F804

 

F806

 

 

 

RS232/RS485 Communications Time-Out Action

Direct Access Number —

F804

Program Communication Setting Parameters Communication

Parameter Type — Selection List

Settings

Factory Default — Trip

 

This parameter plays a role in the setup of the communications network by

Changeable During Run — Yes

 

 

determining the action to be taken in the event of a time-out (Time-Out

 

 

Action).

 

 

The communications network includes other ASDs and Host/Control computers

 

 

that monitor the status of the ASD(s), transfers commands, and loads or

 

 

modifies the parameter settings of the drive.

 

 

Changes made to this parameter require that the power be cycled (Off then On)

 

 

for the changes to take effect.

 

 

Settings:

 

 

No Action

 

 

Alarm

 

 

Trip

 

 

 

 

 

Communication Interval

Direct Access Number —

F805

Program Communication Setting Parameters Communication

Parameter Type — Numerical

Settings

Factory Default — 0.00

 

This parameter sets the Common Serial response delay time.

Changeable During Run — Yes

 

 

 

Minimum — 0.00

 

Changes made to this parameter require that the power be cycled (Off then On)

Maximum — 2.00

 

for the changes to take effect.

 

Units — Seconds

 

 

 

 

 

 

TTL Master Output

Direct Access Number —

F806

Program Communication Setting Parameters Communication

Parameter Type — Selection List

Settings

Factory Default — No Follower (normal

 

operation)

 

In a master/follower configuration, this setting determines the output parameter

of the master ASD that will be used to control the applicable follower ASDs.

Note: Select No Follower if F826 is configured as a Master Output controller. Otherwise, an EOI failure will result.

Changeable During Run — Yes

Changes made to this parameter require that the power be cycled (Off then On) for the changes to take effect.

Settings:

No Follower (normal operation)

Frequency Reference

Output Command Frequency

Torque Command

Output Torque Command

G7 ASD Operation Manual

169

Page 175
Image 175