F013 |
| F015 | |
|
|
| |
Lower Limit Frequency | Direct Access Number — | F013 | |
Program ⇒ Fundamental Parameters ⇒ Frequency Settings | Parameter Type — Numerical | ||
This parameter sets the lowest frequency that the ASD will accept as a | Factory Default — 0.0 |
| |
Changeable During Run — Yes | |||
frequency command or frequency setpoint. The ASD will output frequencies | |||
|
| ||
lower than the Lower Limit Frequency when accelerating to the lower limit or | Minimum — 0.0 |
| |
decelerating to a stop. Frequencies below the Lower Limit may also be output | Maximum — Upper Limit (F012) | ||
when operating in the PID Control mode, Torque Control mode, or the | |||
Units — Hz |
| ||
Vector Control modes (sensorless or feedback). |
| ||
|
| ||
|
|
| |
Motor #1 Base Frequency | Direct Access Number — | F014 | |
Program ⇒ Fundamental Parameters ⇒ Motor Set #1 | Parameter Type — Numerical | ||
The Base Frequency setting determines the frequency at which the output | Factory Default — 60.0 |
| |
Changeable During Run — Yes | |||
voltage of the ASD reaches its maximum setting. The maximum voltage setting | |||
|
| ||
cannot be more that the input voltage (see Maximum Output Voltage at | Minimum — 25.0 |
| |
F306). There are four Base Frequency profile settings: #1 – #4. | Maximum — 299.0 |
| |
|
| ||
Note: For proper motor operation, the Base Frequency is normally set | Units — Hz |
| |
for the |
|
|
V/f Pattern
Program ⇒ Fundamental Parameters ⇒ Frequency Settings
This function establishes the relationship between the output frequency and the output voltage.
Settings:
Constant Torque
Variable Torque Automatic Torque Boost Sensorless Vector Control (speed)
Auto Torque Boost with Automatic Energy Savings
Sensorless Vector Control (speed) with Automatic Energy Savings V/f
Sensorless Vector Control (speed/torque switching) PG Feedback Vector Control (speed/torque switching) PG Feedback Vector Control (speed/position switching)
Direct Access Number — F015
Parameter Type — Selection List
Factory Default — Constant Torque
Changeable During Run — No
Note: For proper operation, the carrier frequency must be 2.2 kHz or above except when operating in the Constant Torque, Variable Torque, or the
The Automatic Torque Boost and the Sensorless Vector Control selections use the motor tuning parameters of the drive to properly configure the ASD for the motor being used. If Load Reactors or Long Lead Filters are used, or if the capacity of the ASD is greater than the motor, manual tuning of the motor parameters may be required for optimum performance.
64 | G7 ASD Operation Manual |