Table 1B Ð 40RMQ Physical Data, English
UNIT 40RMQ | 008 |
| 012 |
| 016 |
NOMINAL CAPACITY (Tons) | 71¤2 |
| 10 |
| 15 |
OPERATING WEIGHT (lb) |
|
|
|
|
|
Base Unit with TXV | 385 |
| 427 |
| 713 |
Plenum | 97 |
| 97 |
| 140 |
FANS |
|
|
|
|
|
Qty...Diam. (in.) | 1...15 |
| 1...15 |
| 2...15 |
Nominal Air¯ow (cfm) | 3000 |
| 4000 |
| 6000 |
Air¯ow Range (cfm) |
|
| |||
Nominal Motor Hp (Standard Motor) |
|
|
|
|
|
2.4 |
| Ð |
| Ð | |
2.4 |
| 2.4 |
| 3.7 | |
2.0 |
| 2.0 |
| 3.0 | |
2.4 |
| 2.9 |
| 2.9 | |
Motor Speed (rpm) |
|
|
|
|
|
1725 |
| Ð |
| Ð | |
1725 |
| 1725 |
| 1725 | |
1725 |
| 1725 |
| 1725 | |
1425 |
| 1425 |
| 1425 | |
REFRIGERANT |
|
|
| ||
Operating charge (lb) | 3.0 |
| 2.0/2.0 |
| 3.0/3.0 |
(approx per circuit)* |
|
| |||
|
|
|
|
| |
| Enhanced Copper Tubes, Aluminum | ||||
Max Working Pressure (psig) |
|
| 435 |
|
|
Face Area (sq ft) | 8.33 |
| 10.0 |
| 17.67 |
No. of Splits | 1 |
| 2 |
| 2 |
No. of Circuits per Split | 15 |
| 9 |
| 16 |
Split Type...Percentage | Ð |
| Face | ...50/50 | |
Rows...Fins/in. | 3...15 |
| 4...15 |
| 4...15 |
STEAM COIL |
|
|
|
|
|
Max Working Pressure (psig at 400 F) |
|
| 175 |
|
|
Total Face Area (sq ft) | 6.67 |
| 6.67 |
| 13.33 |
Rows...Fins/in. | 1...9 |
| 1...9 |
| 1...10 |
HOT WATER COIL |
|
|
|
|
|
Max Working Pressure (psig) |
|
| 150 |
|
|
Total Face Area (sq ft) | 6.67 |
| 6.67 |
| 13.33 |
Rows...Fins/in. | 2...8.5 |
| 2...8.5 |
| 2...8.5 |
Water Volume |
|
|
|
|
|
(gal) | 8.3 |
|
| 13.9 | |
(ft3) | 1.1 |
|
| 1.85 | |
PIPING CONNECTIONS, |
|
|
|
|
|
Quantity...Size (in.) |
|
|
|
|
|
DX Coil Ð Suction (ODF) | 1...11¤8 |
| 2...11¤8 |
| 2...11¤8 |
DX Coil Ð Liquid Refrigerant (ODF) | 1...5¤8 |
| 2...5¤8 |
| 2...5¤8 |
Steam Coil, In (MPT) | 1...21¤2 |
| 1 | ...21¤2 |
|
Steam Coil, Out (MPT) | 1...11¤2 |
| 1...11¤2 |
| |
Hot Water Coil, In (MPT) | 1...11¤2 |
| 1...11¤2 |
| 1...2 |
Hot Water Coil, Out (MPT) | 1...11¤2 |
| 1...11¤2 |
| 1...2 |
Condensate (PVC) |
|
| 1...11¤4 ODM/1 IDF |
|
|
FILTERS | Throwaway Ð Factory Supplied | 4...16 x 20 x 2 | |||
Quantity...Size (in.) | 4...16 x 24 x 2 |
| |||
| 4...16 x 24 x 2 | ||||
Access Location |
|
| Either Side |
| |
|
|
|
|
LEGEND