F218 | F221 |
RX Speed Reference Setpoint #2 (%)
Program ⇒ Frequency Setting Parameters ⇒ Speed Reference Setpoints ⇒ RX
This parameter is used to set the direction, gain, and bias of the RX input terminal when this terminal is used as the control input while operating in the Speed Control or the Torque Control mode.
See F216 for further information on this setting.
This parameter sets the RX input level that represents RX Reference Setpoint #2 (frequency) (direction/torque/frequency). The range of values for this parameter is
Direct Access Number — F218
Parameter Type — Numerical
Factory Default — +100.0
Changeable During Run — Yes
Minimum —
Maximum — +100.0
Units — %
RX Speed Reference Setpoint #2 (frequency)
Program ⇒ Frequency Setting Parameters ⇒ Speed Reference Setpoints ⇒ RX
This parameter is used to set the direction, gain, and bias of the RX input terminal when this terminal is used as the control input while operating in the Speed Control mode.
See F216 for further information on this setting.
This parameter sets RX Speed Reference Setpoint #2 (frequency) and is the frequency that is associated with the setting of F218.
Direct Access Number — F219
Parameter Type — Numerical
Factory Default — +80.0
Changeable During Run — Yes
Minimum —
Maximum — +80.0
Units — Hz
RX Torque Reference Setpoint #1 (%)
Program ⇒ Torque Setting Parameters ⇒ Setpoints ⇒ RX
This parameter is used to set the direction, gain, and bias of the RX input terminal when this terminal is used as the control input while operating in the Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for a given RX input level and motor load.
See F216 for further information on this setting.
This parameter sets RX Torque Reference Setpoint #1 (%) and is the output torque value that is associated with setting of F216. This value is entered as
Direct Access Number — F220
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum —
Maximum — +250.0
Units — %
RX Torque Reference Setpoint #2 (%)
Program ⇒ Torque Setting Parameters ⇒ Setpoints ⇒ RX
This parameter is used to set the direction, gain, and bias of the RX input terminal when this terminal is used as the control input while operating in the Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for a given RX input level and motor load.
See F220 for further information on this setting.
This parameter sets RX Torque Reference Setpoint #2 (%) and is the output torque value that is associated with setting of F218. This value is entered as
Direct Access Number — F221
Parameter Type — Numerical
Factory Default — +100.0
Changeable During Run — Yes
Minimum —
Maximum — +250.0
Units — %
98 | G7 ASD Operation Manual |