G7 ASD Operation Manual 107
Jog Run Frequency
Program Frequency Setting Parameters Jog Settings
This parameter sets the output frequency of the drive during a Jog. Jogging is
the term used to describe turn in g th e moto r on fo r sm a ll inc re ments of time and
is used when precise positioning of motor-driven equipment is required.
Enabling the Jog Window allows for the Manual Jog window to be among the
screens accessed during repeated MON/PRG entries. This screen must be
displayed when Jogging using the EOI.
The Jog function may be initiated from the EOI or remotely via the Control
Terminal Strip or using Communications (for further information on using
Communications for Jogging, see the Communications manual).
To perform a Jog, set this parameter (F260) to the desired Jog frequency.
Select a Jog Stop method (F261).
Jog Using the EOI
To initiate a Jog from the EOI perform the following:
1. Place a check in the Enable Jog Window box (Program Frequency
Setting Parameters Jog Settings Enable Jog Window).
Note: The Jog Window must be displayed on the EOI to perform the
Jog function using the EOI.
2. Press MON/PRG to access the Jog Window.
3. Using the Up/Down arrow keys of the EOI, select Reverse or
Forward.
4. Place the system in the Local mode (Local/Remote LED is on).
5. Press and hold the Run key for the desired Jog duration.
Jog Using the Control Terminal Strip
To initiate a Jog from the Control Terminal Strip perform the following:
1. Assign a discre te input terminal to the Jog function (see Table 8 on pg.
76).
2. Assign a discre te in pu t te rm i n al to the F (Forward) function (and
Reverse if required) (see Table 8 on pg . 76).
3. Provide a Forward and/or Reverse command from the Control
Terminal Strip.
4. From the Jog Window, use the Up/Down arrow keys of the EOI to
select Reverse or Forward (Program Frequency Setting
Parameters Jog Settings Enable Jog Window). Press MON/
PRG to access the Jog Window.
5. Place the system in the Remote mode (Local/Remote LED is off).
6. Connect the assigned Jog terminal (from step 1) to CC for the desired
Jog duration.
Direct Access Number — F260
Parameter Type — Numeri cal
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 20.00
Units — Hz
F260 F260