Carrier 50TJ016-028 specifications Wind Baffle Details

Page 16

Install Motormaster I Controls — Only one Motormaster I control is required per unit. The Motormaster I control must be used in conjunction with the Accessory 0° F Low Ambient Kit (purchased separately). The Motormaster I device controls out- door fan no. 1 while outdoor fans no. 2 and 3 are sequenced off by the Accessory 0° F Low Ambient Kit.

Accessory 0° F Low Ambient Kit — Install the Accessory 0° F Low Ambient Kit per instruction supplied with accessory.

Sensor Assembly — Install the sensor assembly in the location shown in Fig. 26.

Motor Mount — To ensure proper fan height, replace the exist- ing motor mount with the new motor mount provided with accessory.

Transformer (460 and 575-v Units Only) — On 460 and 575-volt units a transformer is required. The transformer is provided with the accessory and must be field-installed.

Motormaster I Control — Recommended mounting location is on the inside of the panel to the left of the control box. The control should be mounted on the inside of the panel, verti- cally, with leads protruding from bottom of extrusion.

MOTORMASTER® III CONTROL INSTALLATION (50TJ024 and 028 Only)

Install Field-Fabricated Wind Baffles — Wind baffles must be field-fabricated for all units to ensure proper cooling cycle operation at low ambient temperatures. See Fig. 25 for baffle details. Use 20-gage, galvanized sheet metal, or similar corrosion-resistant metal for baffles. Use field-supplied screws to attach baffles to unit. Screws should be 1/4-in. diameter and 5/8-in. long. Drill required screw holes for mounting baffles.

To avoid damage to the refrigerant coils and electrical com- ponents, use recommended screw sizes only. Use care when drilling holes.

Replace Outdoor Motor — Replace outdoor fan motor no. 1 with motor included in accessory kit. Existing motor is not Motormaster® III compatible.

Install Motormaster III Controls — Only one Motormaster III control is required per unit.

Sensor — Install the sensor for thermistor input control in the location shown in Fig. 27. Connect sensor leads to the purple and grey control signal leads on the Motormaster III control.

Signal Selection Switch — Remove the cover of the Motor- master III control. Set the switch to accept the thermistor sen- sor input signal. Set the frequency to match the unit power sup- ply (60 Hz).

Motormaster III Control — Recommended mounting location is beneath the control box, mounted to the partition that sepa- rates the control box section from the indoor section.

NOTE: Dimensions in ( ) are in mm.

Fig. 25 — Wind Baffle Details

NOTE: If unit power is supplied through the roof curb and basepan of the unit, mount the Motormaster III control on the corner post adjacent to the conduit running from the basepan to the bottom of the control box.

Step 10 — Install Humidistat for Optional MoistureMiser Dehumidification Package —

MositureMiser dehumidification package operation can be controlled by field installation of a Carrier-approved humidis- tat. To install the humidistat perform the following procedure:

1.Locate humidistat on a solid interior wall in the condi- tioned space. Location should be a well ventilated area to sense average humidity.

2.Route thermostat cable or equivalent single leads of col- ored wire from Humidistat terminals through conduit in unit to the low voltage connection on the 2-pole terminal strip (TB3) as shown in Fig. 28 and Fig. 29.

16

Image 16
Contents Installation ContentsSafety Considerations Roof Curb Details UnitUnit Maximum Dimensions Shipping Weight Ft-in 016020 024Base Unit Dimensions, 50TJ016,020 Base Unit Dimensions, 50TJ024,028 Physical Data COMPRESSOR/MANUFACTURERConcentric Duct Details Make Electrical Connections Unit VoltageGND NECElectrical Data Min MaxRLA LRA Qty FLA eaUnbalanced 3-Phase Supply Voltage 50TJMake Outdoor-Air Inlet Adjustments Optional Non-Fused Disconnect WiringUnit Stage Heat Anticipator Settings016-028 Seal Strip Location Air Hood Cross-Sectional View Default Potentiometer Settings EconoMi$er Switchover Control StrategyChangeover Set Points Motormaster I Control Installation 50TJ016 and 020 Only Wind Baffle Details Motormaster I Sensor Locations Air Quantity Limits START-UPUnit Minimum CFM Maximum CFM Fan Performance 50TJ016 FiopFan Performance 50TJ020 Fan Performance 50TJ028 Accessory/FIOP Static Pressure in. wg 50TJ020-028 Accessory/FIOP Static Pressure in. wg 50TJ016Fan Rpm at Motor Pulley Settings Base Unit Operation Service LubricationEvaporator Fan Service and Replacement Manufacturer LubricantBelt Tension Adjustment To adjust belt tension Condenser-Fan AdjustmentEconoMi$er Control Module Flash Code Identification EconoMi$er AdjustmentFlash Code Cause Action Taken by ECONOMI$ER Cooling Charging Chart Protective DevicesElectric Heat 208/240 v Amps 200/230 v kW 71.3/82.3117/135 156/180Typical Component Arrangement 50TJ024 Shown HPS HTRIFC IFRCooling Service Analysis TroubleshootingProblem Cause Remedy MoistureMiser Dehumidification Subcooler Service Analysis EconoMi$er TroubleshootingProblem Potential Cause Remedy Service Training Call for Free CatalogPage START-UP Checklist PRE-START-UP