F653

Acc/Dec Base Frequency Adjustment

Program Terminal Selection Parameters Analog Input Functions

This parameter Enables/Disables the feature that allows for the external adjustment of the Base Frequency. When enabled, either VI/II or RR may be used as an input source for the modification of the Base Frequency setting.

Settings:

Disabled

VI/II

RR

Direct Access Number — F650

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — Yes

Upper Limit Frequency Adjustment

Program Terminal Selection Parameters Analog Input Functions

This parameter Enables/Disables the feature that allows for the external adjustment of the Upper Limit. When enabled, either VI/II or RR may be used as an input source for the modification of the Upper Limit setting.

Settings:

Disabled

VI/II

RR

Direct Access Number — F651

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — Yes

Acceleration Time Adjustment

Program Terminal Selection Parameters Analog Input Functions

This parameter Enables/Disables the feature that allows for the external adjustment of the Acceleration Time. Selecting either VI/II or RR enables this feature. The selected input is used as a multiplier of the programmed Acceleration Time setting. The multiplication factor may be from 1 to 10.

Direct Access Number — F652

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — Yes

Note: An acceleration time shorter than the load will allow may cause nuisance tripping and mechanical stress to loads.

Settings:

Disabled

VI/II

RR

Deceleration Time Adjustment

Program Terminal Selection Parameters Analog Input Functions

This parameter Enables/Disables the feature that allows for the external adjustment of the Deceleration Time. Selecting either VI/II or RR enables this feature. The selected input is used as a modifier of the programmed Deceleration Time setting.

Direct Access Number — F653

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — Yes

Note: A deceleration time shorter than the load will allow may cause nuisance tripping and mechanical stress to loads.

Settings:

Disabled

VI/II

RR