F364 | F369 |
Upper Deviation Limits
Program ⇒ Feedback Parameters ⇒ Feedback Settings
This parameter determines the maximum amount that the feedback may increase the output signal.
Direct Access Number — F364
Parameter Type — Numerical
Factory Default — 50.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 50.00
Units — %
Lower Deviation Limits
Program ⇒ Feedback Parameters ⇒ Feedback Settings
This parameter determines the maximum amount that the feedback may decrease the output signal.
Direct Access Number — F365
Parameter Type — Numerical
Factory Default — 50.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 50.00
Units — %
Feedback Settings Differential (D) Gain
Program ⇒ Feedback Parameters ⇒ Feedback Settings
This parameter determines the degree that the Differential function affects the output signal. The larger the value entered here, the more pronounced the affect of the differential function for a given feedback signal level.
Direct Access Number — F366
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.0
Maximum — 2.55
Number of PG Input Pulses
Program ⇒ Feedback Parameters ⇒ PG Settings
This parameter is used to set the
Direct Access Number — F367
Parameter Type — Numerical
Factory Default — 500
Changeable During Run — No
Minimum — 1
Maximum — 9999
Units — Pulse Count
PG Input Phases | Direct Access Number — | F368 | |
Program ⇒ Feedback Parameters ⇒ PG Settings | Parameter Type — Selection List | ||
This parameter determines the type of information that is supplied by the phase | Factory Default — 2 |
| |
Changeable During Run — No | |||
encoder. | |||
|
| ||
| Minimum — 1 |
| |
Settings: | Maximum — 2 |
| |
|
| ||
1 — Speed | Units — Phase Count |
| |
2 — Speed and Direction |
| ||
|
| ||
|
|
| |
PG Disconnect Detection | Direct Access Number — | F369 | |
Program ⇒ Feedback Parameters ⇒ PG Settings | Parameter Type — Selection List | ||
| Factory Default — Disabled |
|
This parameter Enables/Disables the system’s monitoring of the PG connection
status when using encoders with line driver outputs.
Settings:
Disabled
Enabled
Changeable During Run — No