F108

F112

Motorized Pot Frequency at Power Down

Program Frequency Setting Parameters Motorized Pot Settings

When the Frequency Mode #1 Selection (F004) setting is set to Use MOP Function Simulation, this parameter determines the outcome of the Frequency Mode #1 setting at powerdown or stop.

Settings:

Erase

Store

Direct Access Number — F108

Parameter Type — Selection List

Factory Default — Erase

Changeable During Run — No

If Erase is selected, the ASD will not store the frequency setpoint and establishes a setpoint of 0.0 Hz when restarted.

If Store is selected, the ASD will maintain the current frequency setpoint in memory while stopped, during fault conditions, or when power is removed. This setpoint will be used as the initial frequency setpoint when the ASD is restarted.

A control terminal configured as MOP Frequency Clear will establish a frequency setpoint of 0.0 Hz regardless of the Motorized Pot Frequency at Power Down setting.

ON Input Terminal Assignment

Program Terminal Selection Parameters Input Terminal Assignment ON

This parameter selects the functionality of the virtual input terminal ON. As a virtual terminal, the ON control terminal exists only in memory and is considered to always be in its True (or connected to CC) state.

It is often practical to assign this terminal to a function that the user desires to be maintained regardless of external conditions or operations.

This parameter sets the programmable ON terminal to 1 of the 68 possible functions that are listed in Table 8 on pg. 76.

Direct Access Number — F110

Parameter Type — Selection List

Factory Default — Unassigned

Changeable During Run — No

F Input Terminal Assignment

Program Terminal Selection Parameters Input Terminal Assignment F

This parameter selects the functionality of the F input terminal.

In addition, the input terminal must be specified as Normally Open or Normally Closed.

This parameter sets the programmable F terminal to 1 of the 68 possible functions that are listed in Table 8 on pg. 76.

Direct Access Number — F111

Parameter Type — Selection List

Factory Default — Forward

Changeable During Run — No

R Input Terminal Assignment

Program Terminal Selection Parameters Input Terminal Assignment R

This parameter selects the functionality of the R input terminal.

In addition, the input terminal must be specified as Normally Open or Normally Closed.

This parameter sets the programmable R terminal to 1 of the 68 possible functions that are listed in Table 8 on pg. 76.

Direct Access Number — F112

Parameter Type — Selection List

Factory Default — Reverse

Changeable During Run — No

G7 ASD Operation Manual

71

Page 77
Image 77
Toshiba G7 manual Motorized Pot Frequency at Power Down, On Input Terminal Assignment