the inlet of the compressor. The compressor should then be run for 10 minutes, shut down, and the access valve opened until no oil flows. This should be repeated twice to make sure the proper oil level has been achieved.
FAN SHAFT BEARINGS — For size 016 units, bearings are permanently lubricated. No field lubrication is required. For size
Typical lubricants are given below:
MANUFACTURER | LUBRICANT |
Texaco | Regal |
Mobil | Mobilplex EP No. 1 |
Sunoco | Prestige 42 |
Texaco | Multifak 2 |
*Preferred lubricant because it contains rust and oxidation inhibitors.
CONDENSER AND
Evaporator Fan Performance Adjustment (Fig.
shown in Table 1.
To change fan speeds:
1.Shut off unit power supply.
2.a. Size 016 Only: Loosen belt by loosening fan motor mounting plate nuts.
b.Size
3.Loosen
4.Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed. In- creasing fan speed increases load on motor. Do not ex- ceed maximum speed specified in Table 1.
See Table 7 for air quantity limits.
5.Set movable flange at nearest keyway of pulley hub and tighten setscrew. (See Table 1 for speed change for each full turn of pulley flange.)
6.Replace and tighten belts. See Belt Tension Adjustment section on page 26.
To align fan and motor pulleys:
1.Loosen fan pulley setscrews.
2.Slide fan pulley along fan shaft.
3.Make angular alignment by loosening motor from mounting plate.
Evaporator Fan Service and Replacement
50TJ016 UNITS (See Fig. 32)
NOTE: To remove belts only, follow Steps
1.Remove filter and
2.Remove unit top panel.
3.Loosen carriage nuts A and B holding motor mount as- sembly to fan scroll side plates.
4.Loosen screw C.
5.Rotate motor mount assembly (with motor attached) as far as possible away from evaporator coil.
6.Remove belt.
7.Rotate motor mount assembly back past original position toward evaporator coil.
8.Remove motor mounting nuts D and E (both sides).
9.Lift motor up through top of unit.
10.Reverse above procedure to reinstall motor.
11.Check and adjust belt tension as necessary.
1.Remove the
2.Remove the center post (located between the evaporator fan and heating control access panels) and all screws se- curing it.
3.Loosen nuts on the two carriage bolts in the motor mount- ing base.
4.Using jacking bolt under motor base, raise motor to top of slide and remove belt. Secure motor in this position by tightening the nuts on the carriage bolts.
5.Remove the belt drive.
6.Remove jacking bolt and tapped jacking bolt plate.
7.Remove the 2 screws that secure the motor mounting plate to the motor support channel.
8.Remove the 3 screws from the end of the motor support channel that interfere with the motor slide path.
9.Slide out the motor and motor mounting plate.
10.Disconnect wiring connections and remove the 4 mount- ing bolts.
11.Remove the motor.
12.To install the new motor, reverse Steps
Fig. 31 — Evaporator-Fan Pulley Alignment
and Adjustment
25