F260

F260

Jog Run Frequency

Program Frequency Setting Parameters Jog Settings

This parameter sets the output frequency of the drive during a Jog. Jogging is the term used to describe turning the motor on for small increments of time and is used when precise positioning of motor-driven equipment is required.

Enabling the Jog Window allows for the Manual Jog window to be among the screens accessed during repeated MON/PRG entries. This screen must be displayed when Jogging using the EOI.

The Jog function may be initiated from the EOI or remotely via the Control Terminal Strip or using Communications (for further information on using Communications for Jogging, see the Communications manual).

To perform a Jog, set this parameter (F260) to the desired Jog frequency.

Select a Jog Stop method (F261).

Jog Using the EOI

To initiate a Jog from the EOI perform the following:

1.Place a check in the Enable Jog Window box (Program Frequency Setting Parameters Jog Settings Enable Jog Window).

Note: The Jog Window must be displayed on the EOI to perform the Jog function using the EOI.

2.Press MON/PRG to access the Jog Window.

3.Using the Up/Down arrow keys of the EOI, select Reverse or Forward.

4.Place the system in the Local mode (Local/Remote LED is on).

5.Press and hold the Run key for the desired Jog duration.

Jog Using the Control Terminal Strip

To initiate a Jog from the Control Terminal Strip perform the following:

1.Assign a discrete input terminal to the Jog function (see Table 8 on pg. 76).

2.Assign a discrete input terminal to the F (Forward) function (and Reverse if required) (see Table 8 on pg. 76).

3.Provide a Forward and/or Reverse command from the Control Terminal Strip.

4.From the Jog Window, use the Up/Down arrow keys of the EOI to select Reverse or Forward (Program Frequency Setting Parameters Jog Settings Enable Jog Window). Press MON/ PRG to access the Jog Window.

5.Place the system in the Remote mode (Local/Remote LED is off).

6.Connect the assigned Jog terminal (from step 1) to CC for the desired Jog duration.

Direct Access Number — F260

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 20.00

Units — Hz

G7 ASD Operation Manual

107

Page 113