F009

F012

Accel #1 Time

Program Fundamental Parameters Accel/Decel #1 Settings

This parameter specifies the time in seconds for the drive to go from 0.0 Hz to the Maximum Frequency for the #1 Acceleration profile. The accel/decel pattern may be set using F502. The minimum accel/decel time may be set using

F508.

Note: An acceleration time shorter than the load will allow may cause nuisance tripping and mechanical stress to loads.

Automatic Accel/Decel and Stall settings may lengthen the acceleration time.

Direct Access Number — F009

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 0.1

Maximum — 6000

Units — Seconds

Acceleration

The acceleration rate of a motor is determined by several factors: applied power, applied load, and the physical properties of the motor (winding parameters, motor size, etc.). The ASD will control the first of these factors: input power. The settings of the ASD control the frequency and amplitude of the applied voltage to the motor.

Under most operating conditions, as the output frequency of the drive goes up so does the output voltage (linear acceleration). The ASD has the ability to modify the relationship between frequency and voltage automatically to produce smoother operation or increased (starting) torque.

Decel #1 Time

Direct Access Number —

F010

Program Fundamental Parameters Accel/Decel #1 Settings

Parameter Type — Numerical

This parameter specifies the time in seconds for the drive to go from the

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Maximum Frequency to 0.0 Hz for the #1 Deceleration profile. The accel/

 

 

decel pattern may be set using F502.

Minimum — 0.1

 

When operating with the Automatic Accel/Decel enabled (F000) the minimum

Maximum — 6000

 

Units — Seconds

 

accel/decel time may be set using F508.

 

 

 

Note:

A deceleration time shorter than the load will allow may cause

 

 

 

nuisance tripping and mechanical stress to loads.

 

 

 

Automatic Accel/Decel and Stall settings may lengthen the

 

 

 

acceleration time.

 

 

 

 

 

Maximum Frequency

Direct Access Number —

F011

Program Fundamental Parameters Frequency Settings

Parameter Type — Numerical

This setting determines the absolute maximum frequency that the ASD can

Factory Default — 80.0

 

Changeable During Run — No

output. This setting is also referred to as FH.

 

 

Accel/decel times are calculated based on the Maximum Frequency setting.

Minimum — 30.0

 

 

 

 

 

Maximum — 299.0

 

Note:

This setting may not be lower than the Upper Limit setting

Units — Hz

 

 

(F012).

 

 

 

 

 

 

 

Upper Limit Frequency

Direct Access Number —

F012

Program Fundamental Parameters Frequency Settings

Parameter Type — Numerical

This parameter sets the highest frequency that the ASD will accept as a

Factory Default — 80.0

 

Changeable During Run — Yes

frequency command or frequency setpoint. The ASD may output frequencies

 

 

higher than the Upper Limit Frequency (but, lower than the Maximum

Minimum — 0.0

 

Frequency) when operating in the PID Control mode, Torque Control mode,

Maximum — Max. Freq. (F011)

or the Vector Control modes (sensorless or feedback).

Units — Hz

 

 

 

 

Note:

This setting may not be higher than the Maximum Frequency

 

 

 

(F011) setting.

 

 

G7 ASD Operation Manual

 

63

Page 69
Image 69
Toshiba G7 manual Accel #1 Time, Acceleration, Decel #1 Time, Maximum Frequency, Upper Limit Frequency