F412 | F421 | |
|
| |
Motor Capacity | Direct Access Number — F412 | |
Program ⇒ Motor Parameters ⇒ Motor Settings | Parameter Type — Numerical | |
This parameter identifies the wattage rating of the motor. | Factory Default — | |
Changeable During Run — No | ||
| ||
| Minimum — 0.10 | |
| Maximum — | |
| Units — kW | |
|
| |
Motor Type | Direct Access Number — F413 | |
Program ⇒ Motor Parameters ⇒ Motor Settings | Parameter Type — Selection List | |
This parameter identifies the type of motor being used. | Factory Default — Toshiba EQP III | |
TEFC | ||
Settings: | Changeable During Run — No | |
| ||
Toshiba EQP III TEFC |
| |
Toshiba EQP III ODP |
| |
Toshiba EPACT TEFC |
| |
Toshiba EPACT ODP |
| |
Other Motor |
| |
|
| |
Motor Constant 3 Enable | Direct Access Number — F414 | |
Program ⇒ Motor Parameters ⇒ Vector Motor Model | Parameter Type — Check Box | |
This parameter Enables/Disables tuning of Motor Constant 3 during an | Factory Default — Enable | |
Changeable During Run — No | ||
Autotune. | ||
| ||
Settings: |
| |
Disabled |
| |
Enabled (box checked) |
| |
|
| |
Torque Command | Direct Access Number — F420 | |
Program ⇒ Torque Setting Parameters ⇒ Torque Control | Parameter Type — Selection List | |
When operating in the Torque Control mode, this parameter allows the user to | Factory Default — RX | |
Changeable During Run — Yes | ||
select the source of the torque command signal. | ||
| ||
Settings: |
| |
VI/II |
| |
RR |
| |
RX |
| |
RX2 (option) |
| |
LED Keypad Option |
| |
Binary/BCD Input |
| |
Common Serial (TTL) |
| |
RS232/RS485 |
| |
Communication Card |
| |
|
| |
Torque Command Filter | Direct Access Number — F421 | |
Program ⇒ Torque Setting Parameters ⇒ Torque Control | Parameter Type — Numerical | |
This parameter reduces the motor vibration caused by | Factory Default — 200.0 | |
Changeable During Run — Yes | ||
small value will have a great effect while an increased value will have a lesser | ||
| ||
effect. | Minimum — 10.0 | |
| Maximum — 200.0 |
G7 ASD Operation Manual | 129 |