Carrier 50TJ016-028 specifications EconoMi$er Switchover Control Strategy, Changeover Set Points

Page 14

MECHANICAL COOLING LOCKOUT — Determine the outdoor-air temperature at which you want the mechanical cooling (compressors) to be disabled. Locate the mechanical cooling lockout (MECH CLG LOCKOUT) potentiometer. To disable this feature, turn the potentiometer counterclockwise (CCW) to the OFF position. Otherwise, set the value between 10 and 60 F. Mechanical cooling will not operate when the out- door air temperature is below this value. See Fig. 16.

DRY BULB CHANGEOVER SET UP — Determine the dry bulb changeover set point from Table 5. The settings are A, B, C and D. Locate the ECON SP potentiometer and set the dry bulb changeover set point. See Fig. 16. When the OAT is above this set point, the damper is limited to minimum position setting.

If a potentiometer fails, its setting will default to the values in Table 6.

Table 4 — EconoMi$er Switchover Control Strategy

ECONOMI$ER SWITCHOVER

 

SENSORS REQUIRED

 

STRATEGY

Outdoor Air Temperature

Outdoor Air Enthalpy

Return Air Temperature

Return Air Enthalpy

Dry Bulb

X

 

 

 

 

 

 

 

 

Single Enthalpy

 

X

 

 

 

 

 

 

 

Differential Temperature

X

 

X

 

 

 

 

 

 

Differential Enthalpy*

 

X

 

X

 

 

 

 

 

*Must be selected manually.

Table 5 — Changeover Set Points

SETTINGS

A

B

C

D

Dry Bulb (°F)

73

69

66

63

Single Enthalpy* (Btu/lb)

27

25

24

22

Differential Temperature*

2

2

2

2

(°F, Not Adjustable)

 

 

 

 

Differential Enthalpy*

1

1

1

1

(Btu/lb, Not Adjustable)

 

 

 

 

*Field-installed accessory.

 

 

 

 

Table 6 — Default Potentiometer Settings

POTENTIOMETER

DEFAULT SETTING

CO2 SP (PPM)

1,000

MECH CLG LOCKOUT

50 F

ECON SP

D

MIN POS (%)

20

 

LEGEND

COM

Common

DAT

Discharge Air Thermistor

DM

Damper Motor

GND

Ground

OAH

Outdoor-Air Enthalpy Sensor

OAT

Outdoor-Air Temperature Sensor

POT

Potentiometer

RAH

Return-Air Enthalpy Sensor

RAT

Return-Air Temperature Sensor

REM

Remote

*OAT sensor shipped with economizer option. OAH, RAT, RAH and CO2 are field-installed accessories.

Fig. 23 — Typical EconoMi$er Sensor Wiring

14

Image 14
Contents Safety Considerations ContentsInstallation Roof Curb Details Unit020 Unit Maximum Dimensions Shipping WeightFt-in 016 024Base Unit Dimensions, 50TJ016,020 Base Unit Dimensions, 50TJ024,028 Physical Data COMPRESSOR/MANUFACTURERConcentric Duct Details GND Make Electrical ConnectionsUnit Voltage NECRLA LRA Electrical DataMin Max Qty FLA eaUnbalanced 3-Phase Supply Voltage 50TJMake Outdoor-Air Inlet Adjustments Optional Non-Fused Disconnect Wiring016-028 Heat Anticipator SettingsUnit Stage Seal Strip Location Air Hood Cross-Sectional View Changeover Set Points EconoMi$er Switchover Control StrategyDefault Potentiometer Settings Motormaster I Control Installation 50TJ016 and 020 Only Wind Baffle Details Motormaster I Sensor Locations Unit Minimum CFM Maximum CFM START-UPAir Quantity Limits Fan Performance 50TJ016 FiopFan Performance 50TJ020 Fan Performance 50TJ028 Fan Rpm at Motor Pulley Settings Accessory/FIOP Static Pressure in. wg 50TJ016Accessory/FIOP Static Pressure in. wg 50TJ020-028 Base Unit Operation Service LubricationEvaporator Fan Service and Replacement Manufacturer LubricantBelt Tension Adjustment To adjust belt tension Condenser-Fan AdjustmentFlash Code Cause Action Taken by ECONOMI$ER EconoMi$er AdjustmentEconoMi$er Control Module Flash Code Identification Cooling Charging Chart Protective Devices117/135 Electric Heat208/240 v Amps 200/230 v kW 71.3/82.3 156/180Typical Component Arrangement 50TJ024 Shown IFC HPSHTR IFRProblem Cause Remedy TroubleshootingCooling Service Analysis Problem Potential Cause Remedy EconoMi$er TroubleshootingMoistureMiser Dehumidification Subcooler Service Analysis Service Training Call for Free CatalogPage START-UP Checklist PRE-START-UP