Emergency Off DC Injection Application Time

Program Protection Parameters Emergency Off Settings

When DC Injection is used as a function of receiving an Emergency Off command (F603), this parameter determines the time that the DC Injection braking is applied to the motor.

Direct Access Number — F604

Parameter Type — Numerical

Factory Default — 0.10

Changeable During Run — Yes

Minimum — 0.00

Maximum — 10.00

Units — Seconds

Output Phase Loss Detection

Direct Access Number —

F605

Program Protection Parameters Phase Loss

Parameter Type — Check Box

This parameter Enables/Disables the monitoring of each phase of the 3-phase

Factory Default — Disabled

 

Changeable During Run — No

output signal (U, V, or W) of the ASD. If either line is missing, inactive, or not

 

 

of the specified level, the ASD incurs a trip.

 

 

Settings:

 

 

Disabled

 

 

Enabled (box checked)

 

 

 

 

 

OL Reduction Starting Frequency

Direct Access Number —

F606

Program Protection Parameters Overload

Parameter Type — Numerical

This parameter is used to reduce the start frequency during very low-speed

Factory Default — 6.00

 

Changeable During Run — Yes

motor operation. During very low-speed operation the cooling efficiency of the

 

 

motor decreases. Lowering the start frequency aides in minimizing the

Minimum — 0.00

 

generated heat.

Maximum — 30.00

 

 

 

 

Units — Hz

 

 

 

 

Motor 150% OL Time Limit

Direct Access Number —

F607

Program Protection Parameters Overload

Parameter Type — Numerical

This parameter establishes a time that the motor may operate at 150% of its

Factory Default — 600

 

Changeable During Run — Yes

rated current before tripping. This setting applies the time/150% reference to

 

 

the individual settings of each motor (e.g., this setting references 150% of the

Minimum — 10

 

F600 setting for the #1 motor).

Maximum — 2400

 

 

 

The unit will trip sooner than the time entered here if the overload is greater

Units — Seconds

 

than 150%.

 

 

 

 

 

 

Inrush Current Suppression

Direct Access Number —

F608

Program Protection Parameters Soft Start

Parameter Type — Numerical

 

Factory Default — 0.30

 

The startup inrush current may be suppressed for up to 2.5 seconds. This

parameter determines the length of the inrush current suppression.

Changeable During Run — No

Minimum — 0.30

Maximum — 2.50

Units — Seconds

Interlock with ST

Program Protection Parameters Soft Start

This parameter Enables/Disables the ST-to-CCconnection dependency on the successful completion of a Soft Start. If enabled, the ST-to-CCconnection will happen only after a successful Soft Start.

Direct Access Number — F609

Parameter Type — Check Box

Factory Default — Disabled

Changeable During Run — No