Table 11 — Accessory/FIOP Static Pressure (in. wg) — 50TJ016
COMPONENT |
|
|
|
| CFM |
|
|
|
|
4500 |
| 5000 |
| 6000 |
| 7200 |
| 7500 | |
|
|
|
|
| |||||
EconoMi$er | 0.04 |
| 0.05 |
| 0.07 |
| 0.09 |
| 0.10 |
Glycol Coil | 0.22 |
| 0.26 |
| 0.35 |
| 0.44 |
| 0.46 |
Electric Heat (kW) |
|
|
|
|
|
|
|
|
|
20 | 0.06 |
| 0.07 |
| 0.09 |
| 0.11 |
| 0.12 |
|
|
|
| ||||||
26/34 | 0.06 |
| 0.07 |
| 0.09 |
| 0.11 |
| 0.12 |
32 | 0.06 |
| 0.07 |
| 0.09 |
| 0.11 |
| 0.12 |
35 | 0.07 |
| 0.08 |
| 0.12 |
| 0.15 |
| 0.17 |
42/56 | 0.07 |
| 0.08 |
| 0.12 |
| 0.16 |
| 0.17 |
50 | 0.09 |
| 0.10 |
| 0.15 |
| 0.20 |
| 0.21 |
55 | 0.07 |
| 0.08 |
| 0.12 |
| 0.15 |
| 0.17 |
56/75 | 0.09 |
| 0.10 |
| 0.15 |
| 0.20 |
| 0.21 |
80 | 0.09 |
| 0.10 |
| 0.15 |
| 0.20 |
| 0.21 |
LEGEND | NOTES: | |
FIOP — | 1. | The static pressure must be added to external static pressure. |
| The sum and the evaporator | |
|
| |
|
| used in conjunction with the Fan Performance tables to deter- |
|
| mine blower rpm and watts. |
| 2. | Heaters are rated at 240 v, 380 v, 480 v, and 600 v. |
Table 12 — Accessory/FIOP Static Pressure (in. wg) — 50TJ020-028
COMPONENT |
|
|
|
|
| CFM |
|
|
|
| ||
5400 |
| 6000 |
| 7200 |
|
| 9000 |
| 10,000 |
| 11,250 | |
|
|
|
|
|
|
| ||||||
EconoMi$er | 0.06 |
| 0.07 |
| 0.09 |
|
| 0.11 |
| 0.12 |
| 0.14 |
Glycol Coil | 0.30 |
| 0.35 |
| 0.44 |
|
| 0.58 |
| 0.66 |
| 0.77 |
Electric Heat (kW) |
|
|
|
|
|
|
|
|
|
|
|
|
20, 26/34 | 0.08 |
| 0.09 |
| 0.11 |
|
| 0.15 |
| 0.17 |
| 0.20 |
|
|
|
|
| ||||||||
32 | 0.08 |
| 0.09 |
| 0.11 |
|
| 0.15 |
| 0.17 |
| 0.20 |
35, 42/56 | 0.11 |
| 0.12 |
| 0.15 |
|
| 0.19 |
| 0.21 |
| 0.24 |
55 | 0.11 |
| 0.12 |
| 0.15 |
|
| 0.19 |
| 0.21 |
| 0.24 |
56/75 | 0.14 |
| 0.15 |
| 0.20 |
|
| 0.24 |
| 0.26 |
| 0.29 |
80 | 0.14 |
| 0.15 |
| 0.20 |
|
| 0.24 |
| 0.26 |
| 0.29 |
LEGEND |
|
|
|
| NOTES: |
|
|
|
|
|
|
|
FIOP — |
|
|
|
| 1. The static pressure must be added to external static pressure. | |||||||
|
|
|
|
| The sum and the evaporator | |||||||
|
|
|
|
| used in conjunction with the Fan Performance tables to deter- |
mine blower rpm and watts.
2. Heaters are rated at 240 v, 380 v, and 480 v. There are no
Table 13 — MoistureMiser Dehumidification
Package Static Pressure Drop (in. wg)
UNIT SIZE | UNIT NOMINAL | CFM PER TON | ||
50TJ | TONS | 300 | 400 | 500 |
016 | 15 | .040 | .071 | .111 |
020 | 18 | .058 | .102 | .160 |
024 | 20 | .071 | .126 | .197 |
028 | 25 | .111 | .197 | .308 |
Table 14 — Fan Rpm at Motor Pulley Settings*
UNIT |
|
|
|
|
| MOTOR PULLEY TURNS OPEN |
|
|
|
| |||
50TJ | 0 | 1/2 | 1 | 11/2 | 2 | 21/2 | 3 | 31/2 | 4 | 41/2 | 5 | 51/2 | 6 |
016 (208/230, 380, 460 v)† | †† | †† | 1179 | 1150 | 1121 | 1093 | 1064 | 1035 | 1006 | 978 | 949 | 920 | 891 |
016 (208/230, 380, 460 v)** | †† | †† | 1559 | 1522 | 1488 | 1455 | 1422 | 1389 | 1356 | 1323 | 1289 | 1256 | 1227 |
016 (575 v)† | †† | †† | 1429 | 1403 | 1376 | 1349 | 1323 | 1296 | 1269 | 1242 | 1215 | 1188 | 1159 |
020† | †† | †† | 1095 | 1077 | 1058 | 1040 | 1021 | 1002 | 984 | 965 | 947 | 928 | 910 |
020** | †† | †† | 1287 | 1265 | 1243 | 1222 | 1200 | 1178 | 1156 | 1134 | 1112 | 1091 | 1069 |
024† | †† | †† | 1225 | 1209 | 1187 | 1165 | 1143 | 1120 | 1098 | 1076 | 1053 | 1031 | 1002 |
024** | †† | †† | 1458 | 1434 | 1407 | 1381 | 1354 | 1328 | 1301 | 1275 | 1248 | 1222 | 1193 |
028† | †† | †† | 1283 | 1269 | 1247 | 1225 | 1203 | 1182 | 1160 | 1138 | 1116 | 1095 | 1066 |
028** | †† | †† | — | — | 1551 | 1524 | 1497 | 1470 | 1443 | 1415 | 1388 | 1361 | 1332 |
*Approximate fan rpm shown. |
|
|
|
|
|
|
|
|
|
|
|
|
|
†Indicates standard drive package. **Indicates alternate drive package.
††Due to belt and pulley size, pulley cannot be set to this number of turns open.