F013

 

F015

 

 

 

Lower Limit Frequency

Direct Access Number —

F013

Program Fundamental Parameters Frequency Settings

Parameter Type — Numerical

This parameter sets the lowest frequency that the ASD will accept as a

Factory Default — 0.0

 

Changeable During Run — Yes

frequency command or frequency setpoint. The ASD will output frequencies

 

 

lower than the Lower Limit Frequency when accelerating to the lower limit or

Minimum — 0.0

 

decelerating to a stop. Frequencies below the Lower Limit may also be output

Maximum — Upper Limit (F012)

when operating in the PID Control mode, Torque Control mode, or the

Units — Hz

 

Vector Control modes (sensorless or feedback).

 

 

 

 

 

 

Motor #1 Base Frequency

Direct Access Number —

F014

Program Fundamental Parameters Motor Set #1

Parameter Type — Numerical

The Base Frequency setting determines the frequency at which the output

Factory Default — 60.0

 

Changeable During Run — Yes

voltage of the ASD reaches its maximum setting. The maximum voltage setting

 

 

cannot be more that the input voltage (see Maximum Output Voltage at

Minimum — 25.0

 

F306). There are four Base Frequency profile settings: #1 – #4.

Maximum — 299.0

 

 

 

Note: For proper motor operation, the Base Frequency is normally set

Units — Hz

 

for the name-plated frequency of the motor.

 

 

V/f Pattern

Program Fundamental Parameters Frequency Settings

This function establishes the relationship between the output frequency and the output voltage.

Settings:

Constant Torque

Variable Torque Automatic Torque Boost Sensorless Vector Control (speed)

Auto Torque Boost with Automatic Energy Savings

Sensorless Vector Control (speed) with Automatic Energy Savings V/f 5-Point Setting (opens 5-point setting screen)

Sensorless Vector Control (speed/torque switching) PG Feedback Vector Control (speed/torque switching) PG Feedback Vector Control (speed/position switching)

Direct Access Number — F015

Parameter Type — Selection List

Factory Default — Constant Torque

Changeable During Run — No

Note: For proper operation, the carrier frequency must be 2.2 kHz or above except when operating in the Constant Torque, Variable Torque, or the 5-Point Setting modes.

The Automatic Torque Boost and the Sensorless Vector Control selections use the motor tuning parameters of the drive to properly configure the ASD for the motor being used. If Load Reactors or Long Lead Filters are used, or if the capacity of the ASD is greater than the motor, manual tuning of the motor parameters may be required for optimum performance.

64

G7 ASD Operation Manual

Page 70