Carrier 40RMS, 40RMQ installation instructions Wiring and Service Access Side Panel Removed

Page 19

Power Supply and Wiring Ð Check the unit data plate to ensure that available power supply matches electri- cal characteristics of the unit. Provide a disconnect switch of size required to provide adequate fan motor starting current. See Tables 4 - 6 for unit electrical data.

Install disconnect switch and power wiring in accordance with all applicable local codes. See Fig. 12-14 and the unit label diagram. For units with motor sizes less than 5 Hp (3.7 kW), connect power wiring to unit with no. 10 ring ter- minal. For units with motor sizes of 5 Hp (3.7 kW) or more, connect power wiring with 1¤4-in. ring terminal.

The 40RM, 40RMQ and 40RMS size 007-016 units (ex- cept 40RM016 with YC or WD option) that have motors wired for 460-v, 3-ph, 60 Hz operation can be ®eld-converted to

230-v, 3-ph, 60 Hz operation. Rewire the motor according to the diagram plate on the motor. After recon®guring the mo- tor, place the sticker specifying 230-v operation (supplied in installation packet) over the 460-v sticker on the units cor- ner post.

Fan motors are factory installed on all units. Indoor-fan contactors are located in the fan contactor box behind the side access panel (see Fig. 12 and 13). Wire the thermostat to the 24-v control circuit terminal block located in the side of the fan contactor control box, according to Fig. 14 or the unit label diagram. If the air handler is part of a split system, complete the wiring from the condensing unit to the ther- mostat shown in Fig. 14.

FAN SCROLL

FAN

CONTACTOR

 

 

BOX

MOTOR

 

AND DRIVE

WIRING

 

ACCESS

CONDENSATE

 

DRAIN

FAN DRIVE

CONNECTION

PULLEY

(HORIZONTAL)

 

 

COIL

FILTER

TXV BULB

ELEMENTS

ACCESS

 

REFRIGERANT/

 

CHILLED WATER

FILTER

PIPING ACCESS

RETAINER

 

CLIP

CONDENSATE

 

FAN CONTACTOR

24V TERMINAL BLOCK

AW RJ 600V

C ° 5 0 1

23

22

21

13

12

11

DRAIN

CONNECTION

(VERTICAL)

TXV Ð Thermostatic Expansion Valve

Fig. 12 Ð Wiring and Service Access

(Side Panel Removed)

POWER WIRING KNOCKOUT

Fig. 13 Ð Fan Contactor Box and Terminal Block

(Cover Removed) (Typical)

19

Image 19
Contents Installation, Start-Up Service Instructions Ð 40RM Physical Data, English Unit 40RMQ Ð 40RMQ Physical Data, EnglishUnit 40RMS Ð 40RMS Physical Data, EnglishChilled Water Coil Ð 40RM Physical Data, SI Ð 40RMQ Physical Data, SI Ð 40RMS Physical Data, SI Unit Unit Weight Ð Dimensions Ð Sizes40RM014 Ð Dimensions Ð Sizes 028,034 40RMQ 40RMS UnitNumbers Refrigerant and Chilled Water Piping Access HolesFace-Split Coil Suction Liquid Line Piping Typical TXV Distributor Feeder Tubes Nozzle Unit PER Distributor Factory-Installed Nozzle and Distributor DataLiquid Unit Line Quantity 38AQS Size Required Reference 40RMQ Fitting Requirements11¤8 Street Elbow Nipple, 23¤4 L Long Radius Elbow Liquid Typical 40RMS Chilled Water Piping Condensate Drains Wiring and Service Access Side Panel Removed Mocp Voltage FAN Motor Power Supply Unit PH-HZElectrical Data, Standard Motors FLAFLA Ð Electrical Data, Alternate MotorsMocp Ð Fan Contactor Coil Data Manufacturer Lubricant Lubricant DataFan Shaft Bearing Fan Pulley Alignment Ð Align as follows 40RMS 40RMQ Unit Ð Fan Motor Data, Standard Motor Ð EnglishÐ Fan Motor Data, Alternate Motor Ð English 40RMQ 40RMS UnitÐ Fan Motor Data, Alternate Motor Ð SI Ð Fan Motor Data, Standard Motor Ð SIFAN Drive Ð Standard Drive Data, 60 Hz Ð EnglishÐ Medium-Static Drive Data, 60 Hz Ð English Motor DriveÐ Standard Drive Data, 50 Hz Ð English Ð High-Static Drive Data, 60 Hz Ð EnglishÐ High-Static Drive Data, 50 Hz Ð English Ð Medium-Static Drive Data, 50 Hz Ð EnglishÐ Medium-Static Drive Data, 60 Hz Ð SI Ð Standard Drive Data, 60 Hz Ð SI40RMQ Unit Ð Standard Drive Data, 50 Hz Ð SI Ð High-Static Drive Data, 60 Hz Ð SIÐ High-Static Drive Data, 50 Hz Ð SI Ð Medium-Static Drive Data, 50 Hz Ð SIAirflow Ð Fan Performance Data Ð 0.0-1.2 in. wg ESP Ð EnglishÐ Fan Performance Data Ð 1.4-2.4 in. wg ESP Ð English Unit Airflow Pressure Drop Ð Fan Performance Data Ð 0-300 Pa ESP Ð SI Ð Fan Performance Data Ð 350-600 Pa ESP Ð SI Filter Removal/Replacement Page Page Copyright 1995 Carrier Corporation START-UP Checklist Comp A1 Comp B1 Check Voltage Imbalance