122 G7 ASD Operation Manual
Upper Deviation Limits
Program Feedback Parameters Feedback Settings
This parameter determin es th e m ax im um amount that the feedba c k m ay
increase the output signal.
Direct Access Number F364
Parameter Type — Numerical
Factory Default — 50.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 50.00
Units — %
Lower Deviation Limits
Program Feedback Parameters Feedback Settings
This parameter determin es th e m ax im um amount that the feedba c k m ay
decrease the output signal.
Direct Access Number F365
Parameter Type — Numerical
Factory Default — 50.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 50.00
Units — %
Feedback Settings Differential (D) Gain
Program Feedback Parameters Feedback Settings
This parameter determines th e de g re e th at the Differential functi on affects the
output signal. The larger the valu e entered here, the more prono un c ed th e aff ec t
of the differential functi on for a given feedback si gnal level.
Direct Access Number F366
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.0
Maximum — 2.55
Number of PG Inp ut Pulses
Program Feedback Parameters PG Settings
This parameter is used to set the end-of-travel range when using an encoder on
a motor-driven positioning system (e.g., hoist/crane, etc.).
Direct Access Number F367
Parameter Type — Numerical
Factory Default — 500
Changeable During Run — No
Minimum — 1
Maximum — 9999
Units — Pulse Count
PG Input Phases
Program Feedback Parameters PG Settings
This parameter determines the type of i nformation that is supplied by the phase
encoder.
Settings:
1 — Speed
2 — Speed and Direction
Direct Access Number F368
Parameter Type — Selection List
Factory Default — 2
Changeable During Run — No
Minimum — 1
Maximum — 2
Units — Phase Count
PG Disconnect Detection
Program Feedback Parameters PG Settings
This parameter Enables/Disables th e syste m’s monitoring of the PG connection
status when using encoders with line drive r outputs.
Settings:
Disabled
Enabled
Direct Access Number F369
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
F364 F369