Carrier 40RM Electrical Data, Standard Motors, Voltage FAN Motor Power Supply Unit PH-HZ, Fla

Page 20

Table 4 Ð Electrical Data, Standard Motors

 

 

VOLTAGE

 

FAN MOTOR

POWER SUPPLY

 

UNIT

V*-PH-HZ

LIMITS

Hp

 

FLA

Minimum

 

MOCP

 

 

 

Circuit Amps

 

 

 

 

 

 

 

 

 

 

208/230-1-60

187-253

1.3

 

7.6

9.5

 

15

 

208/230-3-60

187-253

2.4

 

5.8

7.3

 

15

40RM

460-3-60

414-528

2.4

 

2.6

3.3

 

15

007

575-3-60

518-632

1.0

 

1.35

1.7

 

15

 

230-3-50

207-253

2.4

 

5.8

7.3

 

15

 

400-3-50

360-440

2.4

 

2.6

3.3

 

15

 

208/230-1-60

187-253

2.4

 

11.0

13.8

 

20

40RM

208/230-3-60

187-253

2.4

 

5.8

7.3

 

15

460-3-60

414-528

2.4

 

2.6

3.3

 

15

40RMQ

 

 

40RMS

575-3-60

518-632

2.0

 

2.4

3.0

 

15

008

 

 

 

 

 

 

 

 

230-3-50

207-253

2.4

 

5.8

7.3

 

15

 

 

 

 

400-3-50

360-440

2.4

 

2.6

3.3

 

15

 

208/230-1-60

187-253

2.4

 

11.0

13.8

 

20

 

208/230-3-60

187-253

2.4

 

5.8

7.3

 

15

40RMS

460-3-60

414-528

2.4

 

2.6

3.3

 

15

010

575-3-60

518-632

2.0

 

2.4

3.0

 

15

 

230-3-50

207-253

2.4

 

5.8

7.3

 

15

 

400-3-50

360-440

2.4

 

2.6

3.3

 

15

 

208/230-3-60

187-253

2.4

 

5.8

7.3

 

15

40RM

460-3-60

414-528

2.4

 

2.6

3.3

 

15

40RMQ

 

 

 

 

 

 

 

 

575-3-60

518-632

2.0

 

2.4

3.0

 

15

40RMS

 

 

012

230-3-50

207-253

2.9

 

7.5

9.4

 

15

 

400-3-50

360-440

2.9

 

3.4

4.3

 

15

 

208/230-3-60

187-253

2.9

 

7.5

9.4

 

15

40RM

460-3-60

414-528

2.9

 

3.4

4.3

 

15

40RMS

575-3-60

518-632

3.0

 

3.8

4.8

 

15

014

 

 

 

 

 

 

 

 

230-3-50

207-253

2.9

 

7.5

9.4

 

15

 

 

 

 

400-3-50

360-440

2.9

 

3.4

4.3

 

15

 

208/230-3-60

187-253

3.7

 

10.6

13.3

 

20

40RM

460-3-60

414-528

3.7

 

4.8

6.0

 

15

40RMQ

 

 

 

 

 

 

 

 

575-3-60

518-632

3.0

 

3.8

4.8

 

15

40RMS

 

 

230-3-50

207-253

2.9

 

7.5

9.4

 

15

016

 

 

 

400-3-50

360-440

2.9

 

3.4

4.3

 

15

 

208/230-3-60

187-253

5.0

 

15.2/14.4

19.0/18.0

 

30/30

40RM

460-3-60

414-528

5.0

 

7.2

9.0

 

15

40RMS

575-3-60

518-632

5.0

 

5.6

7.0

 

15

024

 

 

 

 

 

 

 

 

230-3-50

207-253

5.0

 

14.4

18.0

 

30

 

 

 

 

400-3-50

360-440

5.0

 

7.2

9.0

 

15

 

208/230-3-60

187-253

7.5

 

22.0/21.0

27.5/26.3

 

45/45

40RM

460-3-60

414-528

7.5

 

10.5

13.1

 

20

40RMS

575-3-60

518-632

7.5

 

7.6

9.5

 

15

028

 

 

 

 

 

 

 

 

230-3-50

207-253

7.5

 

21.0

26.3

 

45

 

 

 

 

400-3-50

360-440

7.5

 

10.5

13.1

 

20

 

208/230-3-60

187-253

10.0

 

26.4/25.0

33.0/31.3

 

55/55

40RM

460-3-60

414-528

10.0

 

12.5

15.6

 

25

40RMS

575-3-60

518-632

10.0

 

9.6

12.0

 

20

034

 

 

 

 

 

 

 

 

230-3-50

207-253

10.0

 

25.0

31.3

 

55

 

 

 

 

440-3-50

360-440

10.0

 

12.5

15.6

 

25

 

 

 

 

 

 

 

 

 

See Legend and Notes on page 21.

20

Image 20
Contents Installation, Start-Up Service Instructions Ð 40RM Physical Data, English Ð 40RMQ Physical Data, English Unit 40RMQChilled Water Coil Ð 40RMS Physical Data, EnglishUnit 40RMS Ð 40RM Physical Data, SI Ð 40RMQ Physical Data, SI Ð 40RMS Physical Data, SI Ð Dimensions Ð Sizes Unit Unit Weight40RM014 Ð Dimensions Ð Sizes 028,034 Unit 40RMQ 40RMSRefrigerant and Chilled Water Piping Access Holes NumbersFace-Split Coil Suction Liquid Line Piping Typical Liquid Unit Line Quantity 38AQS Size Required Reference Factory-Installed Nozzle and Distributor DataTXV Distributor Feeder Tubes Nozzle Unit PER Distributor Fitting Requirements 40RMQ11¤8 Street Elbow Nipple, 23¤4 L Long Radius Elbow Liquid Typical 40RMS Chilled Water Piping Condensate Drains Wiring and Service Access Side Panel Removed Voltage FAN Motor Power Supply Unit PH-HZ Electrical Data, Standard MotorsFLA MocpMocp Ð Electrical Data, Alternate MotorsFLA Ð Fan Contactor Coil Data Lubricant Data Manufacturer LubricantFan Shaft Bearing Fan Pulley Alignment Ð Align as follows Ð Fan Motor Data, Standard Motor Ð English Ð Fan Motor Data, Alternate Motor Ð English40RMQ 40RMS Unit 40RMS 40RMQ UnitÐ Fan Motor Data, Standard Motor Ð SI Ð Fan Motor Data, Alternate Motor Ð SIÐ Standard Drive Data, 60 Hz Ð English Ð Medium-Static Drive Data, 60 Hz Ð EnglishMotor Drive FAN DriveÐ High-Static Drive Data, 60 Hz Ð English Ð Standard Drive Data, 50 Hz Ð EnglishÐ Medium-Static Drive Data, 50 Hz Ð English Ð High-Static Drive Data, 50 Hz Ð English40RMQ Unit Ð Standard Drive Data, 60 Hz Ð SIÐ Medium-Static Drive Data, 60 Hz Ð SI Ð High-Static Drive Data, 60 Hz Ð SI Ð Standard Drive Data, 50 Hz Ð SIÐ Medium-Static Drive Data, 50 Hz Ð SI Ð High-Static Drive Data, 50 Hz Ð SIÐ Fan Performance Data Ð 0.0-1.2 in. wg ESP Ð English AirflowÐ Fan Performance Data Ð 1.4-2.4 in. wg ESP Ð English Unit Airflow Pressure Drop Ð Fan Performance Data Ð 0-300 Pa ESP Ð SI Ð Fan Performance Data Ð 350-600 Pa ESP Ð SI Filter Removal/Replacement Page Page Copyright 1995 Carrier Corporation START-UP Checklist Check Voltage Imbalance Comp A1 Comp B1