F261 |
| F273 | |
|
|
| |
Jog Stop Control | Direct Access Number — | F261 | |
Program ⇒ Frequency Setting Parameters ⇒ Jog Settings | Parameter Type — Selection List | ||
This parameter sets the stopping method used while operating in the Jog mode. | Factory Default — Deceleration Stop | ||
Changeable During Run — Yes | |||
| |||
Settings: |
|
| |
Deceleration Stop |
|
| |
Coast Stop |
|
| |
DC Injection Braking Stop |
|
| |
|
|
| |
Jump Frequency #1 | Direct Access Number — | F270 | |
Program ⇒ Special Control Parameters ⇒ Jump Frequencies | Parameter Type — Numerical | ||
In conjunction with parameter F271, this parameter establishes a | Factory Default — 0.00 |
| |
Changeable During Run — Yes | |||
frequency range: the Jump Frequency and a | |||
|
| ||
acceleration, the output frequency of the drive will hold at the frequency of the | Minimum — 0.00 |
| |
lower level of the Jump Frequency range until the programmed acceleration | Maximum — Max. Freq. (F011) | ||
ramp reaches the upper level of the Jump Frequency range. Then, the output | |||
Units — Hz |
| ||
frequency of the drive will accelerate to the upper level of the Jump |
| ||
|
| ||
Frequency range and continue upward as programmed. |
|
| |
During deceleration, the output frequency of the drive will hold at the |
|
| |
frequency of the upper level of the Jump Frequency range until the |
|
| |
programmed deceleration ramp reaches the lower level of the Jump Frequency |
|
| |
range. Then, the output frequency of the drive will decelerate to the lower level |
|
| |
of the Jump Frequency range and continue downward as programmed. |
|
| |
Once set up and enabled, it is on in all control modes. |
|
| |
|
| ||
mechanical resonance. |
|
| |
|
|
| |
Jump Frequency #1 Bandwidth | Direct Access Number — | F271 | |
Program ⇒ Special Control Parameters ⇒ Jump Frequencies | Parameter Type — Numerical | ||
| Factory Default — 0.00 |
|
This parameter establishes a
F270).
Changeable During Run — Yes
Minimum — 0.00
Maximum — 30.00
Units — Hz
Jump Frequency #2
Program ⇒ Special Control Parameters ⇒ Jump Frequencies
Same as Jump Frequency #1 (F270) and is used when multiple frequencies are to be jumped (see the
Direct Access Number — F272
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011) Units — Hz
Jump Frequency #2 Bandwidth | Direct Access Number — F273 | |
Program ⇒ Special Control Parameters ⇒ Jump Frequencies | Parameter Type — Numerical | |
This parameter establishes a | Factory Default — 0.00 | |
Changeable During Run — Yes | ||
(F272). | ||
Minimum — 0.00 | ||
| ||
| Maximum — 30.0 | |
| Units — Hz |
108 | G7 ASD Operation Manual |