Jog Stop Control

Direct Access Number —

F261

Program Frequency Setting Parameters Jog Settings

Parameter Type — Selection List

This parameter sets the stopping method used while operating in the Jog mode.

Factory Default — Deceleration Stop

Changeable During Run — Yes

 

Settings:

 

 

Deceleration Stop

 

 

Coast Stop

 

 

DC Injection Braking Stop

 

 

 

 

 

Jump Frequency #1

Direct Access Number —

F270

Program Special Control Parameters Jump Frequencies

Parameter Type — Numerical

In conjunction with parameter F271, this parameter establishes a user-defined

Factory Default — 0.00

 

Changeable During Run — Yes

frequency range: the Jump Frequency and a plus-or-minus value. During

 

 

acceleration, the output frequency of the drive will hold at the frequency of the

Minimum — 0.00

 

lower level of the Jump Frequency range until the programmed acceleration

Maximum — Max. Freq. (F011)

ramp reaches the upper level of the Jump Frequency range. Then, the output

Units — Hz

 

frequency of the drive will accelerate to the upper level of the Jump

 

 

 

Frequency range and continue upward as programmed.

 

 

During deceleration, the output frequency of the drive will hold at the

 

 

frequency of the upper level of the Jump Frequency range until the

 

 

programmed deceleration ramp reaches the lower level of the Jump Frequency

 

 

range. Then, the output frequency of the drive will decelerate to the lower level

 

 

of the Jump Frequency range and continue downward as programmed.

 

 

Once set up and enabled, it is on in all control modes.

 

 

User-selected frequencies may be jumped to avoid the negative effects of

 

 

mechanical resonance.

 

 

 

 

 

Jump Frequency #1 Bandwidth

Direct Access Number —

F271

Program Special Control Parameters Jump Frequencies

Parameter Type — Numerical

 

Factory Default — 0.00

 

This parameter establishes a plus-or-minus value for Jump Frequency #1 (see

F270).

Changeable During Run — Yes

Minimum — 0.00

Maximum — 30.00

Units — Hz

Jump Frequency #2

Program Special Control Parameters Jump Frequencies

Same as Jump Frequency #1 (F270) and is used when multiple frequencies are to be jumped (see the plus-or-minus value setting at F273). When multiple jump frequencies overlap, the system will recognize the lowest and the highest frequencies as one jump range.

Direct Access Number — F272

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — Max. Freq. (F011) Units — Hz

Jump Frequency #2 Bandwidth

Direct Access Number — F273

Program Special Control Parameters Jump Frequencies

Parameter Type — Numerical

This parameter establishes a plus-or-minus value for Jump Frequency #2

Factory Default — 0.00

Changeable During Run — Yes

(F272).

Minimum — 0.00

 

 

Maximum — 30.0

 

Units — Hz

108

G7 ASD Operation Manual

Page 114
Image 114