F201

F202

VI/II Speed Reference Setpoint #1 (%)

Program Frequency Setting Parameters Speed Reference Setpoints VI/II

This parameter is used to set the gain and bias of the VI/II input terminals when either terminal is used as the control input while operating in the Speed Control or the Torque Control mode.

Note: See note on pg. 46 for further information on the VI/II terminal.

Perform the following setup to allow the system to receive control input at the VI/II terminals:

Program Fundamental Parameters Standard Mode Selection Command Mode Use Control Terminal Strip.

Program Fundamental Parameters Standard Mode Selection Frequency Mode #1 Use VI/II.

Provide a Run command (F or R).

Gain and Bias Settings

When operating in the Speed Control mode, the settings that determine the gain and bias of the VI/II terminals are:

VI/II Speed Reference Setpoint #1 (frequency) (F202),

the VI/II input signal level that represents VI/II Speed Reference Setpoint #1 (frequency): F201,

VI/II Speed Reference Setpoint #2 (frequency) (F204), and

the VI/II input signal level that represents VI/II Speed Reference Setpoint #2 (frequency): F203.

When operating in the Torque Control mode, the settings that determine the gain and bias of the VI/II terminals are:

Torque Reference Setpoint #1 (%) (F205),

the VI/II input signal level that represents the VI/II Torque Reference Setpoint #1 (%): F201,

Torque Reference Setpoint #2 (%) (F206),

the VI/II input signal level that represents Torque Reference Setpoint #2 (%): F203.

Direct Access Number — F201

Parameter Type — Numerical

Factory Default — 20.0

Changeable During Run — Yes

Minimum — 0.0

Maximum — 100.0%

Units — %

Frequency Settings

Torque Settings

Once set, as the VI/II input changes, the output frequency or the output torque of the drive will vary in accordance with the above settings.

This parameter sets the VI/II input level that represents VI/II Speed Reference

Setpoint #1 (torque or frequency). This value is entered as 0 – 100% of the

VI/II input signal range.

The input signal may be trimmed using F470 (Bias) and F471 (Gain).

The default value for this parameter (F201) is 20%. The II input is commonly used for the 4 – 20 mA current loop signal where 4 mA equals 20% of a 20 mA signal. If the VI input is used (0 – 10 VDC input), parameter F201 may be changed to 0.0% (of the input signal).

VI/II Speed Reference Setpoint #1 (frequency)

Direct Access Number — F202

Program Frequency Setting Parameters Speed Reference

Parameter Type — Numerical

Setpoints VI/II

Factory Default — 0.0

This parameter is used to set the gain and bias of the VI/II input terminals when

Changeable During Run — Yes

 

either terminal is used as the control input while operating in the Speed

Minimum — 0.0

Control mode.

Maximum — Max. Freq. (F011)

 

See F201 for further information on this setting.

Units — Hz

 

This parameter sets VI/II Speed Reference Setpoint #1 (frequency) and is the

 

frequency that is associated with the setting of F201.

92

G7 ASD Operation Manual

Page 98
Image 98
Toshiba G7 manual VI/II Speed Reference Setpoint #1 %, VI/II Speed Reference Setpoint #1 frequency, Gain and Bias Settings