92 G7 ASD Operation Manual
VI/II Speed Reference Setpoint #1 (%)
Program Frequency Setting Parameters Speed Reference
Setpoints VI/II
This parameter is used to set the gain and bias o f the VI/II input terminals w hen
either terminal is used as the control input while operating in the Speed
Control or the Torque Control mode.
Note: See note on pg. 46 for further information on the VI/II terminal.
Perform the following setup to allow the system to receive control input at the
VI/II terminals:
•Program Fundamental Parameters Standard Mode Selection
Command Mode Use Control Terminal Strip.
•Program Fundamental Parameters Standard Mode Selection
Frequency Mode #1 Use VI/II.
Provide a Run command (F or R).
Gain and Bias Settings
When operating in the Speed Control mode, the settings that determine the
gain and bias of the VI/II terminals are:
VI/II Speed Reference Setpoint #1 (frequenc y) (F202),
•the VI/II input signal level that represents VI/II Speed Reference
Setpoint #1 (frequency): F201,
VI/II Speed Reference Setpoint #2 (frequency) (F204), and
•the VI/II input signal level that represents VI/II Speed Reference
Setpoint #2 (frequency): F203.
When operating in the Torque Control mode, the settings that de termine the
gain and bias of the VI/II terminals are:
Torque Reference Setpoint #1 (%) (F205),
•the VI/II input signal level that represents the VI/II Torque
Reference Setpoint #1 (%): F201,
Torque Reference Setpoint #2 (%) (F206),
•the VI/II input signal level that represents Torque Reference
Setpoint #2 (%): F203.
Once set, as the VI/II input changes, the output frequency or the output torque
of the drive will vary in accordance wi th the above settings.
This parameter sets the VI/II input level that represents VI/II Speed Reference
Setpoint #1 (torque or frequency). This value is entered as 0 – 100% of the
VI/II input signal range.
The input signal may be trimmed using F470 (Bias) and F471 (Gain).
The default value f or this parameter ( F201) is 20%. The II input is commonly
used for the 4 – 20 mA current loop signal where 4 mA equals 20% of a 20 mA
signal. If the VI input is used (0 – 10 VDC input), parameter F201 may be
changed to 0.0% (of the input signal).
Direct Access Number F201
Parameter Type — Numerical
Factory Default — 20.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0%
Units — %
Frequency Settings
Torque Settings
VI/II Speed Reference Setpoint #1 (frequency)
Program Frequency Setting Parameters Speed Reference
Setpoints VI/II
This parameter is used to set the gain and bias o f the VI/II input terminals w hen
either terminal is used as the control input while operating in the Speed
Control mode.
See F201 for further information on this setting.
This parameter sets VI/II Speed Reference Setpoint #1 (frequency) and is the
frequency that is associated with th e setting of F201.
Direct Access Number F202
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
F201 F202