Frequency Control

Selections

The following is a listing and description of the

Frequency Mode (F003) selections (Program

Fundamental Parameters Standard Mode Selection

Frequency Mode #1).

Settings:

Use VI/II

0 to 10-volt DC analog input connected to VI or a 4 – 20 mA (or 0 to 1 mA) DC current connected to

II(cannot use both simultaneously).

Use RR

0 to 10-volt DC analog input connected to RR.

Use RX

-10 to +10-volt DC analog input connected to RX.

Use Option Card RX2

-10 to +10-volt DC analog input connected to RX2.

Use LED Keypad Option

The LED Keypad is unavailable at the time of this release.

Use Binary/BCD Input

Allows for discrete terminal input to control the ASD output.

Use Common Serial (TTL)

To use the EOI for control requires that the LCD Port Connection be set to Common Serial (TTL) to use this feature.

Use RS232/RS485

To use the EOI for control requires that the LCD Port Connection be set to RS232/RS485 to use this feature.

Use Communication Card

Routes the control and monitoring I/O to CNU3 of the Control Board of the G7 ASD (Option Card connector).

Use Motorized Pot Simulation

A discrete terminal may be configured to increase or decrease the speed of the motor by momentarily connecting the assigned terminal to CC. See Table 8 on page 76 for further information on this feature.

Use Pulse Input Option

Configures the system to receive pulse input. See PG Speed Reference Setpoint on pg. 103 for further information on this feature.