F412

F421

 

 

Motor Capacity

Direct Access Number — F412

Program Motor Parameters Motor Settings

Parameter Type — Numerical

This parameter identifies the wattage rating of the motor.

Factory Default — (ASD-dependent)

Changeable During Run — No

 

 

Minimum — 0.10

 

Maximum — (ASD-dependent)

 

Units — kW

 

 

Motor Type

Direct Access Number — F413

Program Motor Parameters Motor Settings

Parameter Type — Selection List

This parameter identifies the type of motor being used.

Factory Default — Toshiba EQP III

TEFC

Settings:

Changeable During Run — No

 

Toshiba EQP III TEFC

 

Toshiba EQP III ODP

 

Toshiba EPACT TEFC

 

Toshiba EPACT ODP

 

Other Motor

 

 

 

Motor Constant 3 Enable

Direct Access Number — F414

Program Motor Parameters Vector Motor Model

Parameter Type — Check Box

This parameter Enables/Disables tuning of Motor Constant 3 during an

Factory Default — Enable

Changeable During Run — No

Autotune.

 

Settings:

 

Disabled

 

Enabled (box checked)

 

 

 

Torque Command

Direct Access Number — F420

Program Torque Setting Parameters Torque Control

Parameter Type — Selection List

When operating in the Torque Control mode, this parameter allows the user to

Factory Default — RX

Changeable During Run — Yes

select the source of the torque command signal.

 

Settings:

 

VI/II

 

RR

 

RX

 

RX2 (option)

 

LED Keypad Option

 

Binary/BCD Input

 

Common Serial (TTL)

 

RS232/RS485

 

Communication Card

 

 

 

Torque Command Filter

Direct Access Number — F421

Program Torque Setting Parameters Torque Control

Parameter Type — Numerical

This parameter reduces the motor vibration caused by large-inertia loads. A

Factory Default — 200.0

Changeable During Run — Yes

small value will have a great effect while an increased value will have a lesser

 

effect.

Minimum — 10.0

 

Maximum — 200.0

G7 ASD Operation Manual

129

Page 135