Carrier 50TJ016-028 specifications Unbalanced 3-Phase Supply Voltage

Page 10

Table 2 — Electrical Data (cont)

UNIT

NOMINAL

VOLTAGE

COMPRESSOR

 

OFM

 

 

IFM

POWER

ELECTRIC

POWER

VOLTAGE

RANGE

No. 1

No. 2

 

 

 

EXHAUST

HEAT*

SUPPLY

 

 

 

 

 

 

50TJ

(3 Ph,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60 Hz)

Min

Max

RLA

LRA

RLA

LRA

Qty

Hp

FLA (ea)

Hp

FLA

FLA

LRA

kW

FLA

MCA

MOCP†

 

 

 

 

 

 

 

 

 

 

 

 

 

 

130/130

150/150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.6

18.8

135/135

175/175

 

 

 

 

 

 

 

 

 

 

 

 

 

 

26/34

71/82

130/138

150/150

 

208/230

187

253

41.0

350

37.8

239

2

1

 

6.6

10.0

28.0/28.0

4.6

18.8

26/34

71/82

135/143

175/175

 

 

42/56

117/135

181/170

200/175

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.6

18.8

42/56

117/135

187/176

200/200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-

56/75**

156/180

191/215

200/225

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.6

18.8

56/75**

156/180

197/221

200/225

 

 

 

 

 

 

 

 

 

 

 

 

 

 

73

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.3

6.0

76

90

028

380

342

418

21.8

151

21.2

145

2

1

 

3.9

10.0

17.0

20

30

73

90

 

2.3

6.0

20

30

76

90

 

 

 

 

 

 

 

 

 

 

 

 

 

(25 Tons)

 

 

 

 

 

 

 

 

 

 

 

 

 

35

52

87

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.3

6.0

35

52

90

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

66

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.3

6.0

68

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

32

39

67

80

 

460

414

508

21.8

158

17.2

125

2

1

 

2.8

10.0

14.6

2.3

6.0

32

39

70

80

 

 

55

66

84

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.3

6.0

55

66

87

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80**

96

114

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.3

6.0

80**

96

117

125

 

575

518

633

17.3

125

12.4

80

2

1

 

3.4

10.0

13.0

54

70

 

 

2.1

4.8

56

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

FLA — Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration

IFM — Indoor (Evaporator) Fan Motor

LRA — Locked Rotor Amps

MCA — Minimum Circuit Amps

MOCP— Maximum Overcurrent Protection

NEC — National Electrical Code

OFM — Outdoor (Condenser) Fan Motor

RLA — Rated Load Amps

*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 380 v, 480 v, and 575 v. Heaters are rated at 240 v, 380 v, 480 v, or 600 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly.

†Fuse or HACR circuit breaker. **Heaters are field installed only.

NOTES:

1.In compliance with NEC requirements for multimotor and combi- nation load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt- age is greater than 2%. Use the following formula to determine the percent of voltage imbalance.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

 

Example: Supply voltage is 460-3-60.

AB = 452 v BC = 464 v AC = 455 v

Average Voltage = 452 + 464 + 455 3

= 1371 3

= 457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

7

% Voltage Imbalance = 100 x 457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

3.MCA calculation for units with electric heaters over 50 kW = (1.25 x IFM amps) + (1.00 x heater FLA).

10

Image 10
Contents Installation ContentsSafety Considerations Roof Curb Details Unit020 Unit Maximum Dimensions Shipping WeightFt-in 016 024Base Unit Dimensions, 50TJ016,020 Base Unit Dimensions, 50TJ024,028 Physical Data COMPRESSOR/MANUFACTURERConcentric Duct Details GND Make Electrical ConnectionsUnit Voltage NECRLA LRA Electrical DataMin Max Qty FLA eaUnbalanced 3-Phase Supply Voltage 50TJMake Outdoor-Air Inlet Adjustments Optional Non-Fused Disconnect WiringUnit Stage Heat Anticipator Settings016-028 Seal Strip Location Air Hood Cross-Sectional View Default Potentiometer Settings EconoMi$er Switchover Control StrategyChangeover Set Points Motormaster I Control Installation 50TJ016 and 020 Only Wind Baffle Details Motormaster I Sensor Locations Air Quantity Limits START-UPUnit Minimum CFM Maximum CFM Fan Performance 50TJ016 FiopFan Performance 50TJ020 Fan Performance 50TJ028 Accessory/FIOP Static Pressure in. wg 50TJ020-028 Accessory/FIOP Static Pressure in. wg 50TJ016Fan Rpm at Motor Pulley Settings Base Unit Operation Service LubricationEvaporator Fan Service and Replacement Manufacturer LubricantBelt Tension Adjustment To adjust belt tension Condenser-Fan AdjustmentEconoMi$er Control Module Flash Code Identification EconoMi$er AdjustmentFlash Code Cause Action Taken by ECONOMI$ER Cooling Charging Chart Protective Devices117/135 Electric Heat208/240 v Amps 200/230 v kW 71.3/82.3 156/180Typical Component Arrangement 50TJ024 Shown IFC HPSHTR IFRCooling Service Analysis TroubleshootingProblem Cause Remedy MoistureMiser Dehumidification Subcooler Service Analysis EconoMi$er TroubleshootingProblem Potential Cause Remedy Service Training Call for Free CatalogPage START-UP Checklist PRE-START-UP