RX Speed Reference Setpoint #2 (%)

Program Frequency Setting Parameters Speed Reference Setpoints RX

This parameter is used to set the direction, gain, and bias of the RX input terminal when this terminal is used as the control input while operating in the Speed Control or the Torque Control mode.

See F216 for further information on this setting.

This parameter sets the RX input level that represents RX Reference Setpoint #2 (frequency) (direction/torque/frequency). The range of values for this parameter is -100 to +100% of the -10 to +10 VDC RX input signal range.

Direct Access Number — F218

Parameter Type — Numerical

Factory Default — +100.0

Changeable During Run — Yes

Minimum — -100.0

Maximum — +100.0

Units — %

RX Speed Reference Setpoint #2 (frequency)

Program Frequency Setting Parameters Speed Reference Setpoints RX

This parameter is used to set the direction, gain, and bias of the RX input terminal when this terminal is used as the control input while operating in the Speed Control mode.

See F216 for further information on this setting.

This parameter sets RX Speed Reference Setpoint #2 (frequency) and is the frequency that is associated with the setting of F218.

Direct Access Number — F219

Parameter Type — Numerical

Factory Default — +80.0

Changeable During Run — Yes

Minimum — -80.0

Maximum — +80.0

Units — Hz

RX Torque Reference Setpoint #1 (%)

Program Torque Setting Parameters Setpoints RX

This parameter is used to set the direction, gain, and bias of the RX input terminal when this terminal is used as the control input while operating in the Torque Control mode.

This is accomplished by establishing an associated V/f output pattern for a given RX input level and motor load.

See F216 for further information on this setting.

This parameter sets RX Torque Reference Setpoint #1 (%) and is the output torque value that is associated with setting of F216. This value is entered as -250 to +250% of the rated torque.

Direct Access Number — F220

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — -250.0

Maximum — +250.0

Units — %

RX Torque Reference Setpoint #2 (%)

Program Torque Setting Parameters Setpoints RX

This parameter is used to set the direction, gain, and bias of the RX input terminal when this terminal is used as the control input while operating in the Torque Control mode.

This is accomplished by establishing an associated V/f output pattern for a given RX input level and motor load.

See F220 for further information on this setting.

This parameter sets RX Torque Reference Setpoint #2 (%) and is the output torque value that is associated with setting of F218. This value is entered as -250 to +250% of the rated torque.

Direct Access Number — F221

Parameter Type — Numerical

Factory Default — +100.0

Changeable During Run — Yes

Minimum — -250.0

Maximum — +250.0

Units — %

98

G7 ASD Operation Manual

Page 104