F604 | F608 |
Emergency Off DC Injection Application Time
Program ⇒ Protection Parameters ⇒ Emergency Off Settings
When DC Injection is used as a function of receiving an Emergency Off command (F603), this parameter determines the time that the DC Injection braking is applied to the motor.
Direct Access Number — F604
Parameter Type — Numerical
Factory Default — 0.10
Changeable During Run — Yes
Minimum — 0.00
Maximum — 10.00
Units — Seconds
Output Phase Loss Detection | Direct Access Number — | F605 | |
Program ⇒ Protection Parameters ⇒ Phase Loss | Parameter Type — Check Box | ||
This parameter Enables/Disables the monitoring of each phase of the | Factory Default — Disabled |
| |
Changeable During Run — No | |||
output signal (U, V, or W) of the ASD. If either line is missing, inactive, or not | |||
|
| ||
of the specified level, the ASD incurs a trip. |
|
| |
Settings: |
|
| |
Disabled |
|
| |
Enabled (box checked) |
|
| |
|
|
| |
OL Reduction Starting Frequency | Direct Access Number — | F606 | |
Program ⇒ Protection Parameters ⇒ Overload | Parameter Type — Numerical | ||
This parameter is used to reduce the start frequency during very | Factory Default — 6.00 |
| |
Changeable During Run — Yes | |||
motor operation. During very | |||
|
| ||
motor decreases. Lowering the start frequency aides in minimizing the | Minimum — 0.00 |
| |
generated heat. | Maximum — 30.00 |
| |
|
| ||
| Units — Hz |
| |
|
|
| |
Motor 150% OL Time Limit | Direct Access Number — | F607 | |
Program ⇒ Protection Parameters ⇒ Overload | Parameter Type — Numerical | ||
This parameter establishes a time that the motor may operate at 150% of its | Factory Default — 600 |
| |
Changeable During Run — Yes | |||
rated current before tripping. This setting applies the time/150% reference to | |||
|
| ||
the individual settings of each motor (e.g., this setting references 150% of the | Minimum — 10 |
| |
F600 setting for the #1 motor). | Maximum — 2400 |
| |
|
| ||
The unit will trip sooner than the time entered here if the overload is greater | Units — Seconds |
| |
than 150%. |
| ||
|
| ||
|
|
| |
Inrush Current Suppression | Direct Access Number — | F608 | |
Program ⇒ Protection Parameters ⇒ Soft Start | Parameter Type — Numerical | ||
| Factory Default — 0.30 |
|
The startup inrush current may be suppressed for up to 2.5 seconds. This
parameter determines the length of the inrush current suppression.
Changeable During Run — No
Minimum — 0.30
Maximum — 2.50
Units — Seconds
Interlock with ST
Program ⇒ Protection Parameters ⇒ Soft Start
This parameter Enables/Disables the
Direct Access Number — F609
Parameter Type — Check Box
Factory Default — Disabled
Changeable During Run — No
G7 ASD Operation Manual | 155 |