Table 3 — Heat Anticipator Settings
UNIT | UNIT | kW* | STAGE 1 | STAGE 2 | |
50TJ | VOLTAGES | ||||
|
|
| |||
|
| 26/34 | .40 | .66 | |
| 42/56 | .66 | .40 | ||
|
| 56/75 | .66 | .66 | |
| 20 | .40 | .40 | ||
| 35 | .40 | .66 | ||
| |||||
| 32 | .40 | .40 | ||
| 55 | .40 | .66 | ||
|
| ||||
| 80 | .66 | .66 | ||
| 50 | .66 | .66 | ||
|
|
*Heater kW is based on heater voltage of 208 v, 240 v, 380 v, 480 v, and 575 v.
Fig. 16 — EconoMi$er Control Module
Adjustment Potentiometers
CONTROL MODULEACTUATOR
Fig. 17 — EconoMi$er Control Module Location
Step 8 — Install
NOTE: The hood top panel, upper and lower filter retainers, hood drain pan, baffle (028), and filter support bracket are secured opposite the condenser end of the unit. The screens, hood side panels, remaining section of filter support bracket, seal strip, and all other hardware are in a package located inside the
1.Attach seal strip to upper filter retainer. See Fig. 19.
2.Assemble hood top panel and side panels, upper filter re- tainer, and hood drain pan (Fig. 20).
3.Secure lower filter retainer and long section of filter sup- port bracket to unit. See Fig. 20. Leave screws loose on 028 units.
4.Slide baffle (size 028 unit) behind lower filter retainer and tighten screws.
5.Loosen sheet metal screws for base unit top panel located above
6.Match notches in hood top panel to unit top panel screws. Insert hood flange between unit top panel flange and unit. Tighten screws.
7.Hold hood side panel flanges flat against unit, and install screws removed in Step 5.
8.Insert
9.Attach remaining short section of filter support bracket.
OUTDOOR AIR ENTHALPY SENSOR INSTALLA- TION — Perform the following procedure to install the out- door air enthalpy sensor (part no. CROUTENT001A00).
1.Remove the outdoor air temperature sensor cover. See Fig. 21. Save cover and screws.
2.Disconnect the wiring from the installed outdoor air tem- perature sensor. See Fig. 22.
3.Use a
4.Mount the outdoor air enthalpy sensor in the outdoor air temperature sensor location using the screws removed in Step 3.
5.Connect the outdoor air enthalpy sensor wiring harness to the EconoMi$er control module and sensor.
6.
RETURN AIR TEMPERATURE SENSOR OR RETURN AIR ENTHALPY SENSOR INSTALLATION — Perform the following procedure to install the return air temperature sensor (part no. CRRETTMP001A00) or return air enthalpy sensor (part no. CRRETENT001A00).
1.Attach the sensor to the mounting bracket using 2 self- tapping
2.Mount the bracket to the inside of the return air opening flange using a
NOTE: The sensor must be mounted in an upright position.
3.Feed the sensor wiring through the bushing in EconoMi$er to secure wires.
4.Route sensor wiring harness from sensor to EconoMi$er control module. Secure wiring harness to the original har- ness using tie wraps.
5.Wire the sensor to the EconoMi$er control module. See Fig. 23 and 24.
Fig. 18 — Outdoor-Air Hood Component Location
12