CHECK VOLTAGE IMBALANCE

 

 

 

 

 

 

 

 

 

 

 

 

LINE-TO-LINE VOLTS:

AB

 

V

AC

 

 

 

V

BC

 

 

V

(AB + AC + BC)/3 = AVERAGE VOLTAGE =

 

 

 

V

V

 

 

MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =

 

 

 

 

%

VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) =

 

 

IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!

CALL LOCAL POWER COMPANY FOR ASSISTANCE.

C. Start-Up

CHECK EVAPORATOR FAN SPEED AND RECORD.

AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:

COMP A1

COMP B1

OIL PRESSURE

SUCTION PRESSURE

SUCTION LINE TEMP

DISCHARGE PRESSURE

DISCHARGE LINE TEMP

ENTERING OUTDOOR UNIT AIR TEMP

LEAVING OUTDOOR UNIT AIR TEMP

INDOOR UNIT ENTERING AIR DB TEMP

INDOOR UNIT ENTERING AIR WB TEMP

INDOOR UNIT LEAVING AIR DB TEMP

INDOOR UNIT LEAVING AIR WB TEMP

OUTDOOR UNIT ENTERING WATER TEMP (40RMS ONLY)

OUTDOOR UNIT LEAVING WATER TEMP (40RMS ONLY)

INDOOR UNIT ENTERING WATER TEMP (40RMS ONLY)

INDOOR UNIT LEAVING WATER TEMP (40RMS ONLY)

COMPRESSOR AMPS (L1/L2/L3)

 

 

 

 

/

 

/

 

 

 

/

 

/

 

 

 

 

 

CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES; ARE THE SIGHT GLASSES SHOWING

 

 

OIL LEVEL AT 1¤8 TO 1¤3 FULL?

(Y/N)

 

 

 

 

 

 

 

 

 

 

NOTES:

Copyright 1995 Carrier Corporation

Manufacturer reserves the right to discontinue, or change at any time, speci®cations or designs without notice and without incurring obligations.

Book

1

4

 

PC 111

Catalog No. 534-053

Printed in U.S.A.

Form 40RM-9SI

CL-2

596

11-95

Replaces: 40RM-1SI

Tab

3c

2e

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Image 44
Contents Installation, Start-Up Service Instructions Ð 40RM Physical Data, English Ð 40RMQ Physical Data, English Unit 40RMQChilled Water Coil Ð 40RMS Physical Data, EnglishUnit 40RMS Ð 40RM Physical Data, SI Ð 40RMQ Physical Data, SI Ð 40RMS Physical Data, SI Ð Dimensions Ð Sizes Unit Unit Weight40RM014 Ð Dimensions Ð Sizes 028,034 Unit 40RMQ 40RMSRefrigerant and Chilled Water Piping Access Holes NumbersFace-Split Coil Suction Liquid Line Piping Typical Liquid Unit Line Quantity 38AQS Size Required Reference Factory-Installed Nozzle and Distributor DataTXV Distributor Feeder Tubes Nozzle Unit PER Distributor Fitting Requirements 40RMQ11¤8 Street Elbow Nipple, 23¤4 L Long Radius Elbow Liquid Typical 40RMS Chilled Water Piping Condensate Drains Wiring and Service Access Side Panel Removed Voltage FAN Motor Power Supply Unit PH-HZ Electrical Data, Standard MotorsFLA MocpMocp Ð Electrical Data, Alternate MotorsFLA Ð Fan Contactor Coil Data Lubricant Data Manufacturer LubricantFan Shaft Bearing Fan Pulley Alignment Ð Align as follows Ð Fan Motor Data, Standard Motor Ð English Ð Fan Motor Data, Alternate Motor Ð English40RMQ 40RMS Unit 40RMS 40RMQ UnitÐ Fan Motor Data, Standard Motor Ð SI Ð Fan Motor Data, Alternate Motor Ð SIÐ Standard Drive Data, 60 Hz Ð English Ð Medium-Static Drive Data, 60 Hz Ð EnglishMotor Drive FAN DriveÐ High-Static Drive Data, 60 Hz Ð English Ð Standard Drive Data, 50 Hz Ð EnglishÐ Medium-Static Drive Data, 50 Hz Ð English Ð High-Static Drive Data, 50 Hz Ð English40RMQ Unit Ð Standard Drive Data, 60 Hz Ð SIÐ Medium-Static Drive Data, 60 Hz Ð SI Ð High-Static Drive Data, 60 Hz Ð SI Ð Standard Drive Data, 50 Hz Ð SIÐ Medium-Static Drive Data, 50 Hz Ð SI Ð High-Static Drive Data, 50 Hz Ð SIÐ Fan Performance Data Ð 0.0-1.2 in. wg ESP Ð English AirflowÐ Fan Performance Data Ð 1.4-2.4 in. wg ESP Ð English Unit Airflow Pressure Drop Ð Fan Performance Data Ð 0-300 Pa ESP Ð SI Ð Fan Performance Data Ð 350-600 Pa ESP Ð SI Filter Removal/Replacement Page Page Copyright 1995 Carrier Corporation START-UP Checklist Check Voltage Imbalance Comp A1 Comp B1