Carrier 50TJ016-028 specifications Protective Devices, Cooling Charging Chart

Page 28

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BOTH CIRCUITS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALL OUTDOOR FANS MUST BE OPERATING

 

 

 

 

 

 

 

(DEG F)

140

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VALVE

120

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ADD

CHARGE

 

IF ABOVE CURVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LIQUIDAT

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TEMPERATURELIQUID

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REDUCE CHARGE IF BELOW CURVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

150

200

250

 

300

 

 

 

350

 

 

 

400

 

50

 

 

 

 

 

 

 

LIQUID PRESSURE AT LIQUID VALVE (PSIG)

Fig. 36 — Cooling Charging Chart

MOISTUREMISER SYSTEM CHARGING — The system charge for units with the MoistureMiser option is greater than that of the standard unit alone. The charge for units with this option is indicated on the unit nameplate drawing. To charge systems using the MoistureMiser Dehumidification package, fully evacuate, recover, and re-charge the system to the name- plate specified charge level. To check or adjust refrigerant charge on systems using the MoistureMiser Dehumidification package, charge per the standard subcooling charts. The sub- cooler MUST be deenergized to use the charging charts. The charts reference a liquid pressure (psig) and temperature at a point between the condenser coil and the subcooler coil. A tap is provided on the unit to measure liquid pressure entering the subcooler (leaving the condenser).

Filter Drier — Replace whenever refrigerant system is ex- posed to atmosphere.

Protective Devices

COMPRESSOR PROTECTION

Overcurrent — Each compressor has internal line break motor protection, except the circuit no. 1 on the 50TJ028 unit. Com- pressor no. 1 on the 50TJ028 unit uses an electronic module lo- cated with the compressor junction box, to provide motor pro- tection. This electronic module monitors winding and dis- charge temperatures. If these temperatures reach the trip values, the module interrupts the control line and causes the compressor to switch off.

Crankcase Heater — Only the 50TJ028 unit and units with the optional MoistureMiser Dehumidification system are equipped with a 70-watt crankcase heater to prevent absorption of liquid refrigerant by oil in the crankcase when the compres- sor is idle. The crankcase heater is energized whenever there is a main power to the unit and the compressor is not energized.

IMPORTANT: After prolonged shutdown or servicing, energize the crankcase heaters for 24 hours before start- ing the compressors.

Compressor Lockout — If any of the safeties (high-pressure, low-pressure, freeze protection thermostat, compressor internal thermostat) trip, or if there is loss of power to the compressors, the CLO (compressor lockout) will lock the compressors off. To reset, manually move the thermostat setting.

EVAPORATOR FAN MOTOR PROTECTION — A manu- al reset, calibrated trip, magnetic circuit breaker protects against overcurrent. Do not bypass connections or increase the size of the breaker to correct trouble. Determine the cause and correct it before resetting the breaker.

CONDENSER-FAN MOTOR PROTECTION — Each condenser-fan motor is internally protected against overtemperature.

HIGH- AND LOW-PRESSURE SWITCHES — If either switch trips, or if the compressor overtemperature switch acti- vates, that refrigerant circuit will be automatically locked out by the CLO. To reset, manually move the thermostat setting.

FREEZE PROTECTION THERMOSTAT (FPT) — An FPT is located on the top and bottom of the evaporator coil. It de- tects frost build-up and turns off the compressor, allowing the coil to clear. Once the frost has melted, the compressor can be reenergized.

Relief Devices — All units have relief devices to protect against damage from excessive pressures (e.g., fire). These de- vices protect the high and low side.

Control Circuit, 24-VThis control circuit is protect- ed against overcurrent by a 3.2-amp circuit breaker. Breaker can be reset. If it trips, determine cause of trouble before resetting.

Replacement Parts — A complete list of replacement parts may be obtained from any Carrier distributor upon request.

EconoMi$er LEDs — The EconoMi$er control module has an LED for diagnostic purposes. The flash code identifica- tion is shown in Table 15.

Optional Hinged Access Doors — When the optional service package is ordered or the if the hinged access doors option is ordered, the unit will be provided with external and internal hinged access doors to facilitate service.

Four external hinged access doors are provided. All external doors are provided with 2 large 1/4 turn latches with folding bail-type handles. (Compressor access doors have one latch.) A single door is provided for filter and drive access. One door is provided for control box access. The control box access door is interlocked with the non-fused disconnect which must be in the OFF position to open the door. Two doors are provided for ac- cess to the compressor compartment.

Two internal access doors are provided inside the filter/ drive access door. The filter access door (on the left) is secured by 2 small 1/4 turn latches with folding bail-type handles. This door must be opened prior to opening the drive access door. The drive access door is shipped with 2 sheet metal screws holding the door closed. Upon initial opening of the door, these screws may be removed and discarded. The door is then held shut by the filter access door, which closes over it.

28

Image 28
Contents Installation ContentsSafety Considerations Roof Curb Details UnitUnit Maximum Dimensions Shipping Weight Ft-in 016020 024Base Unit Dimensions, 50TJ016,020 Base Unit Dimensions, 50TJ024,028 Physical Data COMPRESSOR/MANUFACTURERConcentric Duct Details Make Electrical Connections Unit VoltageGND NECElectrical Data Min MaxRLA LRA Qty FLA eaUnbalanced 3-Phase Supply Voltage 50TJMake Outdoor-Air Inlet Adjustments Optional Non-Fused Disconnect WiringUnit Stage Heat Anticipator Settings016-028 Seal Strip Location Air Hood Cross-Sectional View Default Potentiometer Settings EconoMi$er Switchover Control StrategyChangeover Set Points Motormaster I Control Installation 50TJ016 and 020 Only Wind Baffle Details Motormaster I Sensor Locations Air Quantity Limits START-UPUnit Minimum CFM Maximum CFM Fan Performance 50TJ016 FiopFan Performance 50TJ020 Fan Performance 50TJ028 Accessory/FIOP Static Pressure in. wg 50TJ020-028 Accessory/FIOP Static Pressure in. wg 50TJ016Fan Rpm at Motor Pulley Settings Base Unit Operation Service LubricationEvaporator Fan Service and Replacement Manufacturer LubricantBelt Tension Adjustment To adjust belt tension Condenser-Fan AdjustmentEconoMi$er Control Module Flash Code Identification EconoMi$er AdjustmentFlash Code Cause Action Taken by ECONOMI$ER Cooling Charging Chart Protective DevicesElectric Heat 208/240 v Amps 200/230 v kW 71.3/82.3117/135 156/180Typical Component Arrangement 50TJ024 Shown HPS HTRIFC IFRCooling Service Analysis TroubleshootingProblem Cause Remedy MoistureMiser Dehumidification Subcooler Service Analysis EconoMi$er TroubleshootingProblem Potential Cause Remedy Service Training Call for Free CatalogPage START-UP Checklist PRE-START-UP