RMS | |||
3500 | 42 | ||
016 | |||
|
| ||
40RM | 2900 | 32 | |
40RMS | 3800 | 47 | |
024 | 4700 | 64 | |
40RM | 3500 | 36 | |
40RMS | 4700 | 55 | |
028 | 5900 | 76 | |
40RM | 4250 | 47 | |
40RMS | 5650 | 71 | |
034 | 7050 | 98 |
Replacing Filters Ð Filters can be removed and in- stalled from either side of the unit. Install new ®lters in units that have one fan as follows:
1.Remove the side access panel (retain screws).
2.Remove the ®lter retainer clip.
3.Remove old ®lters by tilting them and lifting them out of the ®lter track. See Fig. 12 and 22.
4.Reverse the procedure to install new ®lters.
To install new ®lters in larger units that have 2 fans, fol- low the preceding steps, but use the
Do not operate unit without air ®lters.
Fig. 22 Ð Filter Removal/Replacement