G7 ASD Operation Manual 67
Preset Speed #3
Program Pattern Run Control Preset Speeds 3
This parameter assigns an output frequency to binary number 0011 and is
identified as Preset Sp eed #3. The binary number is applied to S1S4 of the
Control Terminal Strip to output the Preset Speed (see F018 for further
information on this parameter).
Direct Access Number — F020
Parameter Type — Numeri cal
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Preset Speed #4
Program Pattern Run Control Preset Speeds 4
This parameter assigns an output frequency to binary number 0100 and is
identified as Preset Sp eed #4. The binary number is applied to S1S4 of the
Control Terminal Strip to output the Preset Speed (see F018 for further
information on this parameter).
Direct Access Number — F021
Parameter Type — Numeri cal
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Preset Speed #5
Program Pattern Run Control Preset Speeds 5
This parameter assigns an output frequency to binary number 0101 and is
identified as Preset Sp eed #5. The binary number is applied to S1S4 of the
Control Terminal Strip to output the Preset Speed (see F018 for further
information on this parameter).
Direct Access Number — F022
Parameter Type — Numeri cal
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Preset Speed #6
Program Pattern Run Control Preset Speeds 6
This parameter assigns an output frequency to binary number 0110 and is
identified as Preset Sp eed #6. The binary number is applied to S1S4 of the
Control Terminal Strip to output the Preset Speed (see F018 for further
information on this parameter).
Direct Access Number — F023
Parameter Type — Numeri cal
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Preset Speed #7
Program Pattern Run Control Preset Speeds 7
This parameter assigns an output frequency to binary number 0111 and is
identified as Preset Sp eed #7. The binary number is applied to S1S4 of the
Control Terminal Strip to output the Preset Speed (see F018 for further
information on this parameter).
Direct Access Number — F024
Parameter Type — Numeri cal
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Low Speed Signal Output Fre quency
Program Terminal Selection Parameters Reach Settings
The Low Speed Signal Output Frequency parameter sets a frequency
threshold that activates the assigned output terminal so long as the ASD output
is at or above this setting (see Table 9 on pg. 81 for the available output
assignments).
Direct Access Number — F100
Parameter Type — Numeri cal
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz