F429 |
| F433 | |
|
|
|
|
| Torque Command Mode | Direct Access Number — | F429 |
| Program ⇒ Torque Setting Parameters ⇒ Torque Speed Limiting | Parameter Type — Selection List | |
| This parameter specifies whether the torque command function is to be used in | Factory Default — Fixed Direction | |
| Changeable During Run — No | ||
| one direction or both (F/R). | ||
|
|
| |
| Settings: |
|
|
| Fixed Direction |
|
|
| F/R Permitted |
|
|
|
|
|
|
| Speed Limit (torque) Reference | Direct Access Number — | F430 |
| Program ⇒ Torque Setting Parameters ⇒ Torque Speed Limiting | Parameter Type — Selection List | |
| The system has the ability to limit the amount that the speed may vary as a | Factory Default — None |
|
| Changeable During Run — Yes | ||
| function of a changing load while operating in the Torque Control mode. This | ||
|
|
| |
| parameter sets the input terminal that will be used to control the allowable |
|
|
| speed variance. |
|
|
| Settings: |
|
|
| None |
|
|
| VI/II |
|
|
| RR |
|
|
| RX |
|
|
| RX2 (option) |
|
|
| Fixed |
|
|
|
|
|
|
| Speed Limit Torque Level | Direct Access Number — | F431 |
| Program ⇒ Torque Setting Parameters ⇒ Torque Speed Limiting | Parameter Type — Numerical | |
| The system has the ability to limit the amount that the speed may vary as a | Factory Default — 0.00 |
|
| Changeable During Run — Yes | ||
| function of a changing load while operating in the Torque Control mode. This | ||
|
|
| |
| parameter sets the targeted speed. The | Minimum — 0.00 |
|
| setting may be set at F432. | Maximum — Max. Freq. (F011) | |
|
|
Units — Hz
Speed Limit Torque Range
Program ⇒ Torque Setting Parameters ⇒ Torque Speed Limiting
The system has the ability to limit the amount that the speed may vary as a function of a changing load while operating in the Torque Control mode. This parameter sets a
Direct Access Number — F432
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Speed Limit Torque Recovery
Program ⇒ Torque Setting Parameters ⇒ Torque Speed Limiting
The system has the ability to limit the amount that the speed may vary as a function of a changing load while operating in the Torque Control mode. This parameter sets the response time of the system to torque change requirements.
Direct Access Number — F433
Parameter Type — Numerical
Factory Default — 0.20
Changeable During Run — No
Minimum — 0.00
Maximum — 2.50
Units — Seconds
132 | G7 ASD Operation Manual |