F305

F309

Overvoltage Stall

Program Protection Parameters Stall

This parameter Enables/Disables the Overvoltage Stall function. When enabled, this function causes the drive to extend the decel time when the DC bus voltage increases due to transient voltage spikes, regeneration, supply voltage out of specification, etc. in an attempt to reduce the bus voltage.

Settings:

Enabled

Disabled

Enabled (Forced Shorted Deceleration)

Direct Access Number — F305

Parameter Type — Selection List

Factory Default — Enabled

Changeable During Run — Yes

Motor #1 Max Output Voltage

Direct Access Number —

F306

Program Motor Parameters Motor Set #1

Parameter Type — Numerical

This parameter sets the maximum value of the output voltage of the drive. The

Factory Default — (ASD dependent)

Changeable During Run — Yes

Motor #1 Maximum Output Voltage is the Motor #1 output voltage at the

 

 

Base Frequency (F014). Regardless of the programmed value, the output

Minimum — 0.0

 

voltage cannot be higher than the input voltage.

Maximum — 600.0

 

 

 

The actual output voltage will be influenced by the input voltage of the ASD

Units — Volts

 

and the Supply Voltage Compensation setting (F307).

 

 

 

 

 

 

Supply Voltage Compensation

Direct Access Number —

F307

Program Protection Parameters Base Frequency Voltage

Parameter Type — Check Box

This parameter Enables/Disables the Voltage Compensation function. This

Factory Default — Enabled

 

Changeable During Run — No

function provides an output waveform adjustment that compensates for changes

 

 

in the input voltage.

 

 

Settings:

 

 

Box checked (Enabled)

 

 

Box not checked (Disabled)

 

 

 

 

 

Dynamic Braking Resistance

Direct Access Number —

F308

Program Protection Parameters Dynamic Braking

Parameter Type — Numerical

This parameter is used to input the resistive value of the Dynamic Braking

Factory Default — (ASD-dependent)

Changeable During Run — No

Resistor.

 

 

For additional information on selecting the proper resistance value for a given

Minimum — 1.0

 

 

 

application contact Toshiba’s Marketing Department.

Maximum — 1000.0

 

Note: Using a resistor value that is too low may result in system

Units —

 

 

 

damage.

Dynamic Braking Resistance Capacity

Program Protection Parameters Dynamic Braking

This parameter is used to input the wattage of the Dynamic Braking Resistor.

For additional information on selecting the proper resistor wattage value for a given application contact Toshiba’s Marketing Department.

Note: Using a resistor with a wattage rating that is too low may result in system damage.

Direct Access Number — F309

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — No

Minimum — 0.01

Maximum — 600.0

Units — kW

G7 ASD Operation Manual

113