Carrier 50TJ016-028 specifications Fan Performance 50TJ028

Page 21

Table 10 — Fan Performance — 50TJ028

50TJ028 (25 TONS)*

Airflow

 

 

 

 

 

 

Available External Static Pressure (in. wg)

 

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

 

1.0

 

 

1.2

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

7,000

845

3.26

2693

909

3.60

2979

969

3.96

3272

1028

4.32

3574

 

1083

4.70

3883

1137

5.08

4,200

7,500

896

3.82

3156

956

4.17

3450

1014

4.54

3752

1069

4.91

4060

 

1123

5.29

4375

1174

5.68

4,698

8,000

948

4.43

3667

1005

4.80

3969

1060

5.17

4278

1112

5.56

4593

 

1163

5.94

4915

1213

6.34

5,243

8,500

1001

5.11

4226

1054

5.49

4537

1106

5.87

4853

1156

6.26

5175

 

1205

6.66

5504

1253

7.06

5,838

9,000

1053

5.85

4836

1104

6.23

5155

1154

6.63

5478

1202

7.02

5808

 

1248

7.43

6142

1294

7.84

6,483

9,500

1106

6.65

5498

1155

7.04

5824

1202

7.44

6155

1248

7.85

6492

 

1293

8.26

6833

1336

8.68

7,179

10,000

1159

7.52

6214

1206

7.92

6547

1251

8.33

6886

1295

8.74

7229

 

1338

9.16

7577

1380

9.59

7,929

10,500

1213

8.45

6984

1257

8.86

7325

1300

9.28

7671

1342

9.70

8020

 

1384

10.13

8375

1424

10.56

8,733

11,000

1266

9.45

7810

1309

9.87

8159

1350

10.29

8511

1391

10.73

8868

 

1431

11.16

9229

1470

11.60

9,594

11,250

1293

9.97

8245

1334

10.40

8597

1375

10.83

8953

1415

11.26

9313

 

1454

11.70

9677

1493

12.15

10,045

50TJ028 (25 TONS)* (cont)

Airflow

 

Available External Static Pressure (in. wg)

 

 

1.4

 

 

1.6

 

 

1.8

 

(Cfm)

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

7,000

1189

5.47

4,524

1239

5.87

4,854

1288

4.91

5191

7,500

1224

6.08

5,026

1272

6.48

5,362

1320

5.56

5703

8,000

1261

6.75

5,577

1307

7.16

5,917

1353

6.26

6263

8,500

1299

7.47

6,177

1344

7.89

6,523

1388

7.02

6873

9,000

1338

8.26

6,828

1382

8.68

7,179

1424

7.85

7534

9,500

1379

9.11

7,530

1421

9.54

7,887

1462

8.74

8247

10,000

1421

10.02

8,286

1461

10.46

8,648

1501

9.70

9014

10,500

1464

11.00

9,096

1503

11.45

9,464

1541

10.73

9835

11,000

1508

12.05

9,963

1546

12.50

10,336

11,250

1530

12.60

10,417

 

LEGEND

 

 

 

 

 

 

 

Bhp —

Brake Horsepower

 

 

 

 

 

 

FIOP — Factory-Installed Option

 

 

 

 

 

Watts — Input Watts to Motor

 

 

 

 

 

 

*Standard low-medium static drive range is 1066 to 1283 rpm. Alter- nate high-static drive range is 1332 to 1550. Other rpms require a field-supplied drive.

NOTES:

1.Maximum continuous bhp is 10.2 (208/230, 575 v) or 11.8 (380, 460 v) and the maximum continuous watts are 9510 (208/230, 575 v) or 11,000 (380, 460 v). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maxi- mum operating cfm.

2.Static pressure losses (i.e., EconoMi$er) must be added to external static pressure before entering Fan Performance table.

3.Interpolation is permissible. Do not extrapolate.

4.Fan performance is based on wet coils, clean filters, and casing losses. See Table 12 for accessory/FIOP static pressure information.

5.Extensive motor and drive testing on these units ensures that the full horsepower and watts range of the motor can be utilized with confidence. Using your fan motors up to the watts or bhp rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

6.Use of a field-supplied motor may affect wiring size. Contact your Carrier representative for details.

21

Image 21
Contents Contents InstallationSafety Considerations Unit Roof Curb DetailsFt-in 016 Unit Maximum Dimensions Shipping Weight020 024Base Unit Dimensions, 50TJ016,020 Base Unit Dimensions, 50TJ024,028 COMPRESSOR/MANUFACTURER Physical DataConcentric Duct Details Unit Voltage Make Electrical ConnectionsGND NECMin Max Electrical DataRLA LRA Qty FLA ea50TJ Unbalanced 3-Phase Supply VoltageOptional Non-Fused Disconnect Wiring Make Outdoor-Air Inlet AdjustmentsHeat Anticipator Settings Unit Stage016-028 Seal Strip Location Air Hood Cross-Sectional View EconoMi$er Switchover Control Strategy Default Potentiometer SettingsChangeover Set Points Motormaster I Control Installation 50TJ016 and 020 Only Wind Baffle Details Motormaster I Sensor Locations START-UP Air Quantity LimitsUnit Minimum CFM Maximum CFM Fiop Fan Performance 50TJ016Fan Performance 50TJ020 Fan Performance 50TJ028 Accessory/FIOP Static Pressure in. wg 50TJ016 Accessory/FIOP Static Pressure in. wg 50TJ020-028Fan Rpm at Motor Pulley Settings Base Unit Operation Lubrication ServiceManufacturer Lubricant Evaporator Fan Service and ReplacementCondenser-Fan Adjustment Belt Tension Adjustment To adjust belt tensionEconoMi$er Adjustment EconoMi$er Control Module Flash Code IdentificationFlash Code Cause Action Taken by ECONOMI$ER Protective Devices Cooling Charging Chart208/240 v Amps 200/230 v kW 71.3/82.3 Electric Heat117/135 156/180Typical Component Arrangement 50TJ024 Shown HTR HPSIFC IFRTroubleshooting Cooling Service AnalysisProblem Cause Remedy EconoMi$er Troubleshooting MoistureMiser Dehumidification Subcooler Service AnalysisProblem Potential Cause Remedy Call for Free Catalog Service TrainingPage PRE-START-UP START-UP Checklist