F216

F217

RX Speed Reference Setpoint #1 (%)

Program Frequency Setting Parameters Speed Reference Setpoints RX

This parameter is used to set the direction, gain, and bias of the RX input terminal when this terminal is used as the control input while operating in the Speed Control or the Torque Control mode.

Perform the following setup to allow the system to receive control input at the RX input terminal:

Program Fundamental Parameters Standard Mode Selection Command Mode Use Control Terminal Strip.

Program Fundamental Parameters Standard Mode Selection Frequency Mode #1Use RX.

Provide a Run command (F or R).

Gain and Bias Settings

When operating in the Speed Control mode, the settings that determine the direction, gain, and bias of the RX terminal are:

RX Speed Reference Setpoint #1 (frequency) (F217),

the RX input signal level that represents RX Speed Reference Setpoint #1 (frequency): F216,

RX Speed Reference Setpoint #2 (frequency) (F219), and

the RX input signal level that represents RX Speed Reference Setpoint #2 (frequency): F218.

When operating in the Torque Control mode, the settings that determine the direction, gain, and bias of the RX terminal are:

RX Torque Reference Setpoint #1 (%) (F220),

the RX input signal level that represents the RX Torque Reference Setpoint #1 (%): F216,

RX Torque Reference Setpoint #2 (%) (F221), and

the RX input signal level that represents the RX Torque Reference Setpoint #2 (%): F218.

Direct Access Number — F216

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — -100.0

Maximum — 100.0

Units — %

Frequency Settings

Torque Settings

Once set, as the RX input voltage changes, the directional information, the output frequency, or the output torque of the drive will vary in accordance with the above settings.

This parameter sets the RX input level that represents RX Reference Setpoint #1 (direction/torque/frequency). This value is entered as -100 to +100% of the -10 to +10 VDC RX input signal range.

The input signal may be trimmed using F474 (Bias) and F475 (Gain).

RX Speed Reference Setpoint #1 (frequency)

Direct Access Number — F217

Program Frequency Setting Parameters Speed Reference

Parameter Type — Numerical

Setpoints RX

Factory Default — 0.0

This parameter is used to set the direction, gain, and bias of the RX input

Changeable During Run — Yes

 

terminal when this terminal is used as the control input while operating in the

Minimum — -80.0

Speed Control mode.

Maximum — +80.0

 

See F216 for further information on this setting.

Units — Hz

This parameter sets RX Speed Reference Setpoint #1 (frequency) and is the

 

frequency that is associated with the setting of F216.

 

G7 ASD Operation Manual

97

Page 103
Image 103
Toshiba G7 manual RX Speed Reference Setpoint #1 %, RX Speed Reference Setpoint #1 frequency