Fig. 36 — Cooling Charging Chart
MOISTUREMISER SYSTEM CHARGING — The system charge for units with the MoistureMiser option is greater than that of the standard unit alone. The charge for units with this option is indicated on the unit nameplate drawing. To charge systems using the MoistureMiser Dehumidification package, fully evacuate, recover, and
Filter Drier — Replace whenever refrigerant system is ex- posed to atmosphere.
Protective Devices
COMPRESSOR PROTECTION
Overcurrent — Each compressor has internal line break motor protection, except the circuit no. 1 on the 50TJ028 unit. Com- pressor no. 1 on the 50TJ028 unit uses an electronic module lo- cated with the compressor junction box, to provide motor pro- tection. This electronic module monitors winding and dis- charge temperatures. If these temperatures reach the trip values, the module interrupts the control line and causes the compressor to switch off.
Crankcase Heater — Only the 50TJ028 unit and units with the optional MoistureMiser Dehumidification system are equipped with a
IMPORTANT: After prolonged shutdown or servicing, energize the crankcase heaters for 24 hours before start- ing the compressors.
Compressor Lockout — If any of the safeties
EVAPORATOR FAN MOTOR PROTECTION — A manu- al reset, calibrated trip, magnetic circuit breaker protects against overcurrent. Do not bypass connections or increase the size of the breaker to correct trouble. Determine the cause and correct it before resetting the breaker.
HIGH- AND
FREEZE PROTECTION THERMOSTAT (FPT) — An FPT is located on the top and bottom of the evaporator coil. It de- tects frost
Relief Devices — All units have relief devices to protect against damage from excessive pressures (e.g., fire). These de- vices protect the high and low side.
Control Circuit,
Replacement Parts — A complete list of replacement parts may be obtained from any Carrier distributor upon request.
EconoMi$er LEDs — The EconoMi$er control module has an LED for diagnostic purposes. The flash code identifica- tion is shown in Table 15.
Optional Hinged Access Doors — When the optional service package is ordered or the if the hinged access doors option is ordered, the unit will be provided with external and internal hinged access doors to facilitate service.
Four external hinged access doors are provided. All external doors are provided with 2 large 1/4 turn latches with folding
Two internal access doors are provided inside the filter/ drive access door. The filter access door (on the left) is secured by 2 small 1/4 turn latches with folding