F203 | F206 |
VI/II Speed Reference Setpoint #2 (%)
Program ⇒ Frequency Setting Parameters ⇒ Speed Reference Setpoints ⇒ VI/II
This parameter is used to set the gain and bias of the VI/II input terminals when either terminal is used as the control input while operating in the Speed Control or the Torque Control mode.
See F201 for further information on this setting.
This parameter sets the VI/II input level that represents Reference Setpoint #2 (torque or frequency). This value is entered as 0 – 100% of the VI/II input signal range.
Direct Access Number — F203
Parameter Type — Numerical
Factory Default — 100.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — %
VI/II Speed Reference Setpoint #2 (frequency)
Program ⇒ Frequency Setting Parameters ⇒ Speed Reference Setpoints ⇒ VI/II
This parameter is used to set the gain and bias of the VI/II input terminals when either terminal is used as the control input while operating in the Speed Control mode.
See F201 for further information on this setting.
This parameter sets VI/II Speed Reference Setpoint #2 (frequency) and is the frequency that is associated with the setting of F203.
Direct Access Number — F204
Parameter Type — Numerical
Factory Default — 80.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
VI/II Torque Reference Setpoint #1 (%) | Direct Access Number — | F205 | |
Program ⇒ Torque Setting Parameters ⇒ Setpoints ⇒ VI/II | Parameter Type — Numerical | ||
This parameter is used to set the gain and bias of the VI/II input terminals when | Factory Default — 0.0 |
| |
Changeable During Run — Yes | |||
either terminal is used as the control input while operating in the Torque | |||
|
| ||
Control mode. | Minimum — 0.0 |
| |
This is accomplished by establishing an associated V/f output pattern for a | Maximum — 250.0 |
| |
given VI/II input level and motor load. | Units — % |
| |
|
| ||
See F201 for further information on this setting. |
|
| |
This parameter sets Torque Reference Setpoint #1 (%) and is the output |
|
| |
torque value that is associated with the setting of F201. This value is entered as |
|
| |
0 to 250% of the rated torque. |
|
| |
|
|
| |
VI/II Torque Reference Setpoint #2 (%) | Direct Access Number — | F206 | |
Program ⇒ Torque Setting Parameters ⇒ Setpoints ⇒ VI/II | Parameter Type — Numerical | ||
This parameter is used to set the gain and bias of the VI/II input terminals when | Factory Default — 100.0 |
| |
Changeable During Run — Yes | |||
either terminal is used as the control input while operating in the Torque | |||
|
| ||
Control mode. | Minimum — 0.0 |
| |
This is accomplished by establishing an associated V/f output pattern for a | Maximum — 250.0 |
| |
given VI/II input level and motor load. | Units — % |
| |
|
|
See F201 for further information on this setting.
This parameter sets Torque Reference Setpoint #2 (%) and is the output torque value that is associated with the setting of F203. This value is entered as 0 to 250% of the rated torque.
G7 ASD Operation Manual | 93 |