F305 | F309 |
Overvoltage Stall
Program ⇒ Protection Parameters ⇒ Stall
This parameter Enables/Disables the Overvoltage Stall function. When enabled, this function causes the drive to extend the decel time when the DC bus voltage increases due to transient voltage spikes, regeneration, supply voltage out of specification, etc. in an attempt to reduce the bus voltage.
Settings:
Enabled
Disabled
Enabled (Forced Shorted Deceleration)
Direct Access Number — F305
Parameter Type — Selection List
Factory Default — Enabled
Changeable During Run — Yes
Motor #1 Max Output Voltage | Direct Access Number — | F306 | |
Program ⇒ Motor Parameters ⇒ Motor Set #1 | Parameter Type — Numerical | ||
This parameter sets the maximum value of the output voltage of the drive. The | Factory Default — (ASD dependent) | ||
Changeable During Run — Yes | |||
Motor #1 Maximum Output Voltage is the Motor #1 output voltage at the | |||
|
| ||
Base Frequency (F014). Regardless of the programmed value, the output | Minimum — 0.0 |
| |
voltage cannot be higher than the input voltage. | Maximum — 600.0 |
| |
|
| ||
The actual output voltage will be influenced by the input voltage of the ASD | Units — Volts |
| |
and the Supply Voltage Compensation setting (F307). |
| ||
|
| ||
|
|
| |
Supply Voltage Compensation | Direct Access Number — | F307 | |
Program ⇒ Protection Parameters ⇒ Base Frequency Voltage | Parameter Type — Check Box | ||
This parameter Enables/Disables the Voltage Compensation function. This | Factory Default — Enabled |
| |
Changeable During Run — No | |||
function provides an output waveform adjustment that compensates for changes | |||
|
| ||
in the input voltage. |
|
| |
Settings: |
|
| |
Box checked (Enabled) |
|
| |
Box not checked (Disabled) |
|
| |
|
|
| |
Dynamic Braking Resistance | Direct Access Number — | F308 | |
Program ⇒ Protection Parameters ⇒ Dynamic Braking | Parameter Type — Numerical | ||
This parameter is used to input the resistive value of the Dynamic Braking | Factory Default — | ||
Changeable During Run — No | |||
Resistor. | |||
|
| ||
For additional information on selecting the proper resistance value for a given | Minimum — 1.0 |
| |
|
| ||
application contact Toshiba’s Marketing Department. | Maximum — 1000.0 |
| |
Note: Using a resistor value that is too low may result in system | Units — Ω |
| |
|
|
damage.
Dynamic Braking Resistance Capacity
Program ⇒ Protection Parameters ⇒ Dynamic Braking
This parameter is used to input the wattage of the Dynamic Braking Resistor.
For additional information on selecting the proper resistor wattage value for a given application contact Toshiba’s Marketing Department.
Note: Using a resistor with a wattage rating that is too low may result in system damage.
Direct Access Number — F309
Parameter Type — Numerical
Factory Default —
Changeable During Run — No
Minimum — 0.01
Maximum — 600.0
Units — kW